| 1 | Excavation in trenches in loose / soft soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide and getting out including trimming of sides, for laying of cables & foundation of poles, stay assembly, complete all as specified and directed by Engr-in-Charge. |
| 2 | Taking out old HT under ground cable from trenches / floor / road / pipe / pole of any size and description incl joint, complete all as specified and directed by Engr-in-Charge. |
| 3 | Supply, laying, testing and commissioning of semi conducting compound conductor screened PVC bedded galvanized steel strip or wire armoured XLPE insulated heavy duty 11000 Volts grade with stranded aluminium conductor of size 240 Sqmm x 3 core confirming to IS 7098 Part-II, suitable for earthed system complete all as specified and directed by Engr-in-Charge. Note : 1. The end termination joint shall be measured and paid separately under respective items. 2. Excavation, earth work, sand cushioning and protection cover will be measured and paid for separately. |
| 4 | Supply, laying, testing and commissioning of semi conducting compound conductor screened PVC bedded galvanized steel strip or wire armoured XLPE insulated heavy duty 11000 Volts grade with stranded aluminium conductor of size 95 Sqmm x 3 core confirming to IS 7098 Part-II, suitable for earthed system complete all as specified and directed by Engr-in-Charge.Note : 1. The end termination joint shall be measured and paid separately under respective items. 2. Excavation, earth work, sand cushioning and protection cover will be measured and paid for separately. |
| 5 | M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 10 cm after laying of cable in trenches complete all as directed and sand cover to UG cable, complete all as specified and directed by Engr-in-Charge. Note :- For the purpose of payment only punned thickness will be measured. |
| 6 | M&L for factory made un-reinforced pre cast concrete cable protection cover class HVP, Type 1 with peak, size 300mm x 180mm x 40mm laid across the cable (i.e. width of cover along the length of cable) for HT UG cable protection on the top of the sand cushioning, complete all as specified and directed by Engr-in-Charge. |
| 7 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed by Engr-in-Charge. |
| 8 | Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed by Engr-in-Charge. |
| 9 | S&F of galvanized iron pipe of 100 mm nominal dia light grade fixed to poles with clamps nuts, bolts and washers or laid under road crossing or fixed to wall including painting with two coats of aluminium paint over a coat of red oxide paint, complete all as specified and directed by Engr-in-Charge.Note : The cost of MS clamp, nut, bolt, washer and GI fittings etc shall be inclusive in the item rate. |
| 10 | Supply jointing and testing Outdoor type cable end termination joint (Heat shrinkable) suitable for XLPE armoured aluminium conductor cable of size 240 Sqmm x 3 Core, 11000 Volts (Earthed) grade, complete all as specified and directed by Engr-in-Charge. |
| 11 | All as srl item no 10 here-in-before but indoor type for cable size of 240 sqmm 3 core.complete all as specified and directed by Engr-in-Charge. |
| 12 | Supply jointing and testing outdoor type cable end termination joint (Heat shrinkable) suitable for XLPE armoured aluminium conductor cable of size 95 Sqmm x 3 Core, 11000 Volts (Earthed) grade, complete all as specified and directed by Engr-in-Charge. |
| 13 | All as srl item no 12 here-in-before but indoor type for cable size of 95 sqmm 3 core.complete all as specified and directed by Engr-in-Charge. |
| 14 | Supplying, fixing, jointing and testing cable jointing kit for 11KV (earthed system) grade cable for STRAIGHT THROUGH heat shrink type joint complete with jointing materials and accessories suitable for 95 Sqmm x 3 Core, XLPE armoured aluminium conductor cable 11000 Volts grade, complete all as specified and directed by Engr-in-Charge. |
| 15 | Supplying, fixing, jointing and testing cable jointing kit for 11KV (earthed system) grade cable for STRAIGHT THROUGH heat shrink type joint complete with jointing materials and accessories suitable for 240 Sqmm x 3 Core, XLPE armoured aluminium conductor cable 11000 Volts grade, complete all as specified and directed by Engr-in-Charge. |
| 16 | M&L for dry, blue colour silica gel crystal impregnated with cobalt suitable for transformer breather complete, all as specified and directed by Engr-in-Charge. |
| 17 | Dehydration/filtration of transformer oil of Transformers & Stabilizers of various capacities installed at MH Sub Station and CEJZ area by disconnecting plants electrically for recirculation existing transformer oil with trolley mounted filtration plant till dielectric strength is not less than 50 KV Note :- (I) Test result will be recorded before & after filtration of oil.(ii) Contractor should make his own arrangement for oil filtration plant including transportation complete.(iii)Transformer oil for topping up will be measured and paid in relavant item as required.complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply and Filling Transformer Oil of good quality for Topping Up transformers 500 KVA, 250 KVA, 160 KVA & Servo voltage Stabilizer 250 KVA Capacity having dielectric strength not less than 50 KV , flash point not less than 135 degree C , having low viscosity for filling or replacing the old oil complete all as specified and directed by Engr in Charge. Please Enable Macros to View BoQ information |
| 19 | Supply and Filling Transformer Oil of good quality for Topping Up transformers 500 KVA, 250 KVA, 160 KVA & Servo voltage Stabilizer 250 KVA Capacity having dielectric strength not less than 50 KV , flash point not less than 135 degree C , having low viscosity for filling or replacing the old oil complete all as specified and directed by Engr in Charge. Please Enable Macros to View BoQ information |