| 1 | Shifting of overhead HT/ LT lines along approach road |
| 2 | HT Cables (CB-HT)Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (round ) cable 33 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT ( Note -2 pg. no. 119 pwd el. dsr 2023-24 For round wire armouring increase rate For 11 kV (E) by 15% & For 11 kV(UE), 22 kV, 33kV (E)/(UE) by 18% ) |
| 3 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (Round) cable 11 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT ( Note -2 pg. no. 119 pwd el. dsr 2023-24 For round wire armouring increase rate For 11 kV (E) by 15% & For 11 kV(UE), 22 kV, 33kV (E)/(UE) by 18% ) |
| 4 | Providing and erecting Heat shrinkable outdoor termination kit for 11 KV (E) XLPE HT cable 3x240 to 300 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 5 | Providing and erecting Heat shrinkable straight through joint kit for 11 KV (E) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 6 | Providing and erecting Heat shrinkable outdoor termination kit for 33 kV ( E )/33 kV (UE) XLPE HT cable 3x300 sq. mm. to 400 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 7 | Providing and erecting Heat shrinkable straight through joint kit for 33 kV ( E )/33 kV (UE) XLPE HT cable 3x300 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 8 | Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 9 | Supplying & laying (including excavation) half round reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 10 | Supplying and erecting rolled steel joist (girder) pole 125 x 70 mm (13.3 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 11 | Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 12 | Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 13 | Supplying and erecting V cross arm with ISM channel of 75x40x6mm for 11kV HT OH line with arrangement to fix insulator at 45mm from the end & horizontal distance between insulators 1220mm bent at angle of 60 degree keeping base 305mm and the total vertical height of V cross arm as 460mm, and fixed on pole with MS clamp of 80x10 mm, nut bolts, washers complete as per specification no. OH-PL/VCA |
| 14 | Supplying & erecting MS pole bracket for guarding/LT OH line, fabricated from angle iron 50x50x6mm and 1100mm long for necessary nos. of provided insulators, and erecting on pole with 50x6mm clamp complete as per specification no. OH-PL/BKT |
| 15 | Supplying & erecting 100 x 50 x 6 mm with 4.7 mm thick web and 7.5 mm thick flange channel iron cross arm of suitable length for 2.4 m wide DP structure and erecting on DP with 50x6mm clamp complete as per specification no. OH-PL/BKT |
| 16 | Supplying and erecting bracket for guarding of HT OH Line, made from channel iron 1600mm in length and 75x40x6mm. erected on pole complete as per specification no. OH-PL/VCA |
| 17 | Supplying & erecting inline D. P. Structure for 11/0.415 kV, 100 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 200 Amps as incomer & 6 Nos. 100 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos. of Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 mm for erecting Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min. 124 Kg. iron work ) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire, D.P. Structure shall be erected in c.c. foundation complete |
| 18 | Supplying and erecting ACSR conductor of size - 6/1-4.72 mm (Dog) complete. (394.00 kg/km) as per specification No. OH-CON/ACSR |
| 19 | Supplying, erecting & terminating XLPE insulated 1100 V 3 Core 95 sqmm + 1 Core 70 Aerial bunched aluminium cable along with necessary accessories for LT distribution on provided LT pole as per specification no. OH-CBL/ABC |
| 20 | Providing & erecting junction box as per MSEDCL specification for LT line 3ph 4Wire with all accessories complete ( Msedcl basic rate Rs 2000 x 1.35 labour & transportation charges = Rs2700 ) |
| 21 | Supplying and erecting porcelain shackle type LT medium insulator 75x115mm dia. with G.l. (shackle) strips, nuts and bolts, complete. |
| 22 | Supplying and erecting aluminium bobbin with G.l. (shackle) strip, nuts complete. |
| 23 | Supplying and erecting porcelain pin type insulator with GI pin suitable for 11kV line, complete as per specification no. OH-INS/PN |
| 24 | Supplying and erecting porcelain disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI |
| 25 | Supplying and erecting porcelain pin type insulator with GI pin suitable for 33kV line, complete as per specification no. OH-INS/PN |
| 26 | Supplying and erecting porcelain disc type insulator 70 KN with necessary hardware suitable for 33kV line complete as per specification no. OH-INS/DI |
| 27 | Supplying, installation, testing and commissioning extendable/non-extendable outdoor type 33 kV 800A, load break isolator switch, compliant to IEC 62271 - 102,on provided MS channels/trench/foundation as per MSEDCL specifications. (msedcl baisc rate Rs 80000 x 1.35 labour & transportation charges = Rs 108000 ) |
| 28 | Supplying ,erecting, testing & commissioning of 11KV A B Swich as per MSEDCL requirement. ( MSEDCL basic rate Rs 11088 x 1.35 labour & transportation charges =Rs 14969 ) |
| 29 | Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws, G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete. |
| 30 | Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 31 | Making Cement concrete foundation including excavation (60 x 60 x 150)cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay). |
| 32 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 33 | Providing & erecting danger board in yard (MSEDCL basic rate 57.50 x 1.35 labour & transportation charges =Rs 77.6) |
| 34 | providing & erecting Strain hardware for Dog 0.1 or Equ.AAAC. as per MSEDCL specifications (Msedcl basic rate Rs 369.91 x 1.35 Labour & transportation charges = Rs 499) |
| 35 | Providing & erecting strain hardware for 34 sqmm AAAC as per MSEDCL complete ( Msedcl basic rate Rs 161 x 1.35 labour & transportation charges = Rs 217) |
| 36 | Supplying and erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.). |
| 37 | Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etc. as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces etc. and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete. (PWD Civil SSR 2022-23) |
| 38 | Painting of steel tubular/ rail/ RSJ pole above 6.0m length along with street light pole brackets, clamps etc by scrapping the existing paint complete as per specification no CW -PTG/PTP. |
| 39 | Dismantling the existing pole above 6 m height with brackets, clamps, insulators, stay from the c.c. foundation and making the site clear by refilling the pits with excavated materials and bringing it to the ground level. |
| 40 | Dismantling the existing overhead line including G.I. wires of all sizes without damaging & making the coils in suitable sizes. |
| 41 | Dismantling existing pole mounted distribution transformer safely without any damages. |
| 42 | Erection & commissioning of 100KVA ,11/0.433KV distribution transformer already dismantled safely at required site complete |
| 43 | Providing & erecting 7 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 44 | Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/BKT |
| 45 | Supplying and erecting integrated LED street light fitting 85-90W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 9300 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including driver complete with minimum 2 Years warranty as per specification No. FG-ODF/SL. |
| 46 | Making M-20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal/conical GI pole). |
| 47 | Making Cement concrete foundation including excavation (60 x 60 x 150)cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay). |
| 48 | Supplying & erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places. as per specification no. WG-MA/BW |
| 49 | Supplying & erecting three phase, 415V, street light control panel upto the max load of 12kW, TPN MCB 63A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54, IK10 protection suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation with overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation as per specification SW-STCP. |
| 50 | Supplying, installing and testing earthing with galvanised iron earth plate size 60 x 60 x 0.6 cm complete with all accessories of GI materials & recording the results as per specification No. EA-EP |
| 51 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 52 | Supplying, erecting & marking SP MCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 53 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 54 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 25 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 55 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 56 | making Horizontal Directional Drill / Bore of 150 mm dia and depth up to 1.5 mtr in soft soil and laying 150 mm HDPE/GI pipe etc. complete as per specification no. CW-EXN-CTR (PWD DSR E & M 2022-23) |
| 57 | Supplying, installing, testing & commissioning of 3 phase, 11/0.433 kV, 50 Hz., 100 kVA, Mineral oil immersed and naturally cooled outdoor type, aluminium wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40? by thermometer in oil and 45? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) , with standard accessories complete with test certificate with losses below 475 Watts at 50% load, 1650 Watts at 100% load as per IS:1180 (part 1) : 2014, with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL. |
| 58 | Supplying & erecting inline D. P. Structure for 11/0.415 kV, 100 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 200 Amps as incomer & 6 Nos. 100 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos. of Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 mm for erecting Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min. 124 Kg. iron work ) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire, D.P. Structure shall be erected in c.c. foundation complete |
| 59 | Supplying and erecting G.I. stay set for poles, including loop insulators at inaccessible height with anchor plate 300x300x6 mm., straining screws, G.l. stay wire 7/8 SWG, G.l. stay rod 20mmx1.8m length and pole clamps duly erected in provided cement concrete foundation complete. |
| 60 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP. Please Enable Macros to View BoQ information |