| 1 | Taking down old unserviceable/worn out sub main wiring/service wire of any type and size complete all as specified. |
| 2 | M & L in replacement for Sub main wiring complete with single core 1.5sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 1.5 sqmm in and including Steel conduit on surface and accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 1.5 Sqmm conductor(P+N+E) and one run of steel conduit shall be measured as one unit length.) |
| 3 | M & L in replacement for Sub main wiring complete with single core 1.5sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 1.5 sqmm in existing steel/PVC conduit on surface/concealed and accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 1.5 Sqmm conductor(P+N+E) and one run of conduit shall be measured as one unit length.) |
| 4 | M & L in replacement for Sub main wiring complete with single core 2.5 sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 2.5 sqmm in and including Steel conduit on surface and accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 2.5 Sqmm(P+N+E) conductor and one run of steel conduit shall be measured as one unit length.) |
| 5 | M & L in replacement for Sub main wiring complete with single core 2.5 sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 2.5 sqmm in existing steel/PVC conduit on surface/concealed and accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 2.5 Sqmm conductor and one run of conduit shall be measured as one unit length.) |
| 6 | M & L in replacement for Sub main wiring complete with single core 4 sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 4 sqmm in and including steel conduit on surface incl accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 4 Sqmm conductor(P+N+E) and one run of steel conduit shall be measured as one unit length.) |
| 7 | M & L in replacement for Sub main wiring complete with two single core 4 sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 4 sqmm in existing steel/PVC conduit on surface/concealed incl accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 4 Sqmm conductor(P+N+E) and one run of conduit shall be measured as one unit length.) |
| 8 | M & L in replacement for Sub main wiring complete with single core 6 sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 6 sqmm in and including steel conduit on surface and accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 6 Sqmm conductor(P+N+E) and one run of steel conduit shall be measured as one unit length.) |
| 9 | M & L in replacement for Sub main wiring complete with single core 6 sqmm,1100 volts grade, PVC insulated, stranded copper conductor ZHFR cable with continuous copper earth conductor of 6 sqmm in existing steel/PVC conduit on surface/concealed and accessories complete including necessary connection to existing MCB/Flame proofswitch/Flame proof light fittings/Flame proof Sockets etc all as specified. (Note:- (i) Making good of disturbed surfaces will be done by contractor without any claims. (ii) 3 runs of 6 Sqmm conductor(P+N+E) and one run of conduit shall be measured as one unit length.) |
| 10 | Taking down & Supply and replacement of flame proof and dust proof junction box made up of Die cast Aluminium alloy LM6 4 way IP 65 CMRI certified complete all as directed. |
| 11 | Taking down old unserviceble light fitting and M&L for flame proof, weather proof LED light fitting 40 watts duly CMRI certified recommended for gas/vapour group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminium housing with heat resistant toughned glass, with LED light fixtures driver, holder,connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper cable all as specified and directed by Engineer in Charge. |
| 12 | Taking down old unserviceble light fitting and M&L for flame proof, weather proof LED light fitting 60 watts duly CMRI certified recommended for gas/vapour group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminium housing with heat resistant toughned glass, with LED light fixtures driver, holder,connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper cable complete all as specified |
| 13 | Taking down old unserviceble light fitting and M&L for flame proof, weather proof LED light fitting 90 watts duly CMRI certified recommended for gas/vapour group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminium housing with heat resistant toughned glass, with LED light fixtures driver, holder,connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper cable complete all as specified |
| 14 | Taking down & Supply and fixing LED tube light fitting 1x 16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size. |
| 15 | Taking Down & S&F in repair flame proof rotary type switch with termination box in LM6 including metelic cable galnds , 16 A, single pole 230V complete all as specified |
| 16 | Taking down & S&F Flame proof switch socket & plug combined in LM6 cable termination Box in LM6 , 16A, 250, 2P + earth complete all as specified |
| 17 | M & L for earthing with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm buried directly in ground earth pit not less than 2.25 m deep below normal ground level, with top edge of the plate vertically to depth of not less than 1.5 m below ground level connected to and incl GI wire 4 mm dia and GI pipe 15 mm dia light grade for protection to the extent of 7.5 m as earthing lead by means of GI bolts and nuts etc connecting to equipment with provn of charcoal and salt etc all as per electrical plate No 3 of SSR Pt-I incl RCC cover and MS angle iron frame, watering arrangement with GI pipe 20 mm dia and MS funnel, concrete pit incl excavation and earth work in any type of soil and testing on completion etc complete all as specified |
| 18 | Taking down old unservicable 3 Phase DB TPN 4 Way and M&L for installation, testing and commissioning of flame proof DB complete with CMRI certifided and flame proof complete with emergency off switch with led indicator Including incoming and out going circuit with following accessories.INCOMING (a) Flame proof rotary Switch with MCB 63 Amps 4 pole complete with 10 KA breaking capacity and 'C' curve - 01 Nos. OUTGOING (a) Flame proof rotary Switch with MCB 32 Amps 4pole complete with 10 KA breaking capacity and 'C' curve - 02 Nos. (b) Flame proof rotery Switch with MCB 6 Amps 1 pole complete with 10 KA breaking capacity and 'C' curve - 06 Nos. (c) Flame proof rotary Switch with MCB10 Amps 1 pole complete with 10 KA breaking capacity and 'C' curve - 02 Nos. (d) Flame proof rotary Switch with MCB 16 Amps 2 pole complete with10 KA breking capacity and 'C' curve - 4Nos including internal bus bar, pre wired & copper lugs as required for wiring to teminate at wire complete. |
| 19 | Taking down old unservicable DB and M&L Flame proof DB SPN 8 way with CMRI certified with provn and including following switch gear Incoming (a) Flame proof rotary switch with MCB SPN 40 Amps, 10 KA - 01 No. Outgoing : Flame proof rotary switch with MCB 06 Amps SP with 10 KA - 3 Nos , MCB SP 16 AMPS- 02 Nos & MCB SP 20 AMPS- 01 Nos including internal busbar & copper lugs as required for wiring to teminate the wire complete all as specified |
| 20 | Taking down old unservicable DB and M&L Flame proof DB SPN 6 way with CMRI certified with provn and including following switch gear Incoming (a) Flame proof rotary switch with MCB SPN 32 Amps, 10 KA - 01 No. Outgoing : Flame proof rotary switch with MCB 06 Amps SP with 10 KA - 2 Nos , MCB SP 10 AMPS- 02 Nos including internal busbar & copper lugs as required for wiring to teminate the wire complete all as specified |
| 21 | Taking Down of Exhaust fan of flame proof type having 450mm sweep and M & L for strip opening of body & fan blade,oiling/greasing of moving parts, replacement of broken minor items, checking of electical connections and painting the fan with existing colour. The Exhaust fan will be refixed at the same location/ site. Note : Item as rewinding or major items will be measured and paid seperately complete all as specified |
| 22 | M & L for rewinding of AC motor having capacity upto 250 watts . The exhaust fan will be refixed at the same location/ site complete all as specified |
| 23 | M & L for replacement of fan blade.The exhaust fan will be refixed at the same location/ site complete all as specified |
| 24 | Taking Down & S&F Flame proof switch socket & plug combined in LM6 cable termination Box in LM6 , 32A, 415Volts, three phase, 5 Pin with 3Pole + one Earthing) complete all as specified Please Enable Macros to View BoQ information |