| Sl. No. | Item Description |
| 1 | H.S.R. Item |
| 2 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100Vgrade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make:Finolex / Havells / RR Cables. (95Sqmm size) |
| 3 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 30HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth ault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Jeetuwala Johar) |
| 4 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 10HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-Jagarti Nagar) |
| 5 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 3HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-Jagarti Nagar) |
| 6 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 70Sqmm size |
| 7 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 25Sqmm size |
| 8 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 16Sqmm size |
| 9 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 150 Sqmm size |
| 10 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 185 Sqmm size |
| 11 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 35Sqmm size |
| 12 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 10Sqmm size. |
| 13 | COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2Outer Sheathed, /1100V grade as per IS 7098(Part 1) 1988with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-incharge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables. 50Sqmm size |
| 14 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 12.50HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS- Defence Colony) |
| 15 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 30HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required (For IPS-Govt. College) |
| 16 | Credit of existing outlived Panel Boards and cables etc. IPS- JAGARTI NAGAR - 20HP (1NO.)IPS- JAGARTI NAGAR - 15HP (1NO.)IPS- JAGARTI NAGAR - 12.5HP (1NO.) IPS - AUTO MARKET - 35HP (1NO.)IPS - AUTO MARKET - 20HP (2NO.) IPS - AUTO MARKET - 17.5HP (2NO.) IPS - GOVT. COLLEGE - 40HP (2NO.)IPS - GOVT. COLLEGE - 30HP (1NO.)MPS - MINI SECRETRIAT - 100HP (3NO.) MPS - MINI SECRETRIAT - 75HP (2NO.)IPS - DEFENCE COLONY - 20HP (2NO.)MPS - DHANA ROAD - 125HP (1NO.) MPS - DHANA ROAD - 60HP (2NO.) |
| 17 | Credit of existing outlived pump sets.IPS- JAGARTI NAGAR - 20HP (1NO.)IPS- JAGARTI NAGAR - 15HP (1NO.)IPS- JAGARTI NAGAR - 12.5HP (1NO.) IPS - AUTO MARKET - 35HP (1NO.)IPS - AUTO MARKET - 20HP (2NO.) IPS - AUTO MARKET - 17.5HP (2NO.) IPS - GOVT. COLLEGE - 40HP (2NO.)IPS - GOVT. COLLEGE - 30HP (1NO.)MPS - MINI SECRETRIAT - 100HP (3NO.) MPS - MINI SECRETRIAT - 75HP (2NO.)IPS - DEFENCE COLONY - 20HP (2NO.)MPS - DHANA ROAD - 125HP (1NO.) MPS - DHANA ROAD - 60HP (2NO.) |
| 18 | Boring /excavation including pit making at entry and exit point to the precise dimensions for the Launch of the specialized Auger boring machine in normal soil condition but not in Rock/Bolders/ any underground utility like foundation, water supply line coming in alignment or other underground obstructions complete in all respect including caution sign boards, signals, watching fencing, site clearance etc. Including provision for probe radar survey to check any underground obstruction before finalizing the alignment. For 500mm i/d MS casing pipe. |
| 19 | Providing and insertion of 500mm i/d M.S. casing pipe 8mm thick (Fe-330grade) fabricated as per IS: 3589of 1991from steel plates conforming to IS 2062including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work complete in all respect as per specification given in DNIT. 500mm i/d MS casing pipe |
| 20 | Providing and insertion of 350mm i/d M.S. carrier pipe 8mm thick (Fe-330grade) fabricated as per IS: 3589of 1991from steel plates conforming to IS 2062including cutting, beveling, grinding and radio graphically welding of pipes as per IS-1182and also coating of inner and outer surface of casing pipe with high built epoxy paint as per R.D.S.O. specification No. MandC/PCN.III/88to a dry film thickness of 250 micron for protection against corrosion including cost and cartage of material to site of work and HDPE special complete in all respect as per specification given in DNIT. Providing concrete block 1:1-1/2:3on both ends to plug the space between casing and carrier pipe including all material and labour complete in all respect to the entire satisfaction of Engineer in charge350mm i/d MS carrier pipe |
| 21 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 25HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoH, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS Ninan) |
| 22 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 70HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS Ninan) |
| 23 | Supplying, Installation, Testing and Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV plus or better norms along with having Prime Power Rating of KVA as below, 415volts at 1500RPM, 0.8lagging power factor at 415V suitable for 50Hz, 3phase system, including testing at factory and site with fuel, load for test and other necessary arrangements with rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Turbocharged Diesel engine 4stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500RPM suitable for above output of alternator at 40Deg C, 50%RH and at 1000Meter MSL , capable of taking 10%over loading for one hour after 12hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV plus or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018. (B) Engine mounted Instrument Panel fitted with and having digital display for following: (As per HSR, Gazette notification no. 15-2026Dated on: 13April 2026)(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubrication Oil trip indication(ix) Engine Running Hours indication (x) Fuel Level` (C) Alternator: Synchronous alternator rated of appropriate KVA, 415volts at 1500RPM, 3phase 50Hz, AC supply with 0.8lagging power factor at 40 0C, 50%RH and at 1000Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10%over loading for one hour after 12hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613suitable for tropical conditions and with class- H insulation. (D) Base Frame and Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. (E) FUEL TANK: Daily service fuel tank of suitable liters capacity, fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications and accessories as required as per specifications. (F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. (G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof and dust-proof conforming to IP-65protection. The enclosure shall be as per CPCB IV plus or better norms etc. and.`(I) AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto bypass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering and protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase and Total), KW and provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software etc. as per approved by Engineering in charge and including the following: 1. Suitable numbers and appropriate capacity 4pole motorised electrically operated draw out with cradle type 3position ACB/ MCCB with electronic release for O/C and E/F and shunt trip.2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2nos Over voltage relay, 2Nos. reverse power relay and 2Nos. under voltage relay).4. 3Sets of current transformers 15P 10accuracy for protection and 15VA class-I for metering5. Energy analyser unit to indicate current, Voltage( LN and L_L), kW, kVA (Phase and Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set7. Fuse/ MCB for instruments8. Battery charger, complete with transformer/ rectifier,D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor10. Supply failure timer11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility.14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories17. Maintenance notification based on Engine Run Hour and due date.18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.19. Suitable rating of AC contactors/ ATS / ACB with control wiring. 50KVA |
| 24 | Supplying, Installation, Testing and Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV plus or better norms along with having Prime Power Rating of KVA as below, 415volts at 1500RPM, 0.8lagging power factor at 415V suitable for 50Hz, 3phase system, including testing at factory and site with fuel, load for test and other necessary arrangements with rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Turbocharged Diesel engine 4stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500RPM suitable for above output of alternator at 40Deg C, 50%RH and at 1000Meter MSL , capable of taking 10%over loading for one hour after 12hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV plus or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018. (B) Engine mounted Instrument Panel fitted with and having digital display for following: (As per HSR, Gazette notification no. 15-2026Dated on: 13April 2026)(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubrication Oil trip indication(ix) Engine Running Hours indication (x) Fuel Level(C) Alternator: Synchronous alternator rated of appropriate KVA, 415volts at 1500RPM, 3phase 50Hz, AC supply with 0.8lagging power factor at 40 0C, 50%RH and at 1000Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10%over loading for one hour after 12hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613suitable for tropical conditions and with class- H insulation. (D) Base Frame and Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. (E) FUEL TANK: Daily service fuel tank of suitable liters capacity, fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications and accessories as required as per specifications. (F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. (G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof and dust-proof conforming to IP-65protection. The enclosure shall be as per CPCB IV plus or better norms etc. and.`(I) AMF Panel: Free standing floor mounted IP 42automatic mains failure control panel including auto bypass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering and protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase and Total), KW and provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software etc. as per approved by Engineering in charge and including the following:1. Suitable numbers and appropriate capacity 4pole motorised electrically operated draw out with cradle type 3position ACB/ MCCB with electronic release for O/C and E/F and shunt trip. `2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2nos Over voltage relay, 2Nos. reverse power relay and 2Nos. under voltage relay).4. 3Sets of current transformers 15P 10accuracy for protection and 15VA class-I for metering5. Energy analyser unit to indicate current, Voltage( LN and L_L), kW, kVA (Phase and Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set7. Fuse/ MCB for instruments8. Battery charger, complete with transformer/ rectifier,D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor10. Supply failure timer11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility.14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories17. Maintenance notification based on Engine Run Hour and due date.18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.19. Suitable rating of AC contactors/ ATS / ACB with control wiring. 100KVA |
| 25 | Supplying, Installation, Testing and Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV plus or better norms along with having Prime Power Rating of KVA as below, 415volts at 1500RPM, 0.8lagging power factor at 415V suitable for 50Hz, 3 phase system, including testing at factory and site with fuel, load for test and other necessary arrangements with rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Turbocharged Diesel engine 4stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500RPM suitable for above output of alternator at 40Deg C, 50%RH and at 1000Meter MSL , capable of taking 10%over loading for one hour after 12hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV plus or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018. (B) Engine mounted Instrument Panel fitted with and having digital display for following: (As per HSR, Gazette notification no. 15-2026Dated on: 13April 2026) (i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubrication Oil trip indication(ix) Engine Running Hours indication (x) Fuel Level` (C) Alternator: Synchronous alternator rated of appropriate KVA, 415volts at 1500RPM, 3phase 50Hz, AC supply with 0.8lagging power factor at 40 0C, 50%RH and at 1000Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10%over loading for one hour after 12hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613suitable for tropical conditions and with class- H insulation. (D) Base Frame and Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. (E) FUEL TANK: Daily service fuel tank of suitable liters capacity, fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications and accessories as required as per specifications. (F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. (G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof and dust-proof conforming to IP-65protection. The enclosure shall be as per CPCB IV plus or better norms etc. and.`(I) AMF Panel: Free standing floor mounted IP 42automatic mains failure control panel including auto bypass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering and protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase and Total), KW and provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software etc. as per approved by Engineering in charge and including the following: 1. Suitable numbers and appropriate capacity 4pole motorised electrically operated draw out with cradle type 3position ACB/ MCCB with electronic release for O/C and E/F and shunt trip.2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2nos Over voltage relay, 2Nos. reverse power relay and 2Nos. under voltage relay).4. 3Sets of current transformers 15P 10accuracy for protection and 15VA class-I for metering5. Energy analyser unit to indicate current, Voltage( LN and L_L), kW, kVA (Phase and Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set7. Fuse/ MCB for instruments8. Battery charger, complete with transformer/ rectifier,D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor10. Supply failure timer11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility.14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories17. Maintenance notification based on Engine Run Hour and due date.18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.19. Suitable rating of AC contactors/ ATS / ACB with control wiring |
| 26 | Providing, lowering, laying, cutting, jointing and testing RCC pipe class NP-3 as per IS- 458-2003 with spigot and socketed joints manufactured with ISI marked sulphate resistance cement as per ISI 12330 with 3 mm thick HDPE Lining and manufactured through vertical viberated casting process with rubber rings ISI marked anti termite confirming to IS 5382 as required at site in to trenches for all depths and laying out the same to correct alignment gradients and levels including dressing and trimming and cutting of concrete beds and side of trenches, if required jointing with rubber rings in trenches and jointing with 1:3/2 cement sand mortar and with end dowels filled with 1:3/2 cement sand mortar and finishing the joints at an angle of 45 degree with faces of spigot of socket joints, cutting and finishing the cut surface to a uniform finish etc. as fully described in item No. 21.38, item 21.45, and item 21.46 including cartage loading and unloading complete in all respect, the internal diametre of the sewer being- Note : E/w to be measured and paid separately.(As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 350 mm i/d |
| 27 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 65HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Jeetuwala Johar) |
| 28 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 100 mm dia |
| 29 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 150 mm dia |
| 30 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 200 mm dia |
| 31 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 250 mm dia |
| 32 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 300 mm dia |
| 33 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 400 mm dia |
| 34 | Providing, lowering, laying, aligning, fixing in position and jointing CI dismantling joint (suitable for sluice valves etc.) as per IS specifications with PN 1.6 complete in all respect of the following sizes including all jointing material, cost of all labour, testing and commissioning as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13 April 2026) 450 mm dia |
| 35 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 35HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS- Defence Colony) |
| 36 | Design, Manufacture, Supply, Installation, Testing and Commissioning of Indoor type PLCPanel of size approx. 800mm X 500mm X2000mm (LBH) , Fabricated out of min. 2mm thick CRCA sheet complete with latest configuration, necessary programming software for PLC and SCADA and comprising of all accessories not limited to the following:(As per RUIDP Rajasthan)` DI DO AI AO MCB 16A DP MCB 6A DP SMPS 100-240VAC/ 4.5A / 24VDCSelector Switch (Auto/Manual) and Local / Remote Control Relays `Annunciator with 24Windows NO to NC TypeMicroprocessor Based, Window Size 75*42mm,110VAC, with` Electronic Hooter Control Transformer 200VA Emergency STOP Push Button Panel Cooling Fan and Filter Panel Light with Door Switch, 7W Control Indication Lamp for 24VDC, 220VAC Push Button `Power Wiring plus Control Wiring plus Control TB/ Fuse2A,TB etc` `Panel Hardware, lugs, terminations, ferruls,name plate Ect.` UTILITY SOCKET 16A, 3PIN HMI Display 10Inch, Colour Isolators Dual Output, 24VDC |
| 37 | SIM Card: SIM Cards for five year maintenance of all the instrument above as required. |
| 38 | RTU: Functional Integration at RTU-cum-Gateway for Motorized Control Valve in Pump Control Panel. |
| 39 | Radar and Water Level Transmitter: Supply, Installation, testing, Commissioning with five year maintenance of Radar and Water Level Transmitter along with according to water level in OHSR (for OHSR) Ingress Protection – IP 66, Measuring range – Up to 20M, Process temp.- -40to 60deg. C, Full PVDF Body – For a long sensor lifetime. **Unit Rate given, actual quantity to be ascertained while placing order. |
| 40 | Automation Panel: `Automation Panel for integration with VFD with Pump Control Panel, along with Auto/Manual Selection Switch as well as On/Off push button to be provided. Manual selection between pump 1and pump 2depending on which to be operated and which to be stand by to be provided, along with all relay interlocks and provision of operation of pumps through potential free/open collector digital outputs of RTUcum-Gateway device. The panel will contain RTU-cum-Gateway with necessary I/Os and edge controller Motorized control valve in Local / Remote or Auto/ Manual modes of operation in tandem with Cloud Scheduler or Level sensor-based functions. Panel will contain SMPS with rechargeable battery backup (min. 24hrs.) along with facility to connect all field instruments with 24VDC power supply. |
| 41 | Providing, installation, testing and commissioning of Electromagnetic Flow Meter etc. including all materials (excluding CI/DI fittings) and making connection with existing pipeline required for Electromagnetic Flow Meter including cutting the existing pipe line etc. complete in all respect as per Technical Specifications and specified makes as per direction of Engineer in charge. (As per HSR, Gazette notification no. 15-2026 Dated on: 13April 2026). EMF 600for DN 600mm |
| 42 | Supplying installation testing and commissioning of following capacity (continuous loading) BEE 3Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 33/0.433KV step down, 3Phase, 50Hz, Dyn 11vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9%pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door/indoor applications with On Load Tap Changer (OLTC) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of plus 5%to -15%in steps of 2.5%, having cable end boxes on HV side suitable for 3x400sq.mm XLPE cable of 33KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026(Part 1to Part 5), IS : 1180and as per CPWD specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with plus 12.5percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9Tesla. The permissible temperature-rise shall not exceed 35 0C for oil and 40dg. C up to 200KVA and 40 0C for oil and 45dg. C for above 200KVA for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180(Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition: a) air temperature 50 0C, b) Relative Humidity 90% Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1with all accessories running measured as per IEC 551/ NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180Part-3. The entries on the rating plate shall be indelibly marked.` `Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature: c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates: e) Silica gel breather f) Drain-cum-sampling valve (¾? nominal size thread, IS 554) preferably steel with plug for three phase transformers: g) Thermometer pocket with cap: (h) Oil filling holes having (1¼? nominal size thread) with cover (for sealed type transformers without conservator): i) Lifting lugs for the complete transformer as well as for core and winding assembly: (j) Pressure relief device or explosion vent above 200kVA: k) One filter valve on the upper side of the tank (for transformers above 200kVA): l) Unidirectional flat rollers (for transformers above 200kVA): m) Inspection hole (for transformers above 200kVA): n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth): o) Buchholz relay for transformers above 800kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3Nos. q) Bird guard: r) Oil temperature indicator and winding temperature indicators for transformers above 200kVA with suitable tripping mechanism above permissible limit s) Jacking pads (for transformer above 1 600kVA): t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600kVA) with low oil level alarmcontact: v) Non return valve (for conducting pressure test): w) Pressure relief device or explosion vent x).Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. (As per HSR, Gazette notification no. 15-2026Dated on: 13April 2026)` 630KVA |
| 43 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentiond as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.` 2700LPM x 35.00M Head (For IPS Defence colony) |
| 44 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentiond as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.` 900LPM x 35.00M Head (For IPS Defence colony) |
| 45 | `NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentiond as per the indicated requireents of discharge in LPM and power capacity in BHP as per IS marked.` 500LPM x 35.00M Head (For IPS Defence colony) |
| 46 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 7.50HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required.(For IPS-Dedence Colony) |
| 47 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentiond as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.` 7500LPM x 25.00M Head (For IPS-Govt. College) |
| 48 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 15HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0 to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS Ninan) |
| 49 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.`7800LPM x 35.00M Head (For MPS- Mini Secretriat) |
| 50 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.`3900LPM x 35.00M Head (For MPS- Mini Secretriat) |
| 51 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 50HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Mini Secretriat) |
| 52 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 100HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Mini Secretriat) |
| 53 | EOT: Supplying, erecting, testing and commissioning of Electrically Operated Travelling Crane (EOT) .Main girder and End Carriage fabricated from Rolled Steel Section, Gear Box for all motion, Electro Magnetic Friction Disc Type Brakes, all safety limit switches , LT wheels EN 9, Double Flanged 4No, with Sq. Cage motor of adequate rating (KW), duly painted mechanical cleaning and one coat of primer and two coat of synthetic paint and as per the direction of the Engineerin Charge(As per HSR, Gazette notification no. 15-2026Dated on: 13April 2026) Span 9M and Lift 6M |
| 54 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.` 4800LPM x 35.00M Head (For IPS Ninan) |
| 55 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentiond as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.` 2000LPM x 35.00M Head (For IPS Ninan) |
| 56 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.`1000LPM x 35.00M Head (For IPS Ninan) |
| 57 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 62.50HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS Ninan) |
| 58 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 12.50HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS Ninan) |
| 59 | Supplying, Installation, Testing and Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV plus or better norms along with having Prime Power Rating of KVA as below, 415volts at 1500RPM, 0.8lagging power factor at 415V suitable for 50Hz, 3phase system, including testing at factory and site with fuel, load for test and other necessary arrangements with rating plate as per relevant IS Code etc. and consisting of the followings: (A) Diesel Engine: Turbocharged Diesel engine 4stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500RPM suitable for above output of alternator at 40Deg C, 50%RH and at 1000Meter MSL , capable of taking 10%over loading for one hour after 12hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV plus or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018. (B) Engine mounted Instrument Panel fitted with and having digital display for following: (As per HSR, Gazette notification no. 15-2026Dated on: 13April 2026)(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubrication Oil trip indication(ix) Engine Running Hours indication (x) Fuel Level (C) Alternator: Synchronous alternator rated of appropriate KVA, 415volts at 1500RPM, 3phase 50 Hz, AC supply with 0.8lagging power factor at 40 0C, 50%RH and at 1000Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10%over loading for one hour after 12hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation. (D) Base Frame and Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. (E) FUEL TANK: Daily service fuel tank of suitable liters capacity, fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications and accessories as required as per specifications. (F) Exhaust System: Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor. (G) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. (H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof and dust-proof conforming to IP-65protection. The enclosure shall be as per CPCB IV plus or better norms etc. and. (I) AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto bypass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering and protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase and Total), KW and provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software etc. as per approved by Engineering in charge and including the following: 1. Suitable numbers and appropriate capacity 4pole motorised electrically operated draw out with cradle type 3position ACB/ MCCB with electronic release for O/C and E/F and shunt trip. 2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2nos Over voltage relay, 2Nos. reverse power relay and 2Nos. under voltage relay).4. 3Sets of current transformers 15P 10accuracy for protection and 15VA class-I for metering 5. Energy analyser unit to indicate current, Voltage( LN and L_L), kW, kVA (Phase and Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set7. Fuse/ MCB for instruments8. Battery charger, complete with transformer/ rectifier,D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor10. Supply failure timer11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility.14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories17. Maintenance notification based on Engine Run Hour and due date.18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel, interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring. 19. Suitable rating of AC contactors/ ATS / ACB with control wiring.35KVA |
| 60 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 2.50HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8 m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For IPS-Jagarti Nagar) |
| 61 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 15HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35% VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Jeetuwala Johar) |
| 62 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.`7100LPM x 25.00M Head (For MPS- Jeetuwala Johar) |
| 63 | Providing and laying double flanged (Screwed/ welded) centrifugally (Spun), Ductile Iron Pipes of Class K-9 conforming to IS:8329-2000(amended upto date).(As per HSR, Gazette notification no. 15-2026Dated on: 13 April 2026) 450mm i/d |
| 64 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 130HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3 (Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0 to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Dhana road) |
| 65 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 60HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Dhana road) |
| 66 | Design, Supply, installation and testing of VFD along with distribution panel in enclosure for non clog sewage submersible pump motor rating of 30HP Compatible to work with cable length of 100meters. Enclosure shall be IP54. The panel shall be equipped with MCCB TP with suitable rating, Spreader link TP, Extended rotary handle, Volt meter digital, Volt selector switch, Amp meter, Amp selector switch, C.T with suitable rating, Control MCB SP with suitable rating, PLA Relay, Pushbutton red plus green with element, Indicator ON/Off, Aluminium Bus bar/suitable rating power and Control wiring labour and margin, Fabrication with minimum Sheet thickness of 2mm for load bearing and non-load bearing side. VFD should be capable of protecting motor from high and low voltage and earth fault as well. VFD should restrict harmonics up to 35%VFD should be capable of providing starting torque up to 200%while starting motor. It should have class 3C3(Avg)conformal coating so that components are safe from dust and moisture. Communication -Built-in RS485Modbus RTU, Ambient Temperature -Heavy Duty: -10~ 50deg C Normal Duty: -10~ 40deg C, PCB Protection Conformal Coating complying to IEC 60721-3-3class 3C3, Application Humidity Below relative humidity 95%RH (no condensation) Altitude 0to 1,000m Without deration 1,001to 4,000m With deration of 1%per rise in 100m, Vibration Up to 9.8m/sec2(1.0G), Global Compliance CE, UL, RoHS, Control Method V/F Control, Sensorless Vector Control, Slip Compensation, Closed Loop Vector Control. Starting Torque 200%at 0.5Hz in Sensorless Vector Control and 150%at 3Hz in V/F, Frequency Control Range 0to 400Hz in V/F, 0to 300Hz in Sensorless 1, 0to 120Hz in Sensorless 2/ Vector, Frequency Precision Setting- Digital: 0.01Hz, Analog: 0.03Hz (60Hz Base). complete with all other accessories as required. (For MPS- Dhana road) |
| 67 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.`17600LPM x 20.00M Head (For MPS- Dhana road) |
| 68 | NON CLOG SEWAGE PUMP: Supplying, erection, testing and commissioning of Submersible motor pumping set non clog for sewerage having head below mentioned as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked.`7900LPM x 20.00M Head (For MPS- Dhana road) |
| 69 | MPS 21.00MLD: Design, construction, testing and commissioning of MPS suitable for 21.00MLD average flow with peak factor 2.25complete in all respect as per scope of work and specifications mentioned in DNIT and entire satisfaction of engineer-in-charge including following components: RCC inlet chamber, screen chamber, wet well sump, 6non clog sewage pumping sets having duties 3no.14300LPM x 30m head, 3no. 7200x 30m head with all CI specials, suction / delivery pipes, Sluice valves, NRV, with suitable size cable, VFD panels, LT panels, PLC Panel, all safety devices, 4manual operated sluice gate valves, 2Mechanical coarse screens, electromagnetic flow meter complete in all respect as per specifications mentioned in DNIT and entire satisfaction of Engineerin-charge. Dewatering the sub soil water up to the required depth during the construction period is included in the scope of work. Construction of RCC manhole at existing incoming trunk sewer and laying the HDPE PN6pipe from manhole to proposed MPS by trenchless method at all depth. Laying the 1000mm I/D connecting DI pipe K9from proposed MPS to parallel running 2existing 600mm i/d DI pipe R/M lines with in the campus of MPS including supply of DI pipe having suitable length, Sluice valves, NRV, DI specials complete in all respect. Shifting of exist. 600mm I/D strom water line at required depth as per exist. line from front road to exist. storm water IPS with in the campus which falls in the alignment of proposed MPS including construction of required RCC Manhole, plugging the exist. line and making necessary connection to IPS complete in all respect as per scope of work mentioned in DNIT. The structural, hydraulic, Mechanical, and Electrical design will be approved by the Department before starting of work. All pumping machinery, Panel Board Level Sensor, Flow meter etc shall be controlled by SCADA at STP Charkhi Dadri Road. |
| 70 | Credit for old transformer complete in all respect.MPS desar chungi = 500KVAMPS Jeetuwala Johar = 100KVAMPS Mini secretriat = 300KVAIPS Govt. College = 63KVA Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |