| 1 | Dismantling U/S any size of cross arms and anti climbing devices from pole /structures. complete all as specified and directed. |
| 2 | M&L for work confirming to Fe-410-O or Fe-310-O as in cross arms, support, bracings, stiffeners, clamps channels fabricated from structural steel including nuts, bolts and washers welding, bending cold or hot drilling holes for bolts in any shape or size all as directed including two coats of aluminium paint over a coating of red oxide primer all as directed by Engr-In-Charge. |
| 3 | Dismantling / taking down old unserviceable pin/loop/shackle type insulator any type / size. |
| 4 | Supply & fixing pin type porcelain vitreous insulator 100 mm height and 65 mm dia for 1100 Volts grade including galvanised mild steel spindle, one nut and two washers complete all as specified. |
| 5 | Supply and fixing shackle type insulator porcelain vitreous white,brown and green of size 75 mm heaight and 90 mm dia incl galvanised MS straps 31x3 mm size ,washers,insulator bolt 12 mm dia and nut for working pressure 1100 Volts grade complete all as specified. |
| 6 | M&L for loop insulator, vitreous, porcelain, white, brown or green, large size with overall dimensions 50x140mm clearance of hole 25.5 mm complete. |
| 7 | Dismantling of old unserviceble GI wire/stay wire. |
| 8 | M&L for GI wire 4mm dia as continuous earth wire, guarding and craddles to OH line including binding wire complete all as specified and as directed by Engr-in-Charge. |
| 9 | Dismantling of stay assembly complete from site complete all as specified and directed by Engineer-in-charge. |
| 10 | M&L for stay assembly complete with MS stay plate 300x300x6mm thick galvanized stay rod not less than 20mm dia, 2.15 M long galvanized stay bow, galvanized thimble,stay clamp etc. all as shown in electrical plate No1of SSR part-I (Note:- Excavation,earthwork,cement concrete loop type insulators and stay wire shall be included in the item rates. |
| 11 | Dismantling of old unserviceble Aluminium conductor off sizes from existing over head lines complete all as specified and directed by Engr-in-Charge. |
| 12 | M&L for ACSR conductor any sizes drawn over for over head lines fixed to insulators with binding wire after allowing specified sag complete all as specified and as directed by Engr-in-Charge. |
| 13 | Excavation in soft / loose soil in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out complete. |
| 14 | Returning filling with earth obtained from excavation including spreading watering and consolidation in layers not exceeding 25 cms thick complete. |
| 15 | Removing surplus soil to a distance not exceeding 50 m and depositing at a level not exceeding 1.5 m above the starting point complete. |
| 16 | Sand filling in trenches with clean dry fine sand unwashed including gently punning around cables complete. |
| 17 | Supply and Laying Unreinforced precast concrete cable cover class LV type 1, size 250mmx150mmx40mm complete as directed. |
| 18 | Supplying, laying or fixing or passing through pipe, testing and commissioning XLPE insulated, steel tape / wire armoured heavy duty electric underground cable, 1100 volts grade with stranded aluminium conductor of following nominal cross sectional area including taking down old unserviceable cable of following item no 19 to 29:-Note:- Excavation, returning and removal shall be paid and measured seperately under respective item of BOQ :- |
| 19 | 16 Sqmm, 4 core. |
| 20 | 25 Sqmm, 3.5 core. |
| 21 | 35 Sqmm 3.5 core. |
| 22 | 50 Sqmm 3.5 core. |
| 23 | 70 Sqmm 3.5 core. |
| 24 | 95 Sqmm 3.5 core. |
| 25 | 120 Sqmm 3.5 core. |
| 26 | 150 Sqmm 3.5 core. |
| 27 | 185 Sqmm 3.5 core. |
| 28 | 240 Sqmm 3.5 core. |
| 29 | 300 Sqmm 3.5 core. |
| 30 | Steel tubes light grade galvanised with all fittings fixed to walls/ floors/ poles/ road crossing etc of following sizes (Item no 31 to 33) complete:- |
| 31 | 50 mm bore |
| 32 | 80 mm bore |
| 33 | 100 mm bore |
| 34 | M&L for Cable route indicator showing \\"MES LT UG Cable\\" and route of cable with arrow made of CI in suitable eliptical / round shape and fixed on angle iron 40 x 40 x 6mm, 800mm long painted in Blue Colour with two coats of synthetic enamel paint over a coat of red oxide primer duly embaded in and including PCC 1:4:8 type D-2 (using 20mm graded stone aggregate) block (0.40 x 0.40 x 0.40) mtr in ground and 0.15mtr above ground level complete all as directed and specified. |
| 35 | Supply,installing,commissioning and testing of LT panel board outdoor type,cubical type made out CRCA sheet 3.15 mm thick,inner sheet 2.0 mm thick, dust and vermin proof and angle iron of suitable size, pedestal flame grouted in PCC (1:2:4) type B-1 20 mm graded stone aggregated thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with aluminum bus bar 400 Amp-03 nos for phase & 01 No for neutral ,(in separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following:- (a) MCCB 200 Amp,4P, 25KA,Ics=100%Icu, adjustable thermal based released (I/C)- 01 No (b) MCCB 63A, 16 KA, 3 Pole,Ics=100%Icu,fixed thermal and fixed magnetic (O/G)- 06 Nos(c) Digital meter with Voltmeter (0-500V) - 01 No(d) Rating of CT & Ammeter as per Bus bar capacity as mentioned in BOQ(e) Selector Switch for Ammeter (R,Y & B) - 01 Set(f) Selector Switch for Voltmeter (RY,YB & BR) - 01 Set(g) Indicationg Lamps (R,Y,B) - 01 SetNote : Drawing of LT panel shall be got approved from GE before placing order for procurement. |
| 36 | Supply, installing, testing and commission outdoor double door LT feeder pillar box, cubical type suitable for 3 phase 4 wirem, 50Hz and CPRI approved factory fabricated, powder coated (thickness not less than 100 micron) outer shall be made out of 3.15 mm thick CRCA sheet and MS angle section 50x50x6mm and inner sheet shall be made out of 2.00mm thick CRCA sheet duly compartmentalized having thimble and cable entry boxes with suitable size of aluminium bus bar 04 Nos (three phase and one neutral) mounted/fixed on suitable size angle iron frame/stand embedded in cement concrete type B-1 1:2:4 (using 20mm graded stone aggrigates) including painting steel surface with two coats of synthetic enameled paint over a coat of red oxide primer and general construction confirming to IS/IEC-61439-1:2011, 61439-2:2011 consisting of the following :-(a) MCCB 100 AMPs, 4 pole, 16 KA-01 Nos( Incomming)(b) MCCB 63Amp, 16 KA, 3 pole-02 Nos (outgoing)(c) Bare MCCB space -02 Nos (d) Aluminium Bus bar (RYB & N) with 4 Nos outgoing arrangement-01 Set(e) Three Phase LED indicator switch RY&BNotee : Drawing of LT panel shall be got approved from GE before placing order for proccurement. |
| 37 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint heat shrinkable type complete with Jointing material and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 10 to 16 Sq mm complete all as specified and as directed.Make : Denson/M-seal |
| 38 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material (Epoxy Based) and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 25 to 50 sq mm complete all as specified and as directed.Make : Denson/M-seal |
| 39 | Supply and fix cable jointing kit for 1100 KV grade cable for straight through joint heat shrinkable type complete with Jointing material and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 70 to 150 sq mm complete all as specified and as directed.Make : Denson/M-seal |
| 40 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint heat shrinkable type complete with Jointing material and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 185 to 400 sq mm complete all as specified and as directed.Make : Denson/M-seal |
| 41 | Dismantling of PCC pole/cracked pole from site complete all as specified and directed. |
| 42 | Supply and erecting steel tubular swaged pole with cast iron base plate, finial taper plug, bolts, nuts & washers as per IS 2713 (Part-II) 1980 made out of mild steel tubing, type 410 SP-55 (11 metre long) including painting of poles with one coat of red oxide primer and two coat of aluminum paint (one coat before fixing and one coat of aluminum paint after fixing) over exposed surface and two coats of bituminous paint over embedded portion & the portion above coping shall be painted in alternative bands of black and yellow colour starting with white colour (each band of 30cm wide) by two coats of super enameled paint upto 1.5m height complete all as specified and directed. Note : Earth work and PCC shall be measured separately. |
| 43 | Supply and erecting in true vertical position steel tubular swaged pole 9mtr long type 410 SP-31) complete with base plate and closed at top , painted externally up to the embeeded depth with two coats of black bitumnous paint and remaining external portion with two coats of aluminium paint over a coat of red oxide primer complete. |
| 44 | Excavating in trenches, n exc 1.5 m wide and more than 1.5 m n exc 3.0 m in depth; for foundation, etc. Or for shafts, wells, cesspits, manholes, pier holes, etc. N exc 10 sq m on plan and n exc 3.0 m in depth and getting out complete all as specified and directed |
| 45 | M&L for PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed by Engr in Charge. |
| 46 | M&L for PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed by Engr in Charge. |
| 47 | M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping complete all as specified and directed by Engr in Charge. |
| 48 | Earthing complete with galvanised steel earth plate electrode 60cmX60cmX6.0mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not than 1.5mtr below normal ground level connected to GI earth strip of size 32x6mm dia by means of bolts, nuts, check nuts and washers of galvanised iron complete earth pit of PCC M-10(Nominal mix) using 20mm graded stone aggregate, 50mm thick earth pit cover of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape, PGI funnel, wire mesh and 20mm bore GI water pipe medium grade and 40mm bore medium grade GI pipe for protection of earth strip from plate to main switch panel, eqpmt, bus bar etc, common salt, charcoal dust including testing on completion complete all as specified and as directed all as shown in electrical plate No. 3 including testing on completion and making good the disturbed surfaces of wall floors etc without claiming extra cost complete. Note: GI strip beyond 5.0Mtr length from earth electrode shall be measured and paid separately). |
| 49 | All as per item Srl No.42 here in before but by using GI wire 4mm dia as earth lead & 15mm bore medium grade GI pipe for protection of earth wire from plate to main switch board |
| 50 | M&L for GI strip of size 32x6mm as earth continuity conductor burried in ground or drawn in pipe or fixed to wall on saddle. |
| 51 | M&L for Copper strip 20x3mm as earth continuity conductor burried in ground or drawn in pipe or fixed to wall on saddle. |
| 52 | M&L for earth continuity conductor galvanised iron wire 4 mm dia . |
| 53 | Supply and fixing GI funnel complete with wire mesh for earthing water pipe. |
| 54 | M&L for earth pit cover of size 450x450x50mm thick of with 1:4:8 type D-2 using 20mm graded stone aggregate with top obenable with GI sheet size 150X150X3 mm alongwith handle to pull up complete all as specified and as directed. |
| 55 | Stringing of existing overhead LT line ACSR conductor of any size opening /dismentling of jumpers and ACSR conductors from insulators and connecting after stringing inclusing required ACSR conductor/connectors of following span of conductors (Item no 56-57) :- |
| 56 | Span of two/three ACSR conductors of any size |
| 57 | Span of four /five ACSR consutors of any size |
| 58 | Cutting wild grass, bushes, creaper, unwanted vegetation from inside / surrounding of E/M installations, near transformers, pole structures etc including cutting creapers from barbed / cattle fencing of the installations as when directed and removing of unwanted material from installation compound and depositing where directed. (Note : (a) The item shall be operated maximum three times in entire period of contract in the same installations. (Area measured separately each time). |
| 59 | Labour & tools for trimming tree branches upto 100 mm girth of any location around existing HT/LT OH lines giving clearance of 1.5 m on all sides complete. (Note:- Trimming of tree branches irrespective in numbers in each tree shall be measured as one unit). |
| 60 | M&L for painting and minor repair to LT panels including welding work/repair to door/ hinge etc as required at site complete all as specified and as directed |
| 61 | Supply and fixing in replacement of MCCB 630Amp rating,4-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 36 KA. |
| 62 | Supply and fixing in replacement of MCCB 400Amp rating,4-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 36 KA. |
| 63 | Supply and fixing in replacement of MCCB 250Amp rating,4-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 36KA. |
| 64 | Supply and fixing in replacement of MCCB 100Amp rating,4-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 16KA. |
| 65 | Supply and fixing in replacement of MCCB 63Amp rating,4-pole 415V, fixed thermal fixed megnetic type breaking capacity 16KA. |
| 66 | Supply and fixing in replacement of MCCB 250Amp rating,3-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 35KA. |
| 67 | Supply and fixing in replacement of MCCB 200Amp rating,3-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 35KA. |
| 68 | Supply and fixing in replacement of MCCB 160Amp rating,3-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 16KA. |
| 69 | Supply and fixing in replacement of MCCB 125Amp rating,3-pole 415V, adjustable thermal adjustable megnetic type breaking capacity 16KA. |
| 70 | Supply and fixing in replacement of MCCB 100Amp rating,3-pole 415V, fixed thermal fixed megnetic type breaking capacity 16KA. |
| 71 | Supply and fixing in replacement of MCCB 63Amp rating,3-pole 415V, fixed thermal fixed megnetic type breaking capacity 16KA. Please Enable Macros to View BoQ information |