| 1 | SCHEDULE 'A' PART-I to SCHEDULE 'A' PART-XII:Note: Schedule 'A' Part-I to Part-XII are prepriced by MES. Bidders shall insert their lump sum amount in green coloured field under Column 6 only. |
| 2 | Lumpsum price worked out by the contractor for 'Buildings, Structures and Parking Shed' as listed in Schedule 'A' Part-I |
| 3 | Lumpsum price worked out by the contractor for 'SITE CLEARANCE/AREA DEVELOPMENT/ EARTHWORK EXCAVATION' as listed in Schedule 'A' Part-II |
| 4 | Lumpsum price worked out by the contractor for 'INTERNAL WATER SUPPLY'as listed in Schedule 'A' Part-III |
| 5 | Lumpsum price worked out by the contractor for 'INTERNAL ELECTRIC SUPPLY'as listed in Schedule 'A' Part-IV |
| 6 | Lumpsum price worked out by the contractor for 'EXTERNAL WATER SUPPLY'as listed in Schedule 'A' Part–V |
| 7 | Lumpsum price worked out by the contractor for 'EXTERNAL ELECTRIC SUPPLY' as listed in Schedule 'A' Part-VI |
| 8 | Lumpsum price worked out by the contractor for 'ROAD, HARDSTANDING ,PATH AND CULVERT' as listed in Schedule 'A' Part-VII |
| 9 | Lumpsum price worked out by the contractor for 'SEWAGE DISPOSAL]' as listed in Schedule 'A' Part–VIII |
| 10 | Lumpsum price worked out by the contractor for 'AREA DRAINAGE' as listed in Schedule 'A' Part-IX |
| 11 | Lumpsum price worked out by the contractor for 'LIGHTENING PROTECTION' as listed in Schedule 'A' Part-X |
| 12 | Lumpsum price worked out by the contractor for 'FIRE FIGHTING' as listed in Schedule 'A' Part-XI |
| 13 | Lumpsum price worked out by the contractor for 'COPPER EARTHING' as listed in Schedule 'A' Part-XII |
| 14 | Schedule 'A' Part-XIII (MISCELLANEOUS ITEMS) (TO BE QUOTED BY THE TENDERER IN BOQ): |
| 15 | INTERNAL ELECTRIC SUPPLY: |
| 16 | Energy efficient LED ceiling light fitting 08 watt, minimum 800 lumen output integral round shape, 230V surface mounted with necessary diffuser complete with mounting bracket etc including connecting up with twin core twisted flexible copper conductor cable with sutiable size. Make : Philips/Bajaj/Havells/GE/ Wipro/Surya |
| 17 | MCB vertical TPN DB 4 way 415V, 50 Hz double door, IP 43 protection with 200A rated bus bar for provision MCCB as incommer and MCBs for outgoing circuits complete, fill empty with blanks, making good the disturbed area complete all as specified and directed. Make: LEGRAND/ Siemens/ ABB/ C&S/ GE/ Schneider |
| 18 | Flame Proof LED bulk light fitting 40 Watt or minimum lumen output is not less than 4000 lumens, 240 volts with complete drive all as specified and directed. Make : CG or equalent Sudhir/Baliga/Shyam (for Magazine and amunation Wksp) |
| 19 | Energy efficient LED light fitting with tube 38 watt or minimum lumen output is not less than 3800 lumens, 230V surface mounted LED batten type with extruded aluminium/CRCA housing and robust construction with necessary acrylic cover as diffuser complete with mounting bracket etc including connecting up with twin core twisted flexible copper conductor cable with suitable size. Make : Philips/Havells/GE/Wipro |
| 20 | Flame proof MCB DB TPN 6 way as per IS with MCB TPN 63 A- 01 as incomer & MCB SP 16 Amps -02 Nos (Magazine 600LT AHU Room and Ammunition work shop (HTL) and steel phospetised powder painted with 200 amps rated bus bar 240 volts neutral link, making good the disturbed area as per existing surface complete. (For Magazines), Make : Sudhir/Baliga/Shyam |
| 21 | Flame proof MCB DB TPN 8 way as per IS with MCB TPN 63 A-01 as incomer and MCB SP 16Amps-08 Nos (Ammunition work shop(HTL lighting Circuit) and steel phospetised powder painted with 200 amps rated bus bar 240 volts netural link, making good the disturbed area as per existing surface complete. Make : Sudhir/Baliga/Shyam. |
| 22 | Flame proof MCB DB TPN 8 way as per IS with MCB TPN 63 A- 01 No as incomer and MCB SP 16 Amps-10 Nos (Magazine 600 LT) and steel phospetised powder painted with 200 amps rated bus bar 240 volts neutral link, making good the disturbed area as per existing surface complete. (For Magazines), Make : Sudhir/Baliga/Shyam. |
| 23 | Earthing complete with GI earth plate electrode 60cmx 60cmx6mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to GI earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No-3 of SSR Part-I connected to earthing test point all as specified or indicated including excavation and connected earth work in hard/ dense soil., PCC 1:3:6 type C-1 as in pit, 20 mm dia GI pipe medium grade for watering pipe, 15 mm bore GI medium grade earth lead protection pipe connected upto DBs and suitable C.I top cover with handle, funnel, strainer, charcoal and testing on completion all as specified and directed. Note: Rate quoted deemed to be include excavation and earth work in any type of soil with PCC type B2 in pad and pit complete all as specified and directed. |
| 24 | Earthing complete with GI earth plate electrode 60cmx60cmx6mm thick, burried directly in underground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and include GI earth strip 32x6 mm alternate 5 layer ofn charcoal (250kg) & salt crystal (200kg) and top two inches layer with back filling compound (100kg) , in 40mm dia GI pipe light grade by means of nuts bolts, washer and necessary earth work in any type of soil , PCC (1:3:6) Type C-1 chamber and RCC (1:2:4) Type B-1 covers and watering pipe 20mm dia medium grade with funnel complete with mesh, refiling with black cotton soil , testing on completion all as specified and directed. Note -(i) Rate quoted deemed to be include necessary excavation and earth work in any type of soil with PCC type B2 chamber, RCC cover, reinforcement, removal of surplus soil, site clearance complete all as specified and directed. |
| 25 | (ii) GI Earth strip 32x6 mm, GI tubing light grade 40mm dia up to 7.5m deemed to be included the rate quoted by the contractor (iii) Beyond 7.5m the gi earth strip 32x6mm & GI pipe light grade 40mm dia shall be measured under the respective item of the schedule. Desired earth resistance shall be not less than one OHM ,if the desired result is not acheived, the earthing will be re done No Extra Cost. Earthing pit display boards made out of 3mm thick MS sheet of size 30x35 cm welded to 75 cm long 25x25x5 mm thick MS angle iron grouted in PCC 1:3:6 (using 20mm graded stone aggregate ) to a depth of 20 cm below GL and including applying two coats of synthetic enamel paint of approved colour over coat of red oxide primer on all exposed steel surfaces and writing the letter on plate for showing the details:- Earthing pit No: Date of measurements : Next due date: standard valve: valve obtained; ON testing after completion from test point. |
| 26 | EXTERNAL WATER SUPPLY: |
| 27 | Construction of Valve chamber of size 900x 900x 600mm (internal dimentions) including excavation of earth work in any type of soil,100mm thick PCC 1:4:8 type D2 as in foundation , made out of 230mm thick brick work in cement mortar 1 :6 with 15mm thick plastering in cement mortar 1:4 internally complete and upto 150mm below ground level for external faces with 100mm thick plain cement concrete 1:3:6 type C1 using 20mm graded aggregate as in coping, cover frame made up of 50x50x6mm and 3.15mm thick MS sheet as cover with two Nos of hinges and one No handle made out of MS round bar 10mm dia with neccssary locking arrangement including finishing the exposed steel sufraces with two coats of synthetic enamel paint over a coat of red oxide primer and two coats of white wash on plastered surfaces complete all as specified. |
| 28 | EXTERNAL ELECTRICAL SUPPLY: |
| 29 | Supply, install , testing and commissioning of outdoor type CPRI certified LT Panel board totally enclosed factory fabricated made out of 3mm thick CRCA sheet steel with dust and vermin proof, hinged front opening door shutters with neoprene rubber gasket with base frame of 75x75x6mm powder coated including danger plate, GI earth strip 25x3mm-02 Nos, ventilation, louvers, bottom detachable gland plate complete, cubicle panel board suitable for 3 phase 4 wire, 415 volts 50 Hz with locking arrangement in and with necessary termination arrangements like lugs, glands for both incoming and outgoing LT UG Cables including supply the following switch gear complete all as specified : (For 600 LT Magazine)INCOMINGMCCB 400 Amps 4 Pole, 50 KAOUTGOINGMCCB 350 Amps 3 pole, 36 KA-01 No (AC Plant)MCCB TP 100 Amps, 3 pole, 16KA-01 No (Crane)MCCB TP 63 Amps, 3 pole, 16KA-02 No (street light spare)MCCB TPN 63 Amps, 4 pole, 16KA-02 (600 LT Magazine bldg, spare)MCB SPN 40 Amps-05 (plant room, AHU room, cycle shed, change room, spare)Indication lamp (RYB)-01 NoVoltmeter digital type (0 to 500 Volt)-01 NoAmmeter digital type 0 to 400 Amps with CT and selector switch-01 NoBusbar Aluminium 800A (RYB & N)-01 No |
| 30 | LED street light 24W of minimum 2400 lumens output pressure die cast housing with epoxy powder coated dark graphite with heat resistant puffend glass and IP 65 protection in and including GI tubing medium grade 25 mm dia of 1.5 mtr length bent to shape including flat iron clamps of 20x3mm- 02 Nos with nut bolts and washers complete all as directed. Make : Philips Cat No BRP20 1x24 HP LED or equivalent of WIPRO/K LITE/CG. |
| 31 | Junction box (weather proof) on street light pole made out of themoplastic of size 275 mmx 135mm x 110 mm size with 01 No four pole connector with nuts & bolts for 03 phase and 01 neutral and including provision of 01 No MCB SP 6 Amp with DIN Channel to control the pole light circuit with MS clamps made out of FI 32x4 mm for fixing the box to pole complete with nuts, bolts and washers including necessary cable connection with suitable size cable lugs, complete all as specified and directed.Make: Sintex/Hensel.Make for MCB: Legrand/Siemens/L&T |
| 32 | FLAT/ROUND cable weather proof PVC insulated PVC sheathed multistranded 1100 volts grade with copper conductor 3 core 2.5 sqmm from loop in box to street light fittings all as specified. Make: Finolex/Gloster/Polycab |
| 33 | CI cable route indicator of oval shape with letter embossed as LT or HT UG Cable fixed to MS Angle of size 40 x 40 x 6mm, 6 cm long embedded in PCC block of size 40 x 40 x 25cm (LxWxH) in PCC 1:2:4 type B1 using 20mm graded aggregate including painting of exposed steel surface all as specified. |
| 34 | Laying only, testing cable XLPE insulated screened PVC bedded galvanised steel strip (or) wire armoured electric power cable (heavy duty) 1100 Volts grade with strandard aluminium conductor of size 4 core 16 Sqmm all as specified. |
| 35 | Laying only, testing cable XLPE insulated screened PVC bedded galvanised steel strip (or) wire armoured electric power cable (heavy duty) 1100 Volts grade with strandard aluminium conductor of size 2 core 10 Sqmm all as specified. |
| 36 | ROAD, HARDSTANDING, PATH AND CULVERTS: |
| 37 | 150mm compacted thickness wet mix macadam (WMM) laid/rolled in two layers (each layer 75mm thick compacted seperately) with slip form paver rolled, consolidated and compacted to required gradient and camber all as specified and directed . |
| 38 | FIRE FIGHTING: |
| 39 | Construction of Valve chamber of size 900x900x600mm (internal size) including excavation of earth work in any type of soil,100mm thick PCC 1:4:8 type D2 as in foundation, made out of 230mm thick brick work in cement motor 1 :6 with 15mm thick plastering in cement mortar 1:4 internally complete and upto 150mm below gorund level for external faces with 100mm thick plain cement concrete 1:3:6 using 20mm graded aggregate all around and reinforcement cement concrete slab 1:2:4 type B1 using 20mm size graded stone aggregate of size 95x95x5 cm thick with 10mm dia deformed bars @ 12 cm centre to centre on both the direction with 10mm dia mild steel handle 250mm long bent to shape and fixed with steel angle iron and flat iron including finishing the exposed steel sufraces with two coats of synthetic enamel paint over a coat of red oxide primer and two coats of wihte wash on plastered surfaces complete all as specified. |
| 40 | Foam spray nozzle 63mm x 19 mm dia complete all as specified. |
| 41 | Atmospheric Foam tank concentrate tank 4500 Ltrs made out of stainless steel or carbon steel with thermoplastic internal lining., externally fire red epoxy coating with expansion dome including provisional inbuilt ladder, pressure guages, drain out valve arrangements, vent valve , filling connection, return connection, foam mixing arrangements in and inlcuding with Foam maker induction tank with angle iron frame work of 100x100mm with internal bracing placed on RCC pedestals of 01M height above GL including with all required accessories complete and initial filling of foam capacity complete all as specified and directed. |
| 42 | Fire hydrant stand post type for provision of single out let of size 63mm dia completed all as specifed. |
| 43 | COPPER EARTHING: |
| 44 | Earthing complete with copper earth plate electrode 60cm x 60cm x 3mm thick buried directly in ground earth pit not less than 2.25 M deep below normal ground level and complete earth plate connected to copper strip of size 20 x 3 mm by brazing only earth strip protected with light grade GI pipe 40mm dia bore from copper earth plate electrode and upto in and including the earth test point made of gunmetal phosporous bronze of size 75x75x25 mm including 25mm bore water pipe medium grade GI tubing including GI Funnel, wiew mesh. alternate 5 layers of charcoal (100 Kg) & salt crystal (75 Kg) and top two inches layers with back filling compound (100Kg) including excavation in strata, refiling with black cotton soil above the back filling compound and removal of the excavated soil and depositing at the place where directed.PCC pit in PCC (1:3:6) Type C1 using 20 mm graded stone aggregate, RCC (M) cover 40mm thick in RCC (1:2:4) type B1 usign 20mm grade aggregate reinforced with 8 mm dia TMT bars @ 7.5 mm C/C both ways including MS angle iron frame of 40 x 40x3 mm etc watering the earth pit to acheive earth resistance below 01OHM incl testing all as directed and specified. (for secondary ground).Note: Copper earth strip of size 20x3mm and GI Pipe 40 mm bore light grade up to 7.5 M length deemed to be included in the rate quoted by the contractor beyond 7.5 M copper strip of the size 20x3mm and GI pipe 40 mm bore light grade shall be measured and paid under the respective item of the schedule. 2. desired earth resistance shall be not less than OHM. 3. If the desired result is not acheived, the earthing will be re done no extra cost. earthing pit display boards made out of 3 mm thick MS sheet of size 30 x 35 cm welded to 75 cm long 25 x 25 x 5 mm thick MS angle iron grouted in PCC 1:3:6 (using 20 mm graded stone aggregated) to a depth of 20 cm below GL and including applying two coats of synthetic enamel paint of approved color over a coat of red oxide primer on all exposed steel surfaces and writing the letter on plate for showing the details : earthing pit No : date of measurement : Next due date : standard value : value obtained : on testing |
| 45 | after completion from test point the desired earth resistance shall be not less than 1 OHM. If the desired result is not obtain the earthing will be re done no extra cost. |
| 46 | CRANES: Please Enable Macros to View BoQ information |
| 47 | CRANES: Please Enable Macros to View BoQ information |