| 1 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. in any type of soil n exc 10 sq m on plan and n exc 1.5 m in depth and getting out complete all as specified and as directed.Note:- Nothing extra will be paid or measured to the contractor if hard or rocky soil or interlocking tiles is encountered during execution & make the interlocking tiles as per existing. |
| 2 | All as per the description of Srl item No 1 herein above but depth exceeding 1.50 metre but not exceeding 3.00 metre |
| 3 | Returning, filling in soils as in trenches, including spreading, levelling, watering and well ramming in layers as in any type of soil, not exceeding 25cm thick complete all as specified and as directed |
| 4 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed. |
| 5 | Cement concrete (1:4:8) type D-2, (using 40mm graded crushed stone aggregates) as in foundations and mass concrete etc complete all as specified and as directed. |
| 6 | Cement concrete (1:3:6) type C-2, (using 40mm graded crushed stone aggregates), in foundation and mass concrete etc complete all as specified and as directed. |
| 7 | M&L for providing Cement concrete (1:2:4) type B-1, (using 20mm graded crushed stone aggregates) as in coping, blocks, bed plates, kerbs etc including weathering, slightly rounded or chamfered angles and throating as directed including as necessary formwork as required complete all as specified and directed. Note: Nothing extra will be paid or measured to the contractor for removing/refixing of Junction Box etc with the pole, if any, during the execution of coping etc. at site. |
| 8 | Supply, erection and fixing in position 9.00 metre long, steel tubular swaged poles complete with mild steel base plate, flat top welded type 410, SP-31 IS:2713 marked, drilling of necessary holes including bolts, nuts and washers as required and painting with two coats of Aluminium paint over a coat of red oxide primer on exposed, surfaces of poles and two coats of black bituminous paint throughout internally and externally upto the planting depth including providing reflective strips of width 10cm upto a height of 1.20m from ground level in alternate colour yellow and black around the pole of pattern as approved by GE and marking pole number at appropriate height with shade and colour as approved by Engineer-in-Charge including dismantling of old existing PCC poles complete all as specified and as directed. Note : Earthwork and concrete work shall be measured and paid for separately. |
| 9 | Dismantling of overhead line ACSR conductor (phase + neutral) complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supplying, laying, jointing and testing LT underground electric cable XLPE insulated, PVC sheathed, armoured heavy duty 1100 volts grade cross section area 25 Sqmm 4 Core aluminium conductor laid in trenches/ducts or passing through pipes under road or fixed to poles including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / street light panel / junction box and testing on completion complete all as specified and as directed. |
| 11 | Supply and lay Double wall corrugated HDPE duct pipe of 50mm outer dia conforming to IS:14930 Pt-II with antirodant and non flame propergating properties of make and colour as approved by Engineer-in-Charge with fittings as protection to cable, laid in tranches or fixed to poles/walls for protection of LT/ XLPE cable complete all as specified and as directed. |
| 12 | Supply & fixing multi stranded copper cable PVC insulated unearthed 1100Volts grade of size 2.50 Sqmm 3.00 Core for connection from junction box to light fitting and making connection incl provn of lugs and testing for functioning of light fitting complete all as specified and as directed. |
| 13 | Supply and fixing as in replacement 120W LED floodlight shall be a commercial-grade luminaire with a system wattage of 120 watts providing a luminaire efficiency of minimum 120 lm/W. It shall have a correlated color temperature of 5700K and a Color Rendering Index (CRI) greater than or equal 80. The fitting must maintain lumen output for at least 50,000 hours and operate efficiently within a temperature range of -10°C to +50°C. It shall be equipped with toughened glass and a secondary lens offering a beam angle of 120 degrees.The input voltage shall be in the range of 120 to 277 VAC, with a system current of 1.86 amps at 240V, and operate at 50 Hz frequency. The light shall incorporate SPD protection of 5kV and 10kV and conform to Ingress Protection level IP66, complete all as of directed. |
| 14 | Supply & fixing as in replacement LED Street light 120 W outdoor type with high pressure diecast aluminium housing having rated luminaire efficacy of not less than 100 lm/W and power factor ≥ 0.95 , THD < 10 % with LED life span of > 50000 hrs provided with 5 kv internal surge protection and 10 Kv external surge protection including Ingress protection IP66 , Impact resistance >/= IK07, complete all as of directed. Note : The Driver & LED should be of same make. |
| 15 | Supply & fixing SMC (Sheet Moulded Compound) outdoor type junction box of size 200mm x 140mm x 95mm (Outside Dimensions) with 63Amps rated four pole connector, one single pole MCB of 6-20 Amps rating mounted on DIN rail, stainless steel cable glands of suitable size for incoming and outgoing cables including fixing on steel tubular poles / PCC poles with 25mm x 4mm MS clamps (02 Nos), nuts & bolts etc complete all as specified and as directed by Engineer-in-charge. |
| 16 | Supply & fixing as in replacement street light mounting bracket suitable for LED fitting of length 1.50 metre, made out of light grade GI pipe of 50mm bore bent to shape (120 degree) as directed by Engineer-in-Charge complete with two No GI Clamps made to shape out of 50mm x 6mm flat iron, with GI nuts, bolts and washers of suitable size for fixing on pole wall complete all as specified and as directed. |
| 17 | Making holes (02 Nos - one near cable junction box and other near street light bracket) on existing steel tubular poles of any type, thickness & height through drilling/ gas welding work having smooth and chamber edge of hole, for drawing street light control cable through inside of pole complete all as specified and directed by Engineer-in-Charge. |
| 18 | M&L for scraping old paint and applying painting to existing steel tubular poles 9.00 metre long with two coats of Aluminium paint on pole and cross arm, clamps, brackets fitted/ fixed on pole, above to 1.20 metre height & upto 9 metre of pole including preparing the steel surfaces to the entire satisfaction of Engineer-in-Charge and providing reflective strips of width 10cm upto a height of 1.20 metre from ground level in alternate colour green and white around the pole of pattern alongwith pole number marking with black paint at standard height with shade and colour as approved by Engieer-in-Charge complete all as specified and as directed. Please Enable Macros to View BoQ information |