Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. |
| 3 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 6 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 7 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 8 | Supplying and drawing following sizes of FRLS/ HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 9 | 6 x 1.5 sq. mm |
| 10 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.25mm |
| 11 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 12 | 5/6 A switch |
| 13 | 15/16 A switch |
| 14 | 3 pin 5/6 A socket outlet |
| 15 | 6 pin 15/16 A socket outlet |
| 16 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 17 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 18 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 19 | 3 Module (100mmX75mm) |
| 20 | 6 Module (200mmX75mm) |
| 21 | 12 Module (200mmX150mm) |
| 22 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 23 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 24 | Single pole |
| 25 | Single pole and neutral |
| 26 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 27 | 8 way (4 + 24), Double door |
| 28 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 29 | 4 way (4 + 12), Double door |
| 30 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 31 | 12 way , Double door |
| 32 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 33 | 100 A, 16 KA, TPMCCB |
| 34 | Supplying and fixing 63 Amp rating, 415V, 10kA FP MCB \\"C\\" Curve in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 35 | Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. |
| 36 | 3 X 10 sq. mm (22mm) |
| 37 | 4 X 25 sq. mm (28mm) |
| 38 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt )Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C)................Cont........................ |
| 39 | Powder coated die cast /Extruded aluminum Body including trim18 watt |
| 40 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)36 watt |
| 41 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)36 watt |
| 42 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt).Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).100 watt |
| 43 | HI-WALL SPLIT SYSTEMSSupplying, Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with ndoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).Inverter Type - Cooling only |
| 44 | 1.5 TR with 5 Star BEE Rating |
| 45 | 2.0 TR with 5 Star BEE Rating |
| 46 | Supplying and installation of 1/2\\" and 1/4\\" copper pipe with insulation and copper cable insulation & drain pipe i/c brazing, testing, commissioning etc. as reqd. |
| 47 | Supply and installation of MS (Mild Steel) powder-coated stand suitable for supporting 1.0 / 1.5 / 2.0 Ton split AC outdoor units, wall/floor mounted type, including fasteners, clamps, rubber pads, and necessary accessories for proper fixing etc. complete as required. |
| 48 | S & fixing 3 Core 2.5 Sq.mm Round P.V.C insulated Copper Control cable i/c connection testing etc. as required. |
| 49 | Supplying, installation, Testing & Commissioning of 35-40W LED Post Top Fittings, powder coated pressure die cast aluminum spigot for mounting LED driver and aluminium canopy, Polycarbonate cover and clear acrylic diffuser with built in driver, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, 6500-5700°K i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty i/c testing commissioning etc. as required. |
| 50 | S.I.T.C. of electric ceiling fans 1200mm sweep shall be capacitor type, with double ball bearing complete with capacitor, 300mm down rods, canopies, three number blades made of aluminum alloy, suitable for operation on single phase, AC 230 volt, 50Hz supply but without regulator. |
| 51 | Supply, Installation of Single phase heavy duty exhaust fan of 380 mm sweep 900 rpm in the existing opening including making the hole to suit the size of the above fan, making good the damage, connections, testing, commissioning etc. as required. |
| 52 | Supplying Installation, testing and commissioning of wall mounted bracket fan sweep 400 mm PVC body local speed control complete with all accessories connection etc. as required. |
| 53 | Subhead-II (CCTV System) |
| 54 | 5/6MP IP IR Dome CameraSupplying Installation Testing and Commissioning of 5/6MP IP IR Dome Camera having following specifications and features etc.-1)Type of Camera: Dome Camera2) Image Sensor: 1/2.8\\" or better progressive Scan CMOS get color image even at night condition3) Signal System: PAL/NTSC4) Minimum Illumination: 0.008Lux@ F1.4, AGC ON, 0 lux with IR or better5) Imaging: 1/3s to 1/30000s Shutter Support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking.6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both.7) Signal to Noise Ratio: > 50 dB8) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source- Inbuilt IR LED's with effective distance upto 50 Mtrs integrated IR 30 Mtrs for colour view in night.9) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.72310) Wide Dynamic Range: WDR (120dB or more)11) Digital Noise Reduction: DNR (2D/3D) On/Off12) Streaming: Triple streaming, configurable13) Video Streaming & Frame Rates: Triple streaming , configurable Main stream: 5/6MP @25/30 fps, Sub streams: D1@25/30 fps or better...............................Cont............................. |
| 55 | 14) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser15) Profile Management: User configuration import, export16) Security: User Authentication, Water Marking17) Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card.18) Recording Management: Format SD, overwrite, storage management, video to NAS device,19) Edge Analytics : Tripwire, Intrusion, Motion Detection20) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection21) Alarm Support: It should have 1/1 Alarm In/ Out Port22) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with G.711U/A/ G.711Mu/ AAC/ G.726 audio compression23) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast,24) System Capability: ONVIF25) VMS: Camera shall support open source VMS26) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, , account lockout, video encryption, IP/MAC filtering, HTTPS, trusted upgrade.......................Cont........................... |
| 56 | 27) Ethernet: 1 RJ 45 10/100 Ethernet port28) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE—to ensure continuous operation in the event of a failure in one power source.29) Power Requirement: 12VDC/24VDC/PoE (802.3af)/ePoE30) Enclosure: IP67 weather proof, IK1031) Operating Condition: Ambient Temperature:- (-) 05°C to 50°C, humidity 95% (max) (non-condensing)32) IR life: 40000 hours or higher33) Video Bit rate: 32 KBPS - 8 MBPS or better34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS5MP/6MP IP IR 2.8/ 3.6/6/8/12 mm fixed lens (as per site requirement) Dome Camera. |
| 57 | 5/6MP IP IR Bullet CameraSupplying Installation Testing and Commissioning of 5/6 MP IP IR Bullet Camera having following specifications and features etc. 1) Type of Camera: Bullet Camera2) Image Sensor: 1/2.8\\" or better progressive Scan CMOS get color image even at night condition3) Signal System: PAL/NTSC4) Minimum Illumination: 0.006Lux@ F1.4, AGC ON, 0 lux with IR or better5) Imaging: 1/3s to 1/30000s, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking.6) On Screen Display: Camera should display Camera title, Date & Time in live & recorded video both.7) Signal to Noise Ratio: > 50 dB8) Lens Type & Focus: 3.6mm/6mm fixed lens ( optional as per site requirement)9) Day & Night: True Day & Night High Performance Mechanical IR cut filter with auto switch, IR Source- Inbuilt IR LED's with effective distance upto 50 Mtrs integrated IR and 30 Mtrs for colour view in night.10) Video Compression (Minimum): H.265 or better, H.265, H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726, AAC, G.723 11) Wide Dynamic Range: WDR (120db or more)12) Digital Noise Reduction: DNR (2D/3D) On/Off13) Streaming: Triple streaming, configurable.......................Cont............. |
| 58 | 14) Video Streaming & Frame Rates: Triple streaming , configurable Main stream: 5/6MP @25/30 fps, Sub streams: D1@25/30 fps or better15) Image Setting: Rotate Mode, saturation, brightness, contrast, sharpness adjustable through client software or web browser16) Profile Management: User configuration import, export17) Security: User Authentication, Digital Water Marking18) Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memory Card.19) Recording Management: Format SD, overwrite, storage management, video to NAS device,20) Edge Analytics: Tripwire, Intrusion, Motion Detection21) Alarm Trigger : Motion/tampering detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection22) Alarm Support: It should have 1/1 Alarm In/ Out Port 23) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out Port for external Mic. and Speaker (As per site requirement) with G.711U/A / G.711Mu/ AAC/ G.726 audio compression24) Network Protocol: SFTP, IPv6, IPv4, DNS, RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast,25) System Capability: ONVIF26) VMS: Camera shall support open source VMS.........................CONT.......................... |
| 59 | 27) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, account lockout, , video encryption, IP/MAC filtering, HTTPS, trusted upgrade.28) Ethernet: 1 RJ 45 10/100 Ethernet port29) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE—to ensure continuous operation in the event of a failure in one power source.30) Power Requirement: 12VDC/24 VAC/PoE (802.3af)/ePoE31) Enclosure: IP67 weather proof, IK1032) Operating Condition: Ambient Temperature: - (-)05°C to 50°C, humidity 95% (max) (non-condensing)33) IR life: 40000 hours or higher34) Video Bit rate: 32 KBPS - 8 MBPS or better35) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS5/6MP ((3200 × 1800)@20 fps or better) IP IR 2.8/ 3.6/6/8/12 mm fixed lens (as per site requirement) outdoor bullet Camera |
| 60 | Hard Disk Drive Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications.8TB (Terabytes) |
| 61 | Supplying, installation, Testing and commissioning of following capacity 8 port Layer 2 indoor Network Switch having features and specifications etc. as mentioned here under: Minimum 8 X RJ-45 Gigabit Ethernet Ports and additional 2 X 1G SFP Ports with non-blocking architecture by having Switching capacity of minimum 20Gbps and packet forwarding rate of 14Mpps or higher, 8K MAC table. Internal dual AC Power supply with operating temperature of -5 0C to +50 0C. Jumbo frame: 9KB or higher, IGMP Snooping, IGMP snooping querier and support for IGMP Snooping Fast Leave, Should create 250 or more MLD groups, MLD Snooping, Per VLAN MLD Snooping C MLD Snooping Fast Leave, STP, RSTP, MSTP, Loopback detection, Multicast filtering, VLAN Tagging, ǪOS: 8 Ǫue per port, WRR, IPv4/IPv6 Interface : minimum 100 IPv4 static route entries and minimum 50 IPv6 static route entries, 700 Acess Control entries, SSH CSSL for IPv4 and IPv6, 802.1x, ARP Spoofing, DHCP Snooping and server screening, IP+MAC+Port Binding, Per Port Bandwidth Control, 802.1X Authentication (Supports local/RADIUS database, Port-based Access Control and EAP, OTP, TLS, TTLS, PEAP Support) Cable Diagnostic feature, LLDP, LLDP-MED, SNTP/NTP, RMON, SNMP v1,v2c, v3 and SNMP Traps. Certifications: UL, CE, FCC, CE marked ,UL/EN, RoHS and relevant MTCTE (TEC)/ BIS comliance? certification as applicable,etc. complete as required.8 port PoE Layer 2 Network Switch with PoE Support of 130W or higher with each copper port supporting 802.3at PoE+. |
| 62 | Supplying, Installation, Testing and commissioning of small form-Pluggable (SFP) for Network Switches. Must be hot Pluggable, RoHS Complaint, etc. complete as required.(a) 10 G SFP + Single Mode/Multi Mode |
| 63 | Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel.24 Ports Cat-6 Patch Panel should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. |
| 64 | Supplying, Installation, Testing and commissioning of following CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required. |
| 65 | (a) Copper Patch Cords of length 1m (3ft) |
| 66 | b) Copper Patch Cords of length 3m (10ft) |
| 67 | Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required. |
| 68 | Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 23AWG Twisted Pair Cable in existing conduit/ on surface, Category 6 Unshielded Twisted Pair, 4 pair should be complied as per UL/ETL verification program for compliance with ANSI/TIA-568.2-D standard. Outer diameter should be in the range of 6.1mm nominal with Operating Temperature Range : -5° to +60°C. Bending Radius : < 4 X Cable Diameter at –5°C ± 1°C and Pulling Force: 11.5Kg |
| 69 | 1 run of cable |
| 70 | 2 run of cable |
| 71 | 3 run of cable |
| 72 | Supplying and drawing following core Fiber Optic Cable having corrugated steel armoring. The Fiber should be SM Fiber Central -loose tube filled with Thixotropic jelly, duly following Standards: ISO 11801, IEC 60793-1/60794-1-2, ITU-T-REC G.652D and Telecordia GR-20-core, High quality Electro Chromium Coated Corrugated Steel tape (ECCS ) and HDPE- Sheath, Operating ambient Temperature should be – 5 0C to +50 0C and Storage Temperature shall be – 5 0C to +50 0C, Max Attenuation ± 0.36 (db / km) at Operational Wavelength 1310 nm and ± 0.22 db / km at Operational Wavelength 1550 nm. type of fiber should be 9/125 / G.652D & Refractive Index should be 1.4670/1.4675. The value for Mode-filed,Cladding Diameter 9.2 ± 0.4 μm and 125 ± 0.7 μm correspondingly. The Dispersion value < 3.5 < 18 ps/nm-km and PMD value < 0.2 ps/km and Cable Cutoff wavelength < 1260 nm i/c splicing & marking etc complete as required.(a) Single Mode 12 Core Optical fiber cable |
| 73 | Supply and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required.9U Rack |
| 74 | LED Display Supplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required.55 inch or larger |
| 75 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 76 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 77 | 25 mm |
| 78 | 32 mm |
| 79 | Sub Head - III (POWER BACKUP Systems) |
| 80 | Online UPS - Input supply: Single Phase, Output Supply: Single Phase.Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins. and 150% for 1 minute. ...........................CONT............................. |
| 81 | Operating temperature 0 to 40 deg. C, Relative humidity 0-95% non-condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Display for watt/VA, Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accessories are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. |
| 82 | 2 KVA |
| 83 | 6 KVA |
| 84 | Sub Head - IV (Earthing & Safety Equipments) |
| 85 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 86 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 87 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 88 | SITC of ABC stored pressure type Fire extinguishers of 6 KG capacity fitted with discharge control valve and pressure gauge, filled with mono ammonium phosphate powder as per EN 3615 approved and supplied complete with initial charge as per IS: 15683 with ISI mark and wall bracket complete as required. |
| 89 | SITC of 4.5 kG capacity stored pressure type CO2 type fire extinguishers made from brand new seamless drawn steel cylinder as per IS 7285 with ISI mark, fitted with wheel valve as per IS 3224 with ISI mark, with discharge bend and horn and complete with initial charge as per IS 15683 with ISI mark and wall bracket complete as required. |
| 90 | Sub Head - V (LT Feeder Pillar, Accessories & Cable) |
| 91 | Fabrication, Supplying & installation of compartmentalised type Panel made of powder-coated CRCA steel / galvanized steel sheet of 2 mm thick for framework & covers, 3 mm thick for gland plate duly compartmentalised of suitable size to accommodate incoming and outgoing MCCBs/MCBs having 1.2 times of incomer insulated TPN aluminium busbar, DMC/SMC bus bar supports, with locking arrangement, vermin-proof, weatherproof and mounted on the MS stand of MA angle 40x40x5 with grounting minimum 300 mm depth including connection, inter connection, earthing with 2 Nos earth studs duly painted with one coat of red oxide & two coats of superior quality enamel paint complete etc. as required. (Depth should be 300 mm) |
| 92 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 93 | 200 A,36KA,FPMCCB |
| 94 | 125 A,36KA,FPMCCB |
| 95 | 100 A,30KA,FPMCCB |
| 96 | Supplying & fixing of following electrical accessories in the existing cubical panel/Feeder pillar including connection, inter-connection etc. complete as required. |
| 97 | 3Ph LED Ammeter Cl 0.5 accuracy Flush mounting 96 x 96 mm |
| 98 | 3Ph LED Ammeter Cl 0.5 accuracy Flush mounting 96 x 96 mm |
| 99 | LED Indication lamps (RYB) with selector switch (1 set of 3 nos.) |
| 100 | Supplying & Laying of following size one number PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 KV Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments on existing RCC/ HUME/ METAL/wall surface as required. |
| 101 | 3 x 10 sq. mm |
| 102 | 4 x 16 sq. mm |
| 103 | 4 x 25 sq. mm |
| 104 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 105 | Providing and fixing pole box of size 250mm X 200mm X 105mm with side openable hinged cover complete with two strip aluminium bus-bar of 100 amps capacity mounted on DMC bus support and 1 no. of SPMCB of 6 amps 'C' series capacity with din rail on the existing street light pole with the help of two nos. MS clamps of suitable size, including making hole to insert the cable and dismantling the worn out MS box etc. complete as required. |
| 106 | Sub Head - V (RO & Water Cooler System) |
| 107 | Supplying, Installation, Testing and Commissioning of stainless steel storage type water cooler 150/150 Ltr. capacity, fully stainless steel suitable for operation on 230 V+10% 50 Hz single phase AC supply i/c making water line and electrical connection etc. as required. |
| 108 | Supplying, Installation, Testing and Commissioning of Reverse Osmosis (R.O. System) water Purification unit as per Technical specification attached i/c Providing suitable wall/floor mounting bracket, water connection from the available water inlet point with suitable C.P. angle valve and outlet upto the nearest drain with suitable PVC pipe, complete etc. as required.Capacity:- 50 LPH CapacityMembrane:- 75/100 GPD (4 Nos)Input Power Rating:- 230 Volt AC, 50 Hz % of Rejection in TDS - 90% (Approx.)Indicator:- TD level of output water Tank full indication Audio Beep and No waterAuto Flush Timer Dry Run ProtectionU.V. Sterilization Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail