| 1 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 70 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning including taking out existing cable alongwith protection covers complete all as specified and as directed. |
| 2 | All as per serial item No 01 but cross sectional area 50 sq mm, 3.5 core complete all as specified and directed. |
| 3 | All as per serial item No 01 but cross sectional area 25 sq mm, 3.5 core complete all as specified and directed. |
| 4 | All as per serial item No 01 but cross sectional area 16 sq mm, 3.5 core complete all as specified and directed. |
| 5 | All as per serial item No 01 but cross sectional area 10 sq mm, 2 core complete all as specified and directed. |
| 6 | All as per serial item No 01 but cross sectional area 06 sq mm, 2 core complete all as specified and directed. |
| 7 | Excavation in trenches/ foundation in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed by Engineer-in- Charge. |
| 8 | Returning filling including spreading leveling watering and well ramming in layers not exc 25Cm in soft/ loose soil, complete all as specified and directed. |
| 9 | Removing excavated material in soft/ loose soil n'exc 50M and depositing where directed at a level n'exc1.5M above the starting point, complete all as specified and directed. |
| 10 | Supply and lay DWC Cable duct pipe of size 40 mm dia confirming to IS : 16205 part 24 for laying of LT cables etc complete with all accessories all as specified and directed. |
| 11 | Supply and lay DWC Cable duct pipe of size 63 mm dia confirming to IS : 16205 part 24 for laying of LT cables etc complete with all accessories all as specified and directed. |
| 12 | Supply and lay DWC Cable duct pipe of size 75 mm dia confirming to IS : 16205 part 24 for laying of LT cables etc complete with all accessories all as specified and directed. |
| 13 | M & L GI tube light grade for passing through cables under the floor, along the wall of 50 mm bore dia and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified. |
| 14 | All as per item No 13 above, but 25 mm bore complete all as specified and directed. |
| 15 | Dismantiling/taking out old unserviceable LT insulator any size, any type from poles complete all as specified and directed. |
| 16 | S & F for pin type insulator porcelain vitreous white/ brown or green including one galvanised mild steel spindle two GI washer and one GI nut 100mm height, 65mm dia for 1100 Volt grade complete all as specified and directed. |
| 17 | S & F for Sackle type insulator porcelain vitreous white/ brown or green including one galvanised mild steel straps of size 31 x 5 mm, washers insulator bolt of 14 mm dia and nuts complete of size 100 mm hight and 115mm dia of working pressure 1100 volts grade complete all as specified and directed. |
| 18 | S&F in repair cable route marker of size 100 mm x 100 mm x 5mm thick with GI plate with inspection threon bolted / welded to 35 mm x 35mm x6 mm angle iron 60 cm long and fixing the same in ground as required for LT cable all as specified and directed by Engineer-in-charge. |
| 19 | S&F in repairs Busbar Chambers 8 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts OR provision of fixing on 50 x 50 x 6mm thick angle iron frame work upto height of 0.9mtr above ground level including necessary connection completed all as specified and as directed. Make Havells cat part No IHBC010004 or equivalent make of SMC/Hencel. |
| 20 | S&F Busbar Chambers 4 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts including necessary connection including taking down of old u/s bus bar completed all as specified and as directed. Make Havells cat part No IHBC010004 or equivalent make of SMC/Hensel |
| 21 | M & L for Plain Cement Concrete (1:3:6) mix type C2 (using 40 mm graded stone aggregate) in foundation, filling and mass-concrete etc for pole, stay etc all as specified and directed by Engr-in-charge. |
| 22 | M & L for Plain Cement Concrete (1:2:4) type B1 (using 20 mm graded stone aggregae) as in copping including necessary formwork, weathering, slightly rounded or chamfered angles, finishing of exposed surfaces of concrete to even and smooth without using extra cement all as specified and directed by Engr-in-charge. |
| 23 | Supply and fixing of earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried on ground or drawn in conduit pipe or fixed to poles in repairs or any other indicated situation for the loop earthing etc. as required of size 32 x 6 mm galvanized iron strip complete all as directed. |
| 24 | M&L earthing including dismantling old unserviceable complete with galvanized steel earth plate electrode 600mmX600mmX6.3mm buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15cm on all side and connected to and including using 32 x 6 mm galvanized MS strip wire upto 7.5 mtrs long by means of nuts and bolts, check nuts and washers of GI and connected to earhing test point and earth dolly all as shown in electrical plate No 3 of MES schedule Part-I, and testing on completion including necessary excavation and earth work in any type of soil, PCC(1:3:6) type C1 chamber, pre-cast RCC slab 50mm thick in cement concrete (1:2:4), type B1, reinforced with welded steel wire fabric or XPM, (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with watering pipe 20mm dia medium grade, wire mesh and lugs, GI protection pipe 40 mm dia, light grade 7.5 mtr long for protection of earth lead upto test point etc all as specified and as directed. Note : (a) Length of earthig connection incl GI strip and protection pipe more than 7.5 Mtr will be measured separately. (b) Contractor should conduct necessary test such as Earth continuity, earth resistance test in presence of JE (E/M)/Engr-in-charge. |
| 25 | Description all as per item No. 24.00 above but with GI conductor 4 mm dia as earth electrode and 15mm dia protection pipe complete all as specified and directed. |
| 26 | Supply & Fixing in replacement loop type insulator vitreous porcelain white, brown, or green of size 65 X 90 mm clearance of hole 16 mm complete all as specified and directed. |
| 27 | M&L for painting of steel tubular pole of any size , vertical complete with cross arms with one coat of aluminium paint after cleaning and preparation of surfaces of poles, cross arms, painting 30 cm wide Yellow and black strip on poles up to 1.5 mtr high above coping level and numbering of size 70mmx40mm by using stencil to the pole with black synthetic enemal paint (1st grade ) complete all as directed. |
| 28 | M&L for Repairing of LT panel by means of replace the hinge and locking arrangement of the existing panel, tightening the cable with bus bar by means of suitable lugs, replacement of suitable indicator with colour all as specified and as directed by Engr-in-charge. |
| 29 | S & F in repairs MCCB 4 pole 160 Amps, with thermal release range 70-100% and magnetic setting adjustable, breaking capacity 36 KA completed all as specified and as directed by Engr-in-charge. |
| 30 | S & F in replacement of existing type MCCBs 4 pole of 200 Amps, 415Volt, breaking capacity 25KA, completed all as specified and as directed by Engr-in-charge. |
| 31 | S & F in replacement of existing type MCCBs 4 pole of 250 Amps, 415Volt, breaking capacity 25KA, completed all as specified and as directed by Engr-in-charge. |
| 32 | Material and labour for spray painting to outdoor/Indoor type double door LT panels/Fedder pillar box incl angle iron stand with synthetic enamel paint after cleaning the surface thouroughly with scrapper including protecting/cleaning of cables, wiring and other non painted parts complete all as specified and as directed by Engr-in-charge. |
| 33 | Supply and fix cable jointing kit in repairs of existing LT 1.1 KV grade cable disconnecting from site (by means of disconnecting from panel/trench by excavation) for outdoor termination Straight through tubular sleeve version type joint complete with jointing materials and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 120 Sqmm complete all as specified and directed. |
| 34 | M & L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size, including taking out old unserviceable rusted out danger plate. |
| 35 | M & L for DK Thermoplastic cable junction boxes in repairs of make Sintex, product code GSJB-3126, IP 65 of size 270x225x135mm of metric knockouts for cable entry, weather proof for indoor/outdoor installation with and including glands/insulators and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 2/4 core and fixed to wall/Steel Poles by means of suitable size of clamps with nut and bolts complete including taking down existing existing junction box all as specified and directed by Engineer-in-Charge. NOTE: Make of Junction box shall be Sintex/Hensel or equivalent as approved by GE. |
| 36 | Supply, install, testing and commissioning factory made and tested (including CPRI type test certified) LT Panel box (Design as approved by GE), outdoor type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated copper bus bars installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron 45 cm above ground and 45cm grounted in ground with PCC (1:2:4) Type B1 and coping 30cm above ground level,well Ventilated , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement and including dismantling/ taking down old unserviceable LT feeder piller box with framework 1250mm (W) X 1000mm (H) X 500mm (D) all as specified and as directed. |
| 37 | Incoming : (a) MCCB 200 amps, 4 pole, 36 KA, 415 volts grade, with thermal magnetic - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, mounted on insulators for incomming supply - 01 Set. (c) digital Volt meter ,415 volts, 50 Hz AC supply -01 set. (d) digital Amp meter ,415 volts, 50 Hz AC supply -01 set. (e) Neon indicating lamps (R, Y & B) -01 Set. (f) Control MCB 1P 6 Amp - 04 No ,(g) CT 200/5 - 05 No Outgoing : (a) MCCB 160 amps, 4 pole, 36 KA, 415 volts grade, with thermal magnetic - 02 No (b) MCCB 100 amps, 4 pole, 36 KA, 415 volts grade, with thermal magnetic - 02No (c) digital Volt meter ,415 volts, 50 Hz AC supply -04 set. (d) digital Amp meter ,415 volts, 50 Hz AC supply -04 set. (e) Neon indicating lamps (R, Y & B) -04 Set. |
| 38 | Supply install in replacement and testing out door wheather proof bus bar chamber of size 100 cm x 60cm x 30cm made out of 3.15mm CRCA MS sheet having one side openable hinged door shuter with looking arangement/provn of two nos 80cm long 40x40x6mm anlge iron legs welded and 04 nos copper bus bar of 200Amp rating provn of one MCCB 4 pole 160 Amp 25 KA for controlling Electric supply complete erracted on ground with necessary PCC (1:3:6) type C2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland , lugs/thimbles with framework 1000mm (W) X 600mm (H) X 300mm (D) all as specified and as directed. |
| 39 | Supply and fixing of automatic control panel (Nature switch) designed for automatic control of night senstive electric circuits using space grade infra -red sensor which auto matically adjusts ON and OFF time as per the seasonal variation of day light independtently of altitude and latitude for Three Phase load complete with contractor MCB and timer upto 32 Amp capcity all as specified and directed by Engineer-in-charge. Make HEALER EnterPrices( Model-Navdeep-54-18KW3P)/ Crompton / L&T. |
| 40 | S&F in repairs/replacement of steel tubular swaged pole complete with mild steel box plate, 6 mm thick of size 300 x 300 mm, finial taper plug, pole cap, bolts, nuts, washers & screws as specified, type 410- SP-31 (9 m long), made out of ERW mild steel tubing confirming to IS-2713 Part II including drilling holes of required size for fixing cross arms etc erected in true vertical position including painting the pole with two coats of aluminium paint over a coat of red oxide primer on exposed pole surfaces and two coats of black bituminoius paint for portion embedded in concrete including painting three black/red/ bands at lower portion of pole of 1.8 m height at 300 mm spacing, painting pole No with black paint at suitable height including demolition of foundation concrete and coping complete all as specified and as directed. |
| 41 | S&F in repairs LED street light fittings, IP-66, 70 watt including bracket made out of 40 mm dia light grade GI pipe not less than 1.2 mtr long bend to shape duly fixed with MS clamps of 3mm thick, nut, bolts etc complete fixed to steel tabular poles including electrical connection complete with 3 core 1.5 Sqmm PVC sheathed stranded copper wire ISI marked from junction box to fitting all as specified and as directed. Please Enable Macros to View BoQ information |
| 42 | S&F in repairs LED street light fittings, IP-66, 70 watt including bracket made out of 40 mm dia light grade GI pipe not less than 1.2 mtr long bend to shape duly fixed with MS clamps of 3mm thick, nut, bolts etc complete fixed to steel tabular poles including electrical connection complete with 3 core 1.5 Sqmm PVC sheathed stranded copper wire ISI marked from junction box to fitting all as specified and as directed. Please Enable Macros to View BoQ information |