| 1 | Construction of Retaining Wall around OHSR @ Kodikunnu |
| 2 | 2.31:Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared |
| 3 | 13.4.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 coarse sand) |
| 4 | 13.44.1:Finishing walls with water proofing cement paint of required shade:New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 5 | Supply, Installation, Testing & Commissioning of Clear Water Pump at Putukunnu GLSR |
| 6 | OD343034/2025-2026:Supply, Installing ,Testing and Commissioning Electro Magnetic Flow Meter 200 mm ornearest size conforming to protection level of IP-68 for Flow Sensor and IP- 67 fortransmitter and having an accuracy level of 0.5% with LED/LCD Display unit. The flowmeter should have the housing (flow sensor) to be made of SS 304/ Carbon Steel withanti corrosive protection and inside liner to be made up of Hard Rubber / neoprene allconfirming to drinking water standards. The flow meter should be coupled with HART fordata acquisition and transfer, with provision for wireless transfer through GSM. Themanufacturers should have the calibration standards as per ISO 17025 and the productshall have sufficient warranty provisions.Test certificate from FCRI Palakkad. |
| 7 | OD343058/2025-2026:Design, Manufacture, Inspection, Transportation, SITC of Submersible HorizontalCentrifugal Pump set (1 no. Working + 1 no. Standby) as per specification for a duty of37.68 LPS at a total head of 88 mtrs at 1460 RPM per pump and suitable for operationon all-weather proof and Maintenance free type. The motor is submersible squirrelcage, induction type, 4-pole and dry type with class ?F? or ?H? insulation and IP 68enclosure fitted with ball bearing & mechanical sealing to ensure in high depthsubmergence condition and rated for 425V+/-10% AC, 3 Phase Supply of 50 Hz +/- 5%with suitable mounting frame and all electrical fittings including Power Cables (PVCInsulated Multi-Core), Star-Delta Starter, etc. including labour and fitting chargesincluding all accessories to make it operational, all complete as per direction ofEngineer-In-Charge. Material of Construction: Pump Casing, Motor Body, Oil Chamber,Impeller all SS/Similar material with Material and Shaft ? SS 410 The rate include costfor additional 2 year Warranty for the Pump and Motors, ie. Total 3 Years warranty. |
| 8 | 100.37.7.1:In situ fabrication of M.S. pipes of size 200mm (I.D.) using 8mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete. |
| 9 | 100.37.7.2:Fabricating M.S. flanges of diameter 200mm using 12mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete: For pipes fabricated with 8mm thick M.S. plates. |
| 10 | 100.37.7.3:Cutting 200mm (I.D.) M.S. pipes for making bends and other specials by gas cutting including cost of gas, all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates. |
| 11 | 100.37.7.4:Welding 200mm (I.D.) M.S. pipes for making bends and other specials by gas/electric welding machine including cost of gas and welding rods, all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates. |
| 12 | 100.37.7.5:Grinding cut and weld edges of 200mm (I.D.) M.S. pipes during fabrication work including all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates. |
| 13 | OD343067/2025-2026:All the additional Electrical works to make the system operational including charges foravailing necessary approvals from Electrical Inspectorate and KSEB for the additionalload including preparation of Single Line Drawings and all laisoning works. (Anystatutory fee to be paid by the KWA will be reimbursed to the contractor) Please Enable Macros to View BoQ information |