| 1 | Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. |
| 2 | 9.0 Mtr long PCC pole of 400 Kg Working Load |
| 3 | Labour charges for dismantling of existing PCC/MS electrical Pole including MS channel, V cross arm, 11KV insulator, LT insulator, guard wires, stay wires, one span of ACSR conductors and other electric items, coming along and in the alignment of the road, then removal and re-rolling of the PCC /MS Pole as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge, clean the site good as per the requirement and dismantle material receipt duly signed by DISCOM Engineer submit the receipt to EIC as required. |
| 4 | Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: |
| 5 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 6 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 7 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 8 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer-in-charge. |
| 9 | 1: 3: 6 or richer mix. |
| 10 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as required. |
| 11 | Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm |
| 12 | Supply and fixing of following LT Supporting accessories with nut bolt & Clamps made out as per standard Discom's specifications with two coats of Red oxide and two coats of Aluminium paint etc. as required. |
| 13 | LT cross arm 1200 mm long with clamp |
| 14 | Supply and fixing of LT porcelain pin insulator as per IS 1445-1997 and as per Discom's standard specifications,suitable for working voltage 1100 volts including all accessories like MS Forged GI LT Pin confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. |
| 15 | 100 mm x 70 mm |
| 16 | Supply and fixing of LT porcelain shackle insulator as per IS:1443 1979 and as per Discom's standard specifications, suitable for working voltage 1100 volts including all accessories like GI Hardware fittings confirming to IS:7935/1975 (latest amended) Nut, Bolt etc. as required. |
| 17 | 75mm x 90mm |
| 18 | Supplying and drawing Aluminium conductor steel reinforced (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. |
| 19 | 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT |
| 20 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 21 | 10 SWG G.I. ( Hot Dipped ) Wire |
| 22 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 23 | 25.0 Sq. mm |
| 24 | 4 core |
| 25 | 70.0 Sq. mm |
| 26 | 3.5 core |
| 27 | 120.0 Sq. mm |
| 28 | 3.5 core |
| 29 | 185.0 Sq. mm |
| 30 | 3.5 core |
| 31 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size. |
| 32 | 25.0 Sq.mm |
| 33 | 70.0 Sq.mm |
| 34 | 120.0 Sq.mm |
| 35 | 185.0 Sq.mm |
| 36 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 37 | SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 38 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 39 | (b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7 |
| 40 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 41 | (d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. |
| 42 | (e) Testing of earth resistance for value of 5 ohms or less as required. |
| 43 | (f) Test certificates for confirming above standards from OEM is mandatory. |
| 44 | 17.2 mm thick and 3 Mtr. Long |
| 45 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 46 | 20mm x 3mm copper strip |
| 47 | 20mm x 3mm G.I. ( Hot Dipped ) Strip |
| 48 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) |
| 49 | 100 mm dia. |
| 50 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. of outgoing. |
| 51 | 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer |
| 52 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 53 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 54 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 55 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 56 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 57 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 58 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 59 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 60 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 61 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 62 | Electrolytic grade Aluminium bus bar 6010 grade |
| 63 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 64 | Three phase Ammeter with Inbuilt Selector Switch |
| 65 | Three phase Voltmeter with Inbuilt Selector Switch |
| 66 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 67 | Ring type tape wound CT |
| 68 | C T Class 1, Ratio 800/5 to 1200/5, Burden 15 VA |
| 69 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 70 | Red/yellow/Green colour |
| 71 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor confirming to IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. |
| 72 | 4 pole Power contactors with following AC 1 Rating |
| 73 | 63 Amp |
| 74 | Providing & Fixing of Electromechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. |
| 75 | One day & week reserve (digital type ) |
| 76 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 77 | 4 pole MCCB With Thermal Magnetic release |
| 78 | 200 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 79 | 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 80 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 81 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 82 | 3 core 185.0 Sq.mm |
| 83 | Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 84 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 85 | 11 KV End Termination Kit Indoor type |
| 86 | 3 core 120/150/185 Sq.mm |
| 87 | 11 KV End Termination Kit Outdoor type |
| 88 | 3 core 120/150/185 Sq.mm |
| 89 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated stainless steel Outdoor enclosure of thickness of 2 mm and tank of stainless steel Outdoor enclosure of thickness 3mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for both Cable chamber and gas tank as per IEC 62271-200 and LBS to be rated for class E3 as per IEC 62271 - 103. Vacum Interrupter should be same as used during type test of RMU. Each feeder of RMU should have voltage presence indicator. and VCB feeder should consist of 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder, 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.Load break switch feeder shall have Fault Passage indicator, Right angle boots for all the feeder Modules, Remote trip, Emergency Stop, Cable cover interlocking, Trasnformer protection tapo card etc. All the type test certificates as per IEC and CEA from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) |
| 90 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 91 | Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following specifications A, B, C, D, E. |
| 92 | A) Double pole structure on 2 no ISMB ( I beam ) of size 150 x 75 mm x 8 mm, 9 mtr length using MS channel each of size 100 mm x 50 mm x 2500 mm ( 3 No. ) and of size 75 mm x 40 mm x 2500 (4 No.) mm complete in all respect with nuts, springs washers, clamps as required. |
| 93 | B) Off load type gang operated 3-pole horizontal flute type switch suitable for 11KV ; 400A ,3-ø, central post rotating double break isolator complete with MS hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator , 25 mm ‘B’ class GI pipe of suitable length for operation. |
| 94 | C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators |
| 95 | D) 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv Overhead line with rated voltage of 9kv rms & nominal discharge current rating of 5 kA & complete with galvanized clamping arrangement GI bolts, nuts, washer etc as required. |
| 96 | E) 3 no 11kv ACSR conductors mounted on pin type insulators as required. |
| 97 | S I T C of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 ( Correspnding level as per BIS amended upto date of receipt of tender) & BIS approved as per IS 2026- 1977 & losses as defined as per 2014 (Fourth Revision) Level-1 including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, undirectional rollers as required including carrying of pre-commission Testing & Charging of Transformer complete in all respect . Factory Tests : The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) in OEM's own lab and same shall be witnessed by Department engineer. Site Tests : Following tests shall be carried out on each transformer at site by OEM engineer in presence of department's site engineer:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor) |
| 98 | Note :Manufacturer's testing laboratory should be certified by NABL and have an in house core cutting facility to ensure proper control & monitoring of quality. This is crutial to prevent the mixing of prime core materials with Second grade or defective materials. The core should be constructed from high grade, non ageing, PRIME GRADE CRGO steel with M4 Grade or Better, using silicon steel laminations, and should be of boltless design. The core and coil assembly should be undergo drying process using a highly efficient vacuum drying autoclave to remove moisture through heating and drying. |
| 99 | 160KVA with % impedance 4.5 Please Enable Macros to View BoQ information |