Tender For Repair/Maintenance Of Water Supply Networks System Of 13Brd & 16Brd Domestic And Tech Area, Maintenance Of Submersible Pump And Booster Pump, Starter Panel And Other Allied Maintenance Works Under Ge(Af) Gurgaon No-1.
Tender Value
45 Lakhs
Estimated cost
Bid Submission
04 Jul 2026
2 days left
EMD
90000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Gurgaon → Haryana
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Maintenance Of Water Supply Networks System Of 13Brd & 16Brd Domestic And Tech Area, Maintenance Of Submersible Pump And Booster Pump, Starter Panel And Other Allied Maintenance Works Under Ge(Af) Gurgaon No-1.
BOQ
| Sl. No. | Item Description |
| 1 | Schedule-A |
| 2 | Excavation in trenches in any type of soil i.e. loose/soft not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in width and getting out complete all as specified and as directed by Engineer-In-Charge. |
| 3 | All as per item No. 1 above but in hard/dense soil/cutting of road/hard standing/breaking of PCC etc. |
| 4 | Returning, filling and including spreading, leveling and watering and well ramming in layers not exceeding 25 cm to achieve desired compactness as directed by Engineer-In-Charge. |
| 5 | Removing of excavated material/soil to a distance not exceeding 50 Mtrs and depositing at a level not exceeding 1.5 Mtr above the starting point all as directed by Engineer-In-Charge. |
| 6 | M&L for PCC 1:3:6 type C-1 ( using 20 mm graded stone aggregates) for repairing of valve chamber foundation etc including filling in road cuts/ hard standing etc all as specified and as directed. |
| 7 | M&L for brick work in cement mortar 1:4 using sub class 'B' brick straight or curved on plain not exceeding 6M mean radius comlete all as specified. |
| 8 | M&L for 15mm thick cement plaster in CM 1:4 on brick/concrete surface etc finished even and smooth without using extra cement complete all as specified and directed. |
| 9 | Supply, laying, jointing and testing in replacement in trenches, galvanized iron water tubing medium grade including provision of all necessary ISI marked GI fittings / accessories complete all as specified and directed for the following sizes :- |
| 10 | 50 mm bore. |
| 11 | 40 mm bore. |
| 12 | 25 mm bore. |
| 13 | 20 mm bore. |
| 14 | 15 mm bore. |
| 15 | Supply, laying, jointing & testing in replacement in trenches cast iron pipes with spigot and socketed ends centrifugally cast (spun cast) class LA suitable for tyton joints complete all as specified and directed by Engineer-in-Charge for the following size:-Note:- Earth work, Joints and CI specials/ fittings of the pipes shall be measured and paid for separately under appropriate item. |
| 16 | 150mm bore. |
| 17 | 100mm bore. |
| 18 | 80mm bore. |
| 19 | Supplying, and laying and testing in trenches, jointing/ connecting and testing 150mm bore ductile iron pipe class 'k-7' with spigot and socketed ends, centrifugally cast suitable joint complete, all as specified and directed by Engineer-in-Charge. |
| 20 | Supplying, and laying and testing in trenches, jointing/ connecting and testing 100mm bore ductile iron pipe class 'k-7' with spigot and socketed ends, centrifugally cast suitable joint complete, all as specified and directed by Engineer-in-Charge. |
| 21 | Supply and fixing cast iron specials/fittings such as bend, tee, socket, collar Reducer, Tail Pieces etc. suitable for spigot and socketed/ flanged end pipe upto 150 mm bore complete all as specified and directed by Engineer-in-Charge. |
| 22 | Supply, laying, jointing & testing in replacement in trenches cast iron pipes with spigot and socketed ends centrifugally cast (spun cast) class LA suitable for tyton joints complete all as specified and directed by Engineer-in-Charge for the following size:-Note:- Earth work, Joints and CI specials/ fittings of the pipes shall be measured and paid for separately under appropriate item. |
| 23 | 50 mm bore. |
| 24 | 40 mm bore. |
| 25 | 25 mm bore. |
| 26 | 20 mm bore. |
| 27 | 15 mm bore. |
| 28 | Supply, installation, fixing, jointing and testing in replacement ISI Marked, of approved quality, cast iron sluice valve of class PN-1.6 conforming to IS-14846 of 2000 both ends flanged with iron wheel head and stainless steel spindle, long body type, jointed and tested complete all as specified and directed for following bores :- |
| 29 | 150mm bore. |
| 30 | 100mm bore. |
| 31 | 80mm bore. |
| 32 | Supply and fixing in replacement ISI Marked, of approved quality, cast iron non return valve, both ends flanged jointed and tested complete all as specified and directed for 80 mm bore sizes. |
| 33 | Supply and fixing in replacement ISI Marked, of approved quality, cast iron non return valve, both ends flanged jointed and tested complete all as specified and directed for100 mm bore sizes. |
| 34 | M&L for tyton rubber joints for the following sizes of CI pipes/fittings etc. complete all as specified and directed |
| 35 | 150mm bore. |
| 36 | 100mm bore. |
| 37 | 80mm bore. |
| 38 | M&L for run lead joints in replacement including caulking properly for the following sizes of CI pipes/fittings etc. complete all as specified and directed. |
| 39 | 150mm bore. |
| 40 | 100mm bore. |
| 41 | 80mm bore. |
| 42 | Dismantling flanged pipe joint complete all as directed for following sizes:- |
| 43 | 150mm bore. |
| 44 | 100mm bore. |
| 45 | 80mm bore. |
| 46 | M&L for rubber gasket joints in flanged end cast iron pipes and fittings complete with and including minimum 3mm thick rubber/fibre gasket and necessary nuts/bolts/washers complete all as specified and directed for following sizes:- |
| 47 | 150mm bore. |
| 48 | 100mm bore. |
| 49 | 80mm bore. |
| 50 | M&L for Cutting of the existing CI pipe line for rectifying leakage and reducing to required length, in position, for insertion of collars or other fittings including dewatering etc complete all as specified and directed for the following bore of pipes:- |
| 51 | 150mm bore. |
| 52 | 100mm bore. |
| 53 | 80mm bore. |
| 54 | M&L for rectifying leakage of CI pipe line including excavation in mud (not exc 1.2m x1.2m x 1.2m) and making arrangement for dewatering by using electric/diesel pump/manual additional labour, taking out existing joint and making new run lead joint (except CI fittings unions and CI pipes) complete all as directed for following size of pipe lines:- |
| 55 | 150mm bore. |
| 56 | 100mm bore. |
| 57 | 80mm bore. |
| 58 | M&L for rectifying leakage of GI pipe line including excavation in mud (not exc 0.7m x0.7mx0.7m) and making arrangement for dewatering by using electric/diesel pump/manual additional labour, taking out existing joint and making joint including providing all GI fittings i.e. socket, tee, elbow , nipples upto 6'' length,GI unions,Reducer (Except GI pipes) complete all as directed for following size of pipe lines:- |
| 59 | 80 mm bore. |
| 60 | 50 mm bore. |
| 61 | 40 mm bore. |
| 62 | 25 mm bore. |
| 63 | supply only Liquid Chlorine suitable for water treatment / disinfection in RO Plant operations conforming to relevant IS standards, supplied in approved cylinders/containers complete in all respects including transportation, handling, loading, unloading, safety precautions and delivery at site as directed by Engineer-in-Charge. |
| 64 | Supply only Calcium based, high strength chlorination chemical for water disinfectant in granular form in factory sealed HDPE container (45/50 Kg each ) , chlorine concentration leve 70% and delivered at various water installation underAGE E/M (AF) Palam complete all as specified and as directed. |
| 65 | M&L in replacement of rotational moulded polyethylene water storage tanks 3 layer (cylindrical vertical with closed top) hoisted and fixed in position of capacity upto 10000 ltrs including gasket packing ,nipple of 50 mm dia, check nuts etc complete all as requried for connecting the existing position complete all as specified and directed by Engr in charge. |
| 66 | M&L for two coat painting to exposed CI/GI water pipe lines of header/suction /delivery of borewells/booster pumps any type any make and any size including sluice valves,fittings and non return valves at water supply installations as per specified colour code after cleaning and scraping out old paint including writting /marking complete all as specified and directed . |
| 67 | M&L for construction of valve chambers with MS cover 6 mm thick of valve pit of size 1200x1200x1200 MM( internal dimensions) including necessary excavation, earth work 150 mm thick PCC 1:4:8 Type D2 as in foundation, PCC 1:2:4 Type B1 in coping plastering 15 mm thick in CM 1:4, and angle iron frame 40x40x6 mm and locking arrangement including painting with coat of synthetic enameled paint over a coat of red oxide primer after preparation of surface complete all as specified and as shown in drawing No CE(AF)/TD/30 dated 11.11.2013 including dismantling of existing valve pit. |
| 68 | M&L for construction of valve chambers with MS cover 6 mm thick of valve pit of size 900x900x900 MM( internal dimensions) including necessary excavation, earth work 150 mm thick PCC 1:4:8 Type D2 as in foundation, PCC 1:2:4 Type B1 in coping plastering 15 mm thick in CM 1:4, and angle iron frame 40x40x6 mm and locking arrangement including painting with coat of synthetic enameled paint over a coat of red oxide primer after preparation of surface complete all as specified and as shown in drawing No CE(AF)/TD/30 dated 11.11.2013 including dismantling of existing valve pit. |
| 69 | Lifting / taking out the defective submersible pump motor set of any capacity and description / make, at any depth from bore well by lifting tolls , chain pulley etc all as required carefully, by disconnecting / dismantling all electric connections, column pipes of any size 50/80 mm etc and transporting the defective pump motor set to AGE E/M Yard, lowering the new / serviceable submersible pump motor set to the existing location including replacing the rubber packing/ nut bolts of the column pipes , pipes, valves etc of suitable size where ever required complete all as specified and directed by Engr-in-charge. |
| 70 | Supply, fixing and testing of submersible electric driven pump only with outer dia of pump not exceeding 150 mm having discharge capacity 5 lps at 90 Meter head (operating head range -113-74 mtr) complete all as specified and directed by Engr-in-charge. (Taking out and lowering of pump motor set will be measured and paid separately). |
| 71 | Supply, fixing, connecting electric connections and testing submersible motor only capacity 10 HP 3 phase 415 volts, 50 HZ with outer dia of pump set not exceeding 150 mm suitable to be coupled with pump as mentioned in item no. 58 hereinbefore complete all specified and directed. |
| 72 | M&L for high pressure single electromagnetic diaphragm type adjustable chemical dozing pump capacity 10 LPH at 3 Kg/cm² suitable to doze the NaOCL with accessories including heavy duty Lead Tubing of suitable size , Connecting Nuts, Injection Check Valve, Clay Weight, and connecting Ferrules with mounting arrangement complete all as specified and directed by Engr-in-charge including disconnecting the old one of any type any capacity. |
| 73 | S&F 100 Lit. capacity PVC tank ISI Marked triple layer,including fitting and fixture complete all as specified and directed by Engr-in-Charge. |
| 74 | Supply, connection and testing of submersible cable copper conductor 3 core 1100 Volt grade 4 sq mm nominal cross sectional area including disconnecting the old u/s cable complete all as specified and directed by Engr-in-charge. |
| 75 | Supply, install, connect, test and commission factory made cubicle type dust and vermin proof LT Feeder Pillar of suitble size outdoor type for STP, made out of 3.15 mm thick CRCA sheet and 50x50x6 mm (ISA- 5050) MS angle frame with hinged cubicle doors with locking arrangement, duly painted with two coats of synthetic enamel paint over a coat of red-oxide primer with seven tank process with twin shutter closing & locking arrangements complete and fixed in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate as in foundation 40 cm above ground level. It should be outdoor type and approved through CPRI . LT Feeder Pillar comprising of the following accessories :- |
| 76 | INCOMING(I) MCCB, AC 415 volts,4- Pole, 200 Amps current rating, 36 KA rupturing capacity with adjustable (70% to 100%) thermal setting and fixed magnetic setting conforming to IS: 13947-II complete with connections to the bus-bars. - 01 No. (ii) Aluminium Bus-Bar strip used of suitable rated capacity of 300Amps with coloured PVC insulating sleeves, mounted on post insulatore, 1100 volt grade - 04 Nos.(iii) Voltmeter 0 - 500 volts digital type, flush mounting with Selector Switch. - 01 Set(iv) Ammeter 0 - 600 Amps digital type, flush mounted, with CTs and Selector Switch. - 01 Set(v) Phase Indicator Lamps, LED type. - 01 Set(vi) Panel instrument fuses - 01 Set |
| 77 | OUTGOINGSMccb 3 pole- 63 Amp - 3 nos duly attached with star delta Starter (including Single phase preventer &Thermal Relay) - 3 Nos suitable for 15 HP submersible pumpset along with spare space for fixing of 01 Nos MCCB |
| 78 | S&F in replacement GI pipe heavy duty grade for column pipe 50 mm dia with M.S Flange dia heavy duty V cut on both ends of flanges of submersible cable entry and including rubber gasket and 4nos nuts & bolts with suitable sizes and welding as per site requirement. |
| 79 | M&L for welding MS flange on column pipe including making bore for nut bolts and groove cutting in flange for submersible cable run through grooves complete all as specified and directed. |
| 80 | M&L for Development of bore well for improving the yield of bore well and to achieve sand free crystal clear water by means of air compressor not less than 630 CFM capacity by lowering 32 mm dia pipe up to the depth of not less than 260 feet . Development should be continuing by applying air jerk at required intervals. It also includes pouring of chemical to dissolve the compact rust, sand and other sediments. After development and achieving required result pipe and connected items shall be taken out from the bore well and removed sand shall be removed from the pump house building in all respect. |
| 81 | M&L for complete rewinding of electric motor with super enameled copper wire of superior quality as per existing gauge including vanishing, insulating material complete all as directed and greasing, oiling etc and including reassembling fixing in position making connection testing, commissioning & transporting complete. Note :- rewinding shall be done with gurantee during the contract period. Any defects after rewinding shall be rectified by the contractor at his own expanses. |
| 82 | Cleaning and disinfecting of 50,000 Gallons capacity Overhead Water Tank including draining out water, removal of sludge, scrubbing of internal surfaces, cleaning with approved disinfectants, washing, disposal of waste material and refilling complete in all respects as directed by Engineer-in-Charge.Note-Rate quoted shall include all T&P, labour, consumables and allied charges required for completion of work |
| 83 | Cleaning and disinfecting of Underground (UG) Sump up to 2,50,000 Gallons capacity including dewatering, removal of sludge/sediments, scrubbing and cleaning of floor, walls and ceiling, disinfection with approved chemicals, washing, disposal of waste material, manpower, tools & tackles, safety equipment and making the sump fit for potable water storage complete in all respects as directed by Engineer-in-Charge.Note-Rate quoted shall include all T&P, labour, consumables and allied charges required for completion of work |
| 84 | Painting of Submersible Borewell installation including cleaning of surface, removal of rust/scales by wire brushing/scraping, surface preparation and applying one coat of approved primer and two coats of synthetic enamel paint of approved shade on exposed GI/MS pipe, column pipe, pump accessories, clamps, supports and connected fittings complete in all respects as directed by Engineer-in-Charge. |
| 85 | Painting of Booster Pump and Motor including cleaning of surface, removal of rust/scales, proper surface preparation and applying one coat of approved primer and two coats of synthetic enamel paint on pump body, motor body, base frame and connected accessories complete in all respects as directed by Engineer-in-Charge |
| 86 | Painting of LT Panel including cleaning of surface, removal of rust/scales, sanding, proper surface preparation and applying one coat of approved metal primer and two coats of synthetic enamel paint of approved shade on outer surface of LT panel, panel frame, doors and connected metal parts complete in all respects as directed by Engineer-in-Charge |
| 87 | Repairing/servicing of Booster Pump set capacity upto 50 HP including dismantling, checking of pump and motor components, replacement of damaged/worn-out parts such as bearings, gland packing/mechanical seal, coupling rubber, nuts & bolts, alignment, reassembly, testing, commissioning and satisfactory operation complete in all respects as directed by Engineer-in-Charge |
| 88 | Repairing/servicing of Submersible Pump set up to 15 HP capacity including dismantling, checking of motor and pump assembly, replacement of damaged/worn-out parts such as bearings, bush, impeller, cable joint, gland/seals and other necessary components, reassembly, testing and commissioning complete in all respects as directed by Engineer-in-Charge |
| 89 | Providing, fixing/replacement of flexible coupler/coupling for Booster Pump and Motor up to 50 HP capacity including dismantling of existing coupling, alignment of pump and motor, fixing of new coupling with nuts, bolts, rubber bushes/spider and testing for smooth operation complete in all respects as directed by Engineer-in-Charge. |
| 90 | Water Testing of borewells, Pump House and RO Plant at 13 BRD and 16 BRD area on a Quaterly basis by collecting water samples from different locations in the area as directed by Engineer-in-charge during delivery time for each month complete all as directed. |
| 91 | (a) PH |
| 92 | (b) Specific Conductivity |
| 93 | (c) Free Chloride (CL) |
| 94 | (d) Total Harness as Ca CO₃ |
| 95 | (e) Iron as (FE) |
| 96 | (f) Arsenic (AS) |
| 97 | (g) Total dissolved solids |
| 98 | (h) Coliform |
| 99 | (i) E. Coli |
| 100 | (j) Colour |
| 101 | (k) Odour |
| 102 | (l) Taste |
| 103 | (m) Floride |
| 104 | (n) TDS |
| 105 | (o) Turbidity |
| 106 | Note : (a) Sample of Water for the above media test are to collected in transparent sterlized container/Jar/bottle (to be arranged by contractor) separately for each test against each pump houses. (Hygienically clean bottles) and proper sealing must be done by contractor. |
| 107 | (b) Sample of water to be collected before and after treatment shall be forwarded to Govt Lab approved & NABL accredited Lab for testing within spitulated time frame. No Extra payment will done for transportation charges. |
| 108 | Supply only 50 mm GI pipe union complete as directed by Engineer-in-Charge |
| 109 | Supply only 40 mm GI pipe union complete as directed by Engineer-in-Charge |
| 110 | Supply only 25 mm GI pipe union complete as directed by Engineer-in-Charge |
| 111 | Supply only 20 mm GI pipe union complete as directed by Engineer-in-Charge |
| 112 | Supply only 50 mm GI pipe socket complete as directed by Engineer-in-Charge |
| 113 | Supply only 40 mm GI pipe socket complete as directed by Engineer-in-Charge |
| 114 | Supply only 25 mm GI pipe socket complete as directed by Engineer-in-Charge |
| 115 | Supply only 20 mm GI pipe socket complete as directed by Engineer-in-Charge |
| 116 | Supply only 15 mm GI pipe socket complete as directed by Engineer-in-Charge |
| 117 | Supply only 50 mm GI elbow complete as directed by Engineer-in-Charge |
| 118 | Supply only 40 mm GI elbow complete as directed by Engineer-in-Charge |
| 119 | Supply only 25 mm GI elbow complete as directed by Engineer-in-Charge |
| 120 | Supply only 20 mm GI elbow complete as directed by Engineer-in-Charge |
| 121 | Supply only 15 mm GI elbow complete as directed by Engineer-in-Charge |
| 122 | Supply only 50 mm dia GI pipe nipple 6 inch long complete as directed by Engineer-in-Charge |
| 123 | Supply only 40 mm dia GI pipe nipple 6 inch long complete as directed by Engineer-in-Charge |
| 124 | Supply only 25 mm dia GI pipe nipple 6 inch long complete as directed by Engineer-in-Charge |
| 125 | Supply only 20 mm dia GI pipe nipple 6 inch long complete as directed by Engineer-in-Charge |
| 126 | Supply only 50 mm × 25 mm GI reducer complete as directed by Engineer-in-Charge |
| 127 | Supply only 50 mm × 20 mm GI reducer complete as directed by Engineer-in-Charge |
| 128 | Supply only 25 mm × 20 mm GI reducer complete as directed by Engineer-in-Charge |
| 129 | Supply only 25 mm × 15 mm GI reducer complete as directed by Engineer-in-Charge |
| 130 | Supply only 20 mm × 15 mm GI reducer complete as directed by Engineer-in-Charge Please Enable Macros to View BoQ information |
| 131 | Supply only 20 mm × 15 mm GI reducer complete as directed by Engineer-in-Charge Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jun 12, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 04, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysJul 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender