| 1 | Schedule 1 (Supply of Material) |
| 2 | Schedule 2 (Erection of Material) |
| 3 | Schedule 3 (Civil Works) |
| 4 | Design, Engineering. Manufacture,workshop testing, supply including packing and forwarded, transportation, delivery of Material & Accessories at site storage charges of;- |
| 5 | Main Equipment |
| 6 | 3 Pole , SF6 Circuit Breaker out door circuit breakers with operating mechanism, all accessories, auxiliaries and marshalling boxes / kiosks, SF6 Gas (first filling plus 10 Kg. cylinder additional) alongwith supporting structures etc. complete in all respects as specified in the technical specification mentioned in SBD (72.5KV, 2000 Amps of 3 phase, 50 C/s and 31.5KA(rms) for 3 sec) Complete in all respects in allign with the existing system set-up. |
| 7 | 72.5 kV, 50 c/s, 1250 Amps, SCADA compatible, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (With one Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 8 | 72.5 kV, 50 c/s, 1250 Amps, SCADA compatible, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (Without Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 9 | 72.5 kV, 50 c/s, 1250 Amps, SCADA compatible, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (With Two Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 10 | Single phase, 50 c/s Current Transformers including first fill of transformer oil plus 10% extra and all accessories, auxiliaries etc. complete in all respects as specified in the specification mentioned in SBD (72.5KV) (1250-625/1-1-1 A) Complete in all respects in allign with the existing system set-up. |
| 11 | Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification mentioned in SBD (54 KV) Complete in all respects in allign with the existing system set-up. |
| 12 | 66 KV Control and Relay Panel for 66 KV Line Bay completely wired & SCADA Compatible including Substation automation supporting IEDs/numerical relays Complete in all respects in allign with the existing system set-up. |
| 13 | Post Insulators complete in all respects as specified in the technical specification mentioned in SBD (70 KV) Complete in all respects in allign with the existing system set-up. |
| 14 | Single phase, 50 c/s 66KV Capacitor Voltage Transformers (66/√3) KV/(110/√3)V , One min power freq withstand KVrms Complete in all respects in allign with the existing system set-up. |
| 15 | STRUCTURES |
| 16 | Galvanised Structures |
| 17 | Galvanised Nuts and Bolts |
| 18 | POWER AND CONTROL CABLES |
| 19 | 2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 20 | 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 21 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 22 | 10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 23 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 24 | 2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 25 | 4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 26 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns. |
| 27 | CONDUCTOR AND HARD WARE FITTINGS (Line Bay and Bus Bar Extension) |
| 28 | IPS 4\\" AI tube, OD 120mm, ID 100mm, wall thickness 10mm, weight 9.33kg/m |
| 29 | 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel=7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN |
| 30 | Single tension Fittings For Twin moose 500 mm2 shall have minimum failing load of 100% ultimate strength of bundle conductors with compressive type tension clamps having slipping strength 95% of ultimate strength of conductor.The ball and socket designation must be 20 mm. Minimum ultimate strength ( Tensile strength) shall be 120KN. |
| 31 | Single Suspension Fittings For Twin 500 mm2 shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20 mm |
| 32 | Double tension Fittings For Quad moose 500 mm2 shall have minimum failing load of 100% ultimate strength of bundle conductors with compressive type tension clamps having slipping strength 95% of ultimate strength of conductor.The ball and socket designation must be 20 mm. Minimum ultimate strength ( Tensile strength) shall be 120KN. |
| 33 | Long rod polymer insulator 90KN light weight 66KV |
| 34 | Long rod polymer insulator 120KN light weight 66KV |
| 35 | T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 36 | T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 37 | T- Connector for Moose ACSR through (Quad) Moose TEE OFF(Twin) and shall comply in all respects with IS:5561-1970 (latest edition) |
| 38 | T-Connector suitable for 4\\" tube with twin moose conductor |
| 39 | Expansion/Flexible connector for circuit breaker suitable for 4\\" AI Tube |
| 40 | Twin Pad Clamp for circuit breaker |
| 41 | Isolator clamp for twin moose |
| 42 | Flexible connector for isolator suitable for 4\\" AI Tube |
| 43 | Rigid connector for isolator suitable for 4\\" AI Tube |
| 44 | Rigid terminal connector for BPI suitable for 4\\" AI Tube |
| 45 | Terminal connector for LA(54KV) suitable to Twin Moose ACSR |
| 46 | Rigid connector for CT suitable for 4\\" Aluminium Tube |
| 47 | PT clamp suitable for Twin Moose ACSR Conductor |
| 48 | Spacers For Twin 500mm2 ACSR Conductor |
| 49 | Spacers For Quad 500mm2 ACSR Conductor |
| 50 | Terminal Connector for BPI suitable to Twin Moose ACSR Conductor |
| 51 | P G Clamps/connectors made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 52 | Earthwire 7/3.15 mm,3.41 ohms/km max.d.c. resistance galvanized steel earth strand at 20ºC , 56KN ultimate tensile strength, 11.5x10-6 ºC Coefficient of linear expansion. |
| 53 | Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire |
| 54 | CABLE TRAYS/CABLE RACKS/ACCESSORIES |
| 55 | Cable Trays of size 400mm x 3000 mm made of M.S angles 40x40x6mm, 40x6 Flat. |
| 56 | Cable Trays of size 300mm x 2500 mm made of M.S angles 40x40x6mm, 40x6 Flat. |
| 57 | Lugs, Ferrules, Welding Material, Cotton Waste etc |
| 58 | Supply of equipments for Line Bay (SAS) |
| 59 | Complete Automation System for 01no. 66KV Line Bay including hardware and software along with all I/O modules, communication modules, interfacing equipments, required converters and all other required items/accessories/ optical fibres etc.including complete wiring of all modules (complete job) for integration of 01no. 66KV new Line Bay into the existing system by GE. |
| 60 | 66KV BCU IN SCADA |
| 61 | Miscellaneous items |
| 62 | Air conditioning system for Switchyard Panel Room of 6m length(FCU) in allign with existing system |
| 63 | Air conditioning system for Control and Relay Panel Room as per specifications: 2 Ton Inverter Split AC (5 Star Rating, Copper and Smart view display) of reputed make like LG, Daikin, O General, Hitachi etc. |
| 64 | 3 phase,4 wire,0.2s accuracy class Trivector static Energy Meters (compatible to various protocols like TCP/IP, MODBUS, ICS DLMS etc) for Energy accounting. |
| 65 | Carbondioxide type Fire Fighting equipment |
| 66 | Fire Detection and alarm for SPR with integration of same into existing system |
| 67 | Spare Items |
| 68 | 3 Pole, SF6 Circuit Breaker out door circuit breakers with operating mechanism, all accessories, auxiliaries and marshalling boxes / kiosks, SF6 Gas (first filling plus 10 Kg. cylinder additional) alongwith supporting structures etc. complete in all respects as specified in the technical specification mentioned in SBD (72.5KV, 2000 Amps of 3 phase, 50 C/s and 31.5KA(rms) for 3 sec) Complete in all respects in allign with the existing system set-up. |
| 69 | 72.5 kV, 50 c/s, 1250 Amps, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (With Two Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 70 | Single phase, 50 c/s Current Transformers including first fill of transformer oil plus 10% extra and all accessories, auxiliaries etc. complete in all respects as specified in the specification mentioned in SBD (72.5KV (1250-625/1-1-1 A) Complete in all respects in allign with the existing system set-up. |
| 71 | Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification mentioned in SBD (54 KV) Complete in all respects in allign with the existing system set-up. |
| 72 | Post Insulators complete in all respects as specified in the technical specification mentioned in SBD (70 KV) Complete in all respects in allign with the existing system set-up. |
| 73 | Single phase, 50 c/s 66KV Capacitor Voltage Transformers (66/√3) KV/(110/√3)V , One min power freq withstand KVrms Complete in all respects in allign with the existing system set-up.system. |
| 74 | Handling, transportation, delivery at site, erection work, testing and commisssioning of various type of tower including leg extension complete with Nuts & bolts including tag welding and fixing of tower accessories. |
| 75 | Main Equipment |
| 76 | 3 Pole , SF6 Circuit Breaker out door circuit breakers with operating mechanism, all accessories, auxiliaries and marshalling boxes / kiosks, SF6 Gas (first filling plus 10 Kg. cylinder additional) alongwith supporting structures etc. complete in all respects as specified in the technical specification mentioned in SBD (72.5KV, 2000 Amps of 3 phase ,50 C/s and 31.5KA(rms) for 3 sec) Complete in all respects in allign with the existing system set-up. |
| 77 | 72.5 kV, 50 c/s, 1250 Amps, SCADA compatible, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (With one Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 78 | 72.5 kV, 50 c/s, 1250 Amps, SCADA compatible, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (Without Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 79 | 72.5 kV, 50 c/s, 1250 Amps, SCADA compatible, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD (With Two Earthing Blades) Complete in all respects in allign with the existing system set-up. |
| 80 | Single phase, 50 c/s Current Transformers including first fill of transformer oil plus 10% extra and all accessories, auxiliaries etc. complete in all respects as specified in the specification mentioned in SBD (72.5KV) (1250-625/1-1-1 A) Complete in all respects in allign with the existing system set-up. |
| 81 | Single phase, 50 c/s, outdoor, metal oxide gapless type arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification mentioned in SBD (54 KV) Complete in all respects in allign with the existing system set-up. |
| 82 | 66 KV Control and Relay Panel for 66 KV Line Bay completely wired & SCADA Compatible including Substation automation supporting IEDs/numerical relays Complete in all respects in allign with the existing system set-up. |
| 83 | Post Insulators complete in all respects as specified in the technical specification mentioned in SBD (70 KV) Complete in all respects in allign with the existing system set-up. |
| 84 | Single phase, 50 c/s 66KV Capacitor Voltage Transformers (66/√3) KV/(110/√3)V , One min power freq withstand KVrms Complete in all respects in allign with the existing system set-up. |
| 85 | STRUCTURES |
| 86 | Galvanised Structures |
| 87 | Galvanised Nuts and Bolts |
| 88 | POWER AND CONTROL CABLES |
| 89 | 2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 90 | 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 91 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 92 | 10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 93 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 94 | 2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 95 | 4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,galvanised steel wire/ strip armoured stranded copper conductor control cable complete |
| 96 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns. |
| 97 | CONDUCTOR AND HARD WARE FITTINGS (Line Bay and Bus Bar Extension) |
| 98 | IPS 4\\" AI tube, OD 120mm, ID 100mm, wall thickness 10mm, weight 9.33kg/m |
| 99 | 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel=7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN |
| 100 | Single tension Fittings For Twin moose 500 mm2 shall have minimum failing load of 100% ultimate strength of bundle conductors with compressive type tension clamps having slipping strength 95% of ultimate strength of conductor.The ball and socket designation must be 20 mm. Minimum ultimate strength (Tensile strength) shall be 120KN. |
| 101 | Single Suspension Fittings For Twin 500 mm2 shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20 mm |
| 102 | Double tension Fittings For Quad moose 500 mm2 shall have minimum failing load of 100% ultimate strength of bundle conductors with compressive type tension clamps having slipping strength 95% of ultimate strength of conductor.The ball and socket designation must be 20 mm. Minimum ultimate strength ( Tensile strength) shall be 120KN. |
| 103 | Long rod polymer insulator 90KN light weight 66KV |
| 104 | Long rod polymer insulator 120KN light weight 66KV |
| 105 | T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 106 | T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 107 | T- Connector for Moose ACSR through (Quad) Moose TEE OFF(Twin) and shall comply in all respects with IS:5561-1970 (latest edition) |
| 108 | T-Connector suitable for 4\\" tube with twin moose conductor |
| 109 | Expansion/Flexible connector for circuit breaker suitable for 4\\" AI Tube |
| 110 | Twin Pad Clamp for circuit breaker |
| 111 | Isolator clamp for twin moose |
| 112 | Flexible connector for isolator suitable for 4\\" AI Tube |
| 113 | Rigid connector for isolator suitable for 4\\" AI Tube |
| 114 | Rigid terminal connector for BPI suitable for 4\\" AI Tube |
| 115 | Terminal connector for LA(54KV) suitable to Twin Moose ACSR |
| 116 | Rigid connector for CT suitable for 4\\" Aluminium Tube |
| 117 | PT clamp suitable for Twin Moose ACSR Conductor |
| 118 | Spacers For Twin 500mm2 ACSR Conductor |
| 119 | Spacers For Quad 500mm2 ACSR Conductor |
| 120 | P I Clamps twin made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 121 | P G Clamps/connectors made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 122 | Earthwire 7/3.15 mm,3.41 ohms/km max.d.c. resistance galvanized steel earth strand at 20ºC , 56KN ultimate tensile strength, 11.5x10-6 ºC Coefficient of linear expansion. |
| 123 | Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire |
| 124 | CABLE TRAYS/CABLE RACKS/ACCESSORIES |
| 125 | Cable Trays of size 400mm x 3000 mm made of M.S angles 40x40x6mm, 40x6 Flat. |
| 126 | Cable Trays of size 300mm x 2500 mm made of M.S angles 40x40x6mm, 40x6 Flat. |
| 127 | Lugs, Ferrules, Welding Material, Cotton Waste etc |
| 128 | Testing and commissioning of equipments for Line Bay (SAS) |
| 129 | Complete Automation System for 01no. 66KV Line Bay including hardware and software along with all I/O modules, communication modules, interfacing equipments, required converters and all other required items/accessories/ optical fibres etc.including complete wiring of all modules (complete job) for integration of 01no. 66KV new Line Bay into the existing system by GE. |
| 130 | 66KV BCU IN SCADA |
| 131 | Miscellaneous items |
| 132 | Air conditioning system for Switchyard Panel Room of 6m length(FCU) in allign with existing system |
| 133 | Air conditioning system for Control and Relay Panel Room as per specifications: 2 Ton Inverter Split AC (5 Star Rating, Copper and Smart view display) of reputed make like LG, Daikin, O General, Hitachi etc. |
| 134 | 3 phase,4 wire,0.2s accuracy class Trivector static Energy Meters (compatible to various protocols like TCP/IP, MODBUS, ICS DLMS etc) for Energy accounting. |
| 135 | Carbondioxide type Fire Fighting equipment |
| 136 | Fire Detection and alarm for SPR with integration of same into existing system |
| 137 | Comprehensive servicing of 125 KVA DG Set |
| 138 | Civil works for Cable Ducts With Covers as per approved drawings and instruction of engineer incharge. |
| 139 | Main Duct of Size 1200mm x 1200mm with 6 mm M.S Chequered Trench Covers of size 1300x500 mm |
| 140 | Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M15 of size 1300x500 mm M15 of size 1300x500 mm |
| 141 | Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M15 of size 700x500 mm |
| 142 | Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area |
| 143 | Earth Mat (40mm dia steel bars) as per approved design and existing layout, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing including Earth pit for LA, PT & Tower structure etc as per layout.Complete Job |
| 144 | Concreting of yard & Laying Of Gravel |
| 145 | Civil works for foundation as per approved drawings and instruction of engineer incharge. |
| 146 | Laying of 66KV Column foundations (as per Drawing) |
| 147 | Laying of 66KV Isolator foundations (as per Drawing) |
| 148 | Laying of 66KV SF6 Breaker foundations (as per Drawing) |
| 149 | Laying of 66KV CT foundations (as per Drawing) |
| 150 | Laying of 66KV LA foundations (as per Drawing) |
| 151 | Laying of 66KV PT foundations (as per Drawing) |
| 152 | Laying of 66KV Post Insulator foundations (as per Drawing) |
| 153 | Civil works for Switchyard Panel Room (SPR) |
| 154 | Switchyard Panel Room (SPR)-all civil works as per drawing and specification complete- brickwork, finishing ( external and internal windows etc including excavation, PCC, RCC and reinforcement as per BPS ( Complete job) including electrical work as per the existing SPR Layout Please Enable Macros to View BoQ information |