| 1 | PVC INSULATED FR COPPER CONDUCTOR CABLES:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 2 | Overall size 1.5sq.mm (Un-sheathed) |
| 3 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 4 | Double Walled Corrugated HDPE Pipe 50/ 38mm (Outer/ Inner dia.) |
| 5 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE):Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- |
| 6 | Overall size 16sq.mm (4Core) Un-armoured (Loose) |
| 7 | Supply & erection of 20W LED Bulb B-22 white. Complete in all respect as desire by the Engineer in charge of work at site. The certification and specification of the LED fitting should be as approved by office Advisor Technical Govt. of Punjab vide letter NO. AT2021 GL 1410-1422 Dated 06-05-2021. Beside this the lighting fixtures manufacturer should have in house NABL accredited LAB. |
| 8 | Supply and erection of LED Street Light 45 watt (including LED driver) with pressure die cast aluminium housing with control gear ( IP 66 protection),THD< 10%, CRI minimum 70, High power LED with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, efficacy of LED fixture minimum 120 lumens per watt, complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to CM Punjab vide letter No. AT-2021/GL 1410-1422 Dated 06/05/2021. Beside this the lighting fixtures manufacturer should have in house NABL accredited LAB. |
| 9 | MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 10 | MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 11 | PAINTING INCLUDING LABOUR AND MATERIAL:Painting of Steel tubular pole with brackets with two coats of aluminium paint (With brush):- |
| 12 | Overall Length 7 Metre |
| 13 | Overall Length 8.5 to 9 Metre |
| 14 | Upgrading of existing Sub Station System:-INDOOR LT PANELS: LT PANELS & MCCB's (MOULDED CASE CIRCUIT BREAKERS): Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55).SUB LT PANEL (NORMAL): |
| 15 | LT Panel enclosure having space for 1No. Incomer MCCB 630Amp. and 6Nos. outgoing MCCB's 40amp. to 250amp. (Option: MCCB 200-250amp.= 2Nos. and MCCB's 40-100amp.= 4Nos.) according to the requirement at site (Approx. size 1475 x 1800 x 400mm) |
| 16 | MCCB's (FOR PANELS & SHEET ENCLOSURE):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc |
| 17 | MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 18 | MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting |
| 19 | MCCB Four Pole 630amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting |
| 20 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE):-Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- |
| 21 | Overall size 400sq.mm (3½ Core) Un-armoured (Loose) |
| 22 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 23 | Double walled corrugated (DWC) HDPE pipe120/103.50mm (outer/ inner dia.) |
| 24 | ON LOAD CHANGEOVER SWITCH (Without Sheet Enclosure):Supply and erection of On Load Change over Switch with advance neutral UNIT (Panel mounting Cubical type) in the existing Cubical Panel Confirms to IS 13947 (Part-3) complete with G.I. Bolts, Nuts & Connections on both sides of switch with suitable size of thimbles as per PWD General Specifications:- |
| 25 | On Load Change Over Switch Four Pole 400amp., 415volts |
| 26 | INDOOR LT CABLES, CABLE TRAY & DWC PIPE:CABLE TRAY:Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications:- |
| 27 | Cable Tray Size 300mm x 50mm x 50mm (2mm thick) |
| 28 | Supply and erection of heavy duty brass single compression gland for cable end termination duly complete with checknuts etc. including making necessary connections:- |
| 29 | Brass Gland for Aluminium cable 3/3½/4 Core size 400sq.mm |
| 30 | Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:- |
| 31 | Aluminium thimble cable Core size 240sq.mm |
| 32 | Aluminium thimble cable Core size 400sq.mm |
| 33 | COPPER EARTHING COPPER EARTHING (Upto 8 metre in Length):Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 34 | Earthing with 20mm x 3mm Copper Tape (upto 8Metre in Length) |
| 35 | COPPER EARTHING STRIP (As Additional Length):Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:- |
| 36 | Additional Length 20mm x 3mm thick Copper Tape |
| 37 | 8 SWG COPPER EARTHING :Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 38 | Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 4.50 metre (14.76 feet) below ground level (up to 8metre in Length) with G.I. pipe 20mm dia. (A-class), 3metre long |
| 39 | Charges of ACB Servicing including Maintenance, Closing tripping coil, contact relays etc. (2) VCB Servicing including Maintenance, Closing tripping coil, Vacumm interruptor checking, IR test, COOC operation test, High pot test etc. (3) Dry type Transformer Servicing including visual inspection of trasformer core, tightining of HVLV terminal, IR test, PI test, turn ratio test, temprature sensor test etc. (4) Bus Bar contact resistance test, Measurement and IR test etc. complete in all respect. |
| 40 | Providing Advance Lightning Protection System:- |
| 41 | Providing Advance Lightning Protection System:-Supply, installation, testing & commissioning of fully autonomous Early Streamer Emission Lightning Air Terminal (ESEAT) comprising of floating panels/body isolated from an earthed central finial/tip (elevated sharp tip) on top of the highest point to protect from direct lightning strikes with the following technical parameters. As per NF C 17-102 : 2011, (Annexe C), Clause C.3.4 ESE terminal is tested & certified for the below parameters. • ESE air terminal should be tested for an Impulse current (10/350 micro sec)=103 KA • Charge (Q) = 54.9 A.s • Specific Energy (W/R) = 2500 KJ/Ω and as per Clause C.3 all the tests should be carried out on a sample (preferably all tests in one lab) according to the flow chart in figure C.1 (Sequence of testing) pg 69 i. General tests, ii. Mechanical tests, iii. Environmental tests, iv. Electrical tests, v. Early Streamer Test (Δt in 10μs to 60 μs and standard deviation) • For the local certification, the ESE air terminal should be tested for switching impulse current of 40 KA (8/20 micro sec) or more. LPI is Tested & certified by CPRI (Central Power Research Institute), Govt of India for the Impulse current of 70 KA with 5 positive & 5 negative impulse • The International testing laboratory should be duly accredited by ILAC / IEC / ENAC / EZU / UL to ensure the genuine testing and the quality of the product. The serial number displayed on the ese lightning arrester is duly supported with the \\"certificate of country of origin\\" issued and duly sealed by the Australian Government \\"Chamber of Commerce & Industry\\". Complete in all respect and as per design and size approved by engineer incharge at site. |
| 42 | GALVANIZED IRON PIPES AND G.I. EARTHING: Supply & erection of G.I. pipe (A-Class) as per IS:1239 (Part-I) 2004 including sockets, bends, inspection boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:- |
| 43 | Galvanized Iron Pipe 50mm dia. (A-class) Flushed |
| 44 | COPPER EARTHING (Upto 14 metre in Length):-iii- Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 45 | Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length) |
| 46 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 47 | Overall size 70sq.mm (Un-sheathed) |
| 48 | DESKTOP , COMPUTER, PRINTERS, ETC OTHER ACCESSORIES |
| 49 | Supply and Installation of Computer 14th Generation intel core 17 processor 23.8\\" FHD display 16 GB DDR 5 RAM 1 TB SSD Hard disk Multimedia Keyboard, wireless Mouse, Speaker, LAN card and Modem, pre loaded legal window operating System software (with media), UPS 0.7 KVA (with 30 minutes back up) Computer complete as per specifications & as desired by Engineer-in-Charge. |
| 50 | Supply and Installation of A 43-inch smart TV typically features a 4K UHD LED display, 60Hz refresh rate, and HDR support. Common smart systems include Android TV, Google TV, or Tizen, with built-in Wi-Fi, Bluetooth, 2-3 HDMI ports, and 20W+ speakers complete as per specifications & as desired by Engineer-in-Charge |
| 51 | Supply and Installation of Laser print, Scan, Copier 3 in 1 Print machine Laser technology, Up to 30 PPM COLOURED MACHINE, Print Resolution: 600x600, Connectivity: Ethernet, 2GB Memory, 10.Inch Smart Touch Panel Zoom range 400%, HDD: 320 GB, Copy Speed: 25 cpm complete as per specifications & as desired by Engineer-in-Charge. |
| 52 | Supply and Installation of Table Fan Commonly 400mm (16 inch) for standard, 200mm-300mm, High-speed My fans generally operate between 1300-2400 RPM, 40W to 115W Power Consumption., Usually 3 to 5 aerodynamic polypropylene blades, Plastic, ABS, or metal bodies, Oscillation (up to 180\\"), tilt adjustment, and 100% coppe complete as per specifications & as desired by Engineer-in-Charge. |
| 53 | Supply and Installation of 14th gen Intel or AMD Ryzen 9 processors, 16GB RAM, and 1TB SSD, microsoft windows, MS Office, Antivirus etc Laptop complete as per specifications & as desired by Engineer-in-Charge. |
| 54 | Supply and Installation of fans usually feature 35-41 L tanks, 3 speed settings, and 260-350W motors, capable of cooling up to 800-1400 sq. ft. through centrifugal misting Mist fan complete as per specifications & as desired by Engineer-in-Charge. |
| 55 | Supply and insallation of PVC Extension box of suitable size with 3 Nos. sockets and 1 switch of 6 Amp each including PVC insultated PVC Sheathered round flexible wire with copper conductor (FR Cable) ISI Marked up to minimum 5mtr in length with 3 pin 6Amp shoe, complete in all respects as approved and desired by the Engineer-in-Charge |
| 56 | Supply and insallation of PVC Extension box with 1. Nos switch and sockets of 16/20Amp each with extension wire with copper conductor (FR Cable) ISI Marked of min. 5mtr in length with 3 pin 16/20Amp shoe, complete in all respects as approved and desired by the Engineer-in-Charge. |
| 57 | Add Cultural Cess 1% Please Enable Macros to View BoQ information |