| 1 | DSR Item No.1.15Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 2 | Group C |
| 3 | DSR Item No.1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 4 | 3 x 1.5 sq. mm |
| 5 | 3 x 2.5 sq. mm |
| 6 | 3 x 4 sq. mm |
| 7 | DSR Item No.1.21Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 8 | 20 mm |
| 9 | 25 mm |
| 10 | DSR Item No.1.24Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 11 | 5/6 amps switch |
| 12 | 3 pin 5/6 A socket outlet |
| 13 | 15/16 A switch |
| 14 | 6 pin 15/16 A socket outlet |
| 15 | DSR item no. 1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 16 | DSR Item No.1.27Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 17 | 1 or 2 Module (75mmX75mm) |
| 18 | 3 Module (100mmX75mm) |
| 19 | 4 Module (125mmX75mm) |
| 20 | 6 Module (200mmX75mm) |
| 21 | 8 Module (125mmX125mm) |
| 22 | 12 Module (200mmX150mm) |
| 23 | DSR Item No.1.31Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 24 | DSR Item No.1.32Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 25 | DSR Item no. 2.3Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 26 | 8 way , Double door |
| 27 | DSR Item No. 2.23Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 28 | For 8 way, Double door SPN MCBDB |
| 29 | DSR Item No. 2.4Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 30 | 4 way (4 + 12), Double door |
| 31 | 8 way (4 + 24), Double door |
| 32 | DSR Item No. 2.24Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 33 | For 4 way, Double door TPN MCBDB |
| 34 | For 8 way, Double door TPN MCBDB |
| 35 | DSR Item no. 2.10Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 36 | Single pole |
| 37 | Double pole |
| 38 | Triple pole and neutral |
| 39 | DSR ITEM No.2.16Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 40 | DSR Item No.2.2Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 41 | Note: The MCCB should have adjustable overload and adjustable S/C protections ((Ics=100% of Icu). |
| 42 | 100 A,30KA,FPMCCB |
| 43 | DSR 9.1 Brush Less Direct Current (BLDC) Fan with RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance asper IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 44 | Supply & erection of U PVC trunking 100mmx 50mm with cover of M.K/ Legrand/ AKG make. The PVC Trunking should be fixed on the existing surface with the help of suitable size of steel fastners at each 1 mtr. Distance to hold the same properly. The rate include cost of material, carriage erection charges & petty material i.e. screws/ washers etc. to complete the job. |
| 45 | U PVC Trunking 100mm x 50mm. |
| 46 | External angle 100mm x 50mm |
| 47 | Internal angle 100mm x 50mm |
| 48 | End Cap 100mm x 50mm. |
| 49 | Supply & erection of fan rod 3’ long |
| 50 | Supply and fixing of 12 modules (200 mm x 150 mm) G.I box suitable for accommodate the following accessories along with modular base and cover plate for modular switches in recess / surface etc as required for Computer Point with 4 Nos. 5/6 Amp. modular switch and 4 Nos. 3 pin 5/6 Amp. modular socket outlet. The job includes the cost of making interconnections with suitable copper wire, painting of box with approved paint and other petty material required to complete the job to the entire satisfaction of Engineer-in-Charge at site. |
| 51 | Supply & erection of Exhaust Fan (heavy duty motor with copper wound metallic body) following size complete with motor, metallic blades, double ball bearing with minimum power consumption, rigid frame with rubber mounting for silent operation, epoxy powder coating along with metallic louver to be installed in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. |
| 52 | Size 15 inches (380mm) Sweep, 900 RPM Heavy Duty Exhaust fan (Single Phase) with louver of Havells (TurboForceSP)/Crompton(EXHD380-6-1)/ Bajaj(Supreme Plus)/ Orient (Industrial Heavy Duty)/ Usha (Turbo HDEF900RPM) make only. |
| 53 | DSR 8.10 LED Batten light (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumptionshould not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing requiredfor LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness >0.50 mm)18- 22 Watt |
| 54 | Supply & Erection of 1’x4’ approx. long Surface Type LED Luminaries complete in all respect to be installed on existing surface with the help of rawl plug & screws etc. The fitting should be Philips / Bajaj / Wipro / Crompton / Surya / Jaguar / Panasonic / Havells / Lighting Technologies / Trilux make only. The job includes the cost of testing, commissioning and making connection with 3x1.5 sq. mm copper wire from adjacent light point, other petty material and labour etc. as required to complete the same to the entire satisfaction of Engineer in Charge AS PER COMPLETE ITEM NO.21 OF DNIT. |
| 55 | S/E of 1’x1’ LED fitting surface type square type with integral/ non integral driver to be installed on existing surface with the help of rawl plug & screws etc. The fitting should be Philips/ Wipro/ Bajaj/ Havells/ Crompton/ Trilux/ Lighting Technologies/ Jaquar/ Panasonic/ Surya make only. The job includes the cost of testing, commissioning and making connection with 3x1.5 sq. mm copper wire from adjacent light point, other petty material and labour etc. as required to complete the same to the entire satisfaction of Engineer in Charge AS PER COMPLETE ITEM NO.22 OF DNIT. |
| 56 | Supply and Erection of B.L Holder on the existing junction box/ wooden block including making the connection etc as required. The job includes the all labour and petty material charges required to complete the job to the entire satisfaction of E.I.C. of work. Approved makes: Anchor/ Goldmedal/ Lauritz Knudsen &T/ Havells make only. |
| 57 | Supply and erection of sheet metal bus-bar chamber on existing surface with required No. of bus-bar strips of suitable length and cross-sectional area, made of copper strips of suitable length and cross-sectional area enclosure made of M.S. sheet 1.6mm thick with detachable cover fitted with dust excluding gasket and secured with sufficient No. of cadmium plated iron screws and of given overall dimensions and to be fixed with G.I. bolts and nuts / Rag bolts and nuts etc., complete with all accessories including connections with suitable size tin coated copper thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-Charge. |
| 58 | Sheet metal bus-bar chamber suitable for 100 Amp. 415 Volts capacity with 4 copper strip Bus-bars each of length 600 mm & cross-sectional area (25.4mmx3.17mm) enclosure having overall dimensions (680mm x 400mm x 150mm) nominal. Please Enable Macros to View BoQ information |