| 1 | 1(A) Supply & fixing steel tubular pole 7.50 Metre long designated 410 SP-6 in 1:3:6 cement concrete foundation including excavation back filling Paint with 06 feet PVC Pole Cover , T&P having one year defect liability period with replacement complete in all respect. (SI No. 607 PWD Schedule 2018) |
| 2 | (B) Supply & fixing steel tubular pole 9.50 Metre long designated 410 SP-38 in 1:3:6 cement concrete foundation including excavation & back fillig Paint with 06 feet PVC Pole Cover , T&P having one year defect liability period with replacement complete in all respect.(SI No. 618 PWD Schedule 2018) |
| 3 | 2(A) (Cables in Existing Masonary Open Duct) Supply and Laying of 10 Sq mm 2 Core Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade on wall surface as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc (S.I No.20e. 1.2 PWD Schedule 2024) |
| 4 | (B)Supply and Laying of 16 Sq mm 4 Core Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade at depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc (S.I No.20a. 1.9 PWD Schedule 2024) |
| 5 | 3(A) Supply & fixing of LED Street light fitting with mandatory driver set laving dia cast aluminum body with toughend glass/UV Stbilized PC Cover and lenses suitable for 75 watt to 90 watt and Confirming to IP 66 and IK07 and above protection having Company LOGO Engraved including labour, Clamp, Bracket, Connection wire, and cables as required with 05 years warrantee/ guarantee with replacement as per direction of the Engineer in charge complete in all respects having Specifications as : – ”9000-10800 System Lumen, High Power LED with lenses , 120 L,m/w, PF > 0.95, THD < 10% at full load, CRI> 70, Polled Driver Set in metal housing (Not Circuitry), Phase to Phase Protection at 440 V & > 300 V over voltage auto cut and restart feature, 4 KV internal Surge Protection.” CAT – AAA (S.I No. 23.16 PWD Schedule 2024) |
| 6 | (B) Supply & fixing of LED Street light fitting with mandatory driver set laving dia cast aluminum body with toughend glass/UV Stbilized PC Cover and lenses suitable for 110 watt to 130 watt and Confirming to IP 66 and IK07 and above protection having Company LOGO Engraved including labour, Clamp, Bracket, Connection wire and cables as required with 05 years warrantee/ guarantee with replacement as per direction of the Engineer in charge complete in all respects having Specifications as : – ”13200-15600 System Lumen, High Power LED with lenses , 120 L,m/w, PF > 0.95, THD < 10% at full load, CRI> 70, Polled Driver Set in metal housing (Not Circuitry), Phase to Phase Protection at 440 V & > 300 V over voltage auto cut and restart feature, 4 KV internal Surge Protection.” CAT – AAA (S.I No. 23.17 PWD Schedule 2024) |
| 7 | 4. supply & fixing of 32 Amp 240 V DP metal clad rewireable type switch fuse unit on M.D.F.E.G / Teak wood board complete in all respect (S.I No. 305 CAT B) PWD Schedule 2018) (One Year Defect liability) |
| 8 | 5. S&F of 63 Amp. 415 V metal clad TPN HRC type switch fuseunit complete with HRC fuse on angle iron bracket complete inall respect. ( S.I No. 327 CAT B, PWD Schedule 2018) (One Year Defect liability) |
| 9 | 6. Supply and burying of 600mmx600mmx 6mmG.I.plate vertically for earthing with its top at least 3 meters below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG.G.I. wire will be extra) 30 cm square C.I frame with hinged cover masonary housing alternate layers of charcoal /coke and salt at least 150 mm thick alround etc. as per directions of Engineer –in-charge complete in all respects as per drawing ( This will apply for earthing of poles also)(S.I.No-702 PWD Schedule – 2018) Please Enable Macros to View BoQ information |