| 1 | Taking down carefully copper /aluminium point wiring (Light, fan, socket, or power) complete including fittings and fixture such as switches, ceiling roses pendents, regulators sockets / DBs / main switches include boards etc removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately), removing material, from site and making good the disturbed surfaces of walls/floor complete all as specified and directed. |
| 2 | Material and labour for point wiring for one light point/fan/bell point controlled by one switch complete with PVC insulated unsheathed, 1100 volts grade cable 1.5 Sqmm (nominal area) FRLS type multi stranded copper conductor, single core using approved colour code as per IS code drawn in and including not less than 20 mm dia rigid PVC conduit 'medium grade' ISI marked but shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I including all conduit accessories for concealed wiring including concealed GI flush mounting junction box of required size factory made , with modular base and cover plate of required colour for mounting modular switch, sockets, fan regulator etc including 1.5 Sqmm FRLS type PVC insulated unsheathed cable multi-stranded copper conductor as continuous earth wire and connected to earth dolly as required at site & including chases cutting & making good disturbed surface complete all as specified and directed. Note: The rate of cutting chases required for concealing the PVC conduits alongwith the fittings / fixtures like elbow, bends , conduit, junction box, modular frame, modular plate etc and making good the disturbed surface shall be deemed to be included in unit rate quoted and nothing extra shall be paid for this. |
| 3 | All as per Ser item No 02 here-in-before but one light point controlled by two 2-way switch with the cable 1.50 sqmm size complete all as specified and directed. |
| 4 | All as per Ser item No 02 here-in-before but for 05/06 Amp socket outlets point controlled by one switch on same board with the cable 1.50 sqmm size complete all as specified and directed. |
| 5 | All as per Ser item No 02 here-in-before but for 05/06 Amp 3 pin socket outlets point controlled by one switch on Independent board with the cable 1.50 sqmm size complete all as specified and directed. |
| 6 | All as per Ser item No 02 here-in-before but for 15/16 Amp 3 pin socket outlets point controlled by one switch on Independent socket outlet using 2.5 sqmm PVC insulated and unsheathed FRLS copper conductor single core multi stranded flexible copper cable 1100 V of approved colour code as per IS code for phase and neutral along with PVC insulated and unsheathed FRLS 2.5 sqmm multi stranded copper unsheathed cable 1100V (green color) as continuous earth lead wire connected to common earth and earth dolly complete all as specified and directed. |
| 7 | Material and labour for point wiring for one light point/fan/bell point controlled by one switch complete with PVC insulated unsheathed, 1100 volts grade cable 1.5 Sqmm (nominal area) FRLS type multi stranded copper conductor, single core using approved colour code as per IS code drawn in existing conduit incl GI flush mounting junction box of required size factory made , with modular base and cover plate of required colour for mounting modular switch, sockets, fan regulator etc including 1.5 Sqmm FRLS type PVC insulated unsheathed cable multi-stranded copper conductor as continuous earth wire and connected to earth dolly as required at site & including chases cutting for fixing of junction box concealed in wall & making good disturbed surface complete all as specified and directed. Note: The rate of cutting chases required for concealing the Junction box incl junction box, modular frame, modular plate etc and making good the disturbed surface shall be deemed to be included in unit rate quoted and nothing extra shall be paid for this. |
| 8 | All as per Ser item No 07 here-in-before but one light point controlled by two 2-way switch with the cable 1.50 sqmm size complete all as specified and directed. |
| 9 | All as per Ser item No 07 here-in-before but for 05/06 Amp 3 pin socket outlets point controlled by one switch on same board with the cable 1.50 sqmm size complete all as specified and directed. |
| 10 | All as per Ser item No 07 here-in-before but for 05/06 Amp 3 pin socket outlets point controlled by one switch on Independent board with the cable 1.50 sqmm size complete all as specified and directed. |
| 11 | All as per Ser item No 07 here-in-before but for 15/16 Amp 3 pin socket outlets point controlled by one switch on Independent socket outlet using 2.5 sqmm PVC insulated and unsheathed FRLS copper conductor single core multi stranded flexible copper cable 1100V of approved colour code as per IS code for phase and neutral along with PVC insulated and unsheathed FRLS 2.5 sqmm multi stranded copper unsheathed cable 1100V (green color) as continuous earth lead wire connected to common earth and earth dolly complete all as specified and directed. |
| 12 | Supply and fixing for modular switch one way 5/6 Amp, 1 module complete all as specified and directed. |
| 13 | Supply and fixing for modular socket, 5/6 amps 3 pin, 2 module complete all as specified and directed. |
| 14 | Supply and fixing for modular switch , one way, 15/16 amps, one Module complete all as specified and as directed. |
| 15 | Supply and fixing for modular socket 5/6 & 15/16 amps 3 pin multipin, 2 module complete all as specified and directed. |
| 16 | Supply and fixing for modular switch 2 way 6 Amp,1 module complete all as specified and directed. |
| 17 | Supply and fixing for modular bell push 5 Amp,1 module complete all as specified and directed. |
| 18 | Supply and fixing for modular fan regulator electronic step type 230 V 2 Module complete all as specified and directed. |
| 19 | Supply and fixing for in repairs ceiling rose surface type, PVC/polycarbonate three terminals complete all as specified and directed. |
| 20 | Supply and fixing for door bell, ding dong, AC, 240 Volts, SP complete all as specified and directed. |
| 21 | Supply only PVC casing caping of size 25 mm including of all tee, bend, elbow etc with fixing accessories complete all as specified and directed. Note: Casing Caping shall be taken in charge by MES through RV. |
| 22 | Dismantling and taking down carefully by sub main wiring/service connection of any type complete all as specified and directed. |
| 23 | Material and labour for sub main wiring using PVC insulated and unsheathed fire retardant low smoke (FRLS) copper conductor single core multi stranded unsheathed copper cable 2x4.00 sqmm (for Phase and neutral) and earth continuity conductor of size 1x4.00 sqmm multistranded copper conductor FRLS 1100V using approved colour code for phase,neutral & earth as per IS code drawn through existing conduit complete all as specified and directed.Note : (i) 3 runs of 4.00 sqmm copper cable shall be measured as one unit. |
| 24 | Material and labour for sub main wiring using PVC insulated and unsheathed fire retardant low smoke (FRLS) copper conductor single core multi stranded unsheathed copper cable 2x10.00 sqmm (for Phase and neutral) and earth continuity conductor of size 1x10.00 sqmm multistranded copper conductor FRLS 1100V using approved colour code for phase,neutral & earth as per IS code drawn through existing conduit complete all as specified and directed. Note : (i) 3 runs of 10.00 sqmm copper cable shall be measured as one unit. |
| 25 | Material and labour for sub main wiring using PVC insulated and unsheathed fire retardant low smoke (FRLS) copper conductor single core multi stranded unsheathed copper cable 2x4.00 sqmm (for Phase and neutral) and earth continuity conductor of size 1x4.00 sqmm multistranded copper conductor FRLS 1100V using approved colour code for phase,neutral & earth as per IS code drawn through non-metallic PVC rigid concealed conduit, 20 mm outer dia (Minimum dia). The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including chases cutting & making good disturbed surface complete all as specified and directed. Note : (i) 3 runs of 4.00 sqmm copper cable & 1 run of 20 mm (Minimum dia) PVC conduit shall be measured as one unit. (ii) The rate of cutting chases required for concealing the PVC conduits alongwith the fittings / fixtures like elbow, bends , conduit/flush boxes etc. and making good the disturbed surface is deemed to be included in overall rate quoted and nothing extra shall be paid for this. |
| 26 | Material and labour for sub main wiring using PVC insulated and unsheathed fire retardant low smoke (FRLS) copper conductor single core multi stranded unsheathed copper cable 2x10.00 sqmm (for Phase and neutral) and earth continuity conductor of size 1x10.00 sqmm multistranded copper conductor FRLS 1100V using approved colour code for phase,neutral & earth as per IS code drawn through non-metallic PVC rigid concealed conduit, 25 mm outer dia (Minimum dia). The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including chases cutting & making good disturbed surface complete all as specified and directed. Note : (i) 3 runs of 10.00 sqmm copper cable & 1 run of 25 mm (Minimum dia) PVC conduit shall be measured as one unit. (ii) The rate of cutting chases required for concealing the PVC conduits alongwith the fittings / fixtures like elbow, bends , conduit/flush boxes etc. and making good the disturbed surfaceshall be deemed to be included in unit rate quoted and nothing extra shall be paid for this. |
| 27 | Supply and fixing for LED batten (4 feet) surface / wall mounted with specially designed powder coated aluminium housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired up to terminal block, power consumption 22 Watt, driver efficiency>85%, power factor > 0.9 incl dismantling and taking down old unser lights (any type) complete all as specified and directed. |
| 28 | Supply and fixing for surface and wall mounted LED Batten 10W (2 Feet) light fitting complete with tube, & duly pre-wired from fitting to ceiling rose incl dismantling and taking down old unser lights (any type)complete all as specified and directed. |
| 29 | Supply and fixing for LED Bulk Head 10W bulk head edge LED lighting fixture , energy efficent surface mounted ready to use pack 10W LED, complete with connecting accesseries & Driver duly pre-wired and connecting up with suitable size flexible wire complete all as specified and directed. |
| 30 | Supply and fixing for LED decorative wall light with B22 base including LED bulb of 9 watt having base B22 complete with connecting accesseries & Driver duly pre-wired and connecting up with suitable size flexible wire incl dismantling and taking down old unser lamp holder/light (any type) complete all as specified and directed. |
| 31 | Supply and fixing for recessed mounted 2'x2' 36W LED ceiling light suitable for armstrong/grid/POP ceiling, delivers high brightness & excellent illumination complete with connecting accesseries & driver duly pre-wired complete all as specified and directed. |
| 32 | Supply and fixing for recessed mounted 1'x1' 20W LED ceiling light suitable for armstrong/grid/POP ceiling, delivers high brightness & excillent illumination complete with connecting accesseries & driver duly pre-wired complete all as specified and directed. |
| 33 | Supply only LED bulb 9 watt with B22 base complete all as specified and directed. Note: bulb shall be taken in charge by MES through RV. |
| 34 | Supply and fixing for LED landscape bollard light 10 watt, 230 volt, inverted pyramid tripod type with soft 360 degree distribution, IP-65 protection, incl necessary civil work for grouting & foundation work of suitable size with PCC work complete all as specified and directed . |
| 35 | Supply and fixing for in repair LED post top lantern luminaire with die cast aluminium spigot, lid cover and clear acrylic cover 40 watt, 5700 K with IP-65 protection including connection complete all as specified and directed. |
| 36 | Supply and fixing for bed side LED lamp 5 Watt with flexible gooseneck, bedside fixture with push button switch including connection complete all as specified and directed. |
| 37 | Supply and fixing for sheet metal enclosure MCB distribution board single pole & neutral 240 volts 12 way with IP-43 double door complete with 200 Amps rated bus bar, earth link and neutral link with provision for fixing incomer and outgoing MCBs as outgoing switchgears, fixed flush in wall including chases cutting in wall for fixing DB and making good distributed wall surfaces complete all as specified and directed. Note - MCBs shall be measured separately. |
| 38 | Supply and fixing for in repairs sheet metal enclosure distribution board 415volt, vertical TPN 8 Way (load line DB) with provision for suitable MCCB FP up to 160 A as incomer & MCBs as out going as per IS including compact insulated bus bar and rounded neutral bar, door earthing complete double door surface/reccess mounting IP-43 protection, including connection with the existing sub circutis, electric meter etc with proper size new copper cable, lugs,connectors etc complete all as specified and directed. Note - MCCB & MCBs shall be measured separately. |
| 39 | Supply and fixing for in repairs sheet metal enclosure distribution board 415volt, Vertical TPN 4 Way (load line DB) with provision for suitable MCCB FP up to 125 A as incomer & MCBs as out going as per IS including compact insulated bus bar and rounded neutral bar, door earthing complete double door surface/reccess mounting IP-43 protection, , including connection with the existing sub circuits, electric meter etc with proper size new copper cable, lugs,connectors etc complete all as specified and directed. Note - MCCB & MCBs shall be measured separately. |
| 40 | Supply and fixing for sheet metal enclosure MCB distribution board TPN 415 volts 04 way with IP-43 double door complete with 200 Amps rated bus bar and neutral link with provision for MCB as incomer and MCBs as outgoing switchgears, fixed flush in wall including chases cutting in wall for fixing DB and making good distributed wall surfaces complete all as specified and directed. Note - MCBs shall be measured separately. |
| 41 | Supply and fixing for in repairs MCCB, 4-pole, adjustable breaking capacity 16 KA, 415 volts, 125 Amps including taking down unservicable one complete all as specified and as directed. |
| 42 | Supply and fixing in repairs MCB SP 6 to 32 Amps 240 volts 10 KA ''C''Series complete all as specified and directed. |
| 43 | Supply and fixing in repairs MCB SPN 40 to 63 Amps 240 volts 10 KA ''C''Series complete all as specified and directed. |
| 44 | Supply and fixing in repairs MCB TPN 40 to 100 Amps 415 volts Breaking capacity 10KA C Series complete all as specified and directed. |
| 45 | Supply and laying for PVC insulated flexible unarmoured cable three core copper conductor 1.5 sqmm size 1100 volt grade complete all as specified and directed. |
| 46 | Supply and fixing for portable residual current device (PRCD) 30 mA , 16 Amps plug/Socket top for geyser and other electric devices suitable for fitting in existing power sockets incl dismanting and taking down old u/s normal plug top at any type complete all as specified and directed. |
| 47 | Supply and fixing for DBOX MCB protected socket , single phase, with MCB 20 Amps 'C' curve with plastic enclosure 4 module suitable for AC and other electrical connection incl dismantling and taking down old unser switch sockets box or AC socket box or MCB enclosure 2 module (PVC/Metal) as per actual complete all as specified and directed. |
| 48 | Supply only capacitor of 2.5 mfd , 240 V, complete all as specified and directed. Note: capacitor shall be taken in charge by MES through RV. |
| 49 | Supply only down rod for ceiling fan of 19/20 mm dia of mild steel pipe of 75/90 cm long complete all as specified and directed. Note: Rod shall be taken in charge by MES through RV. |
| 50 | Supply only PVC connections 15 mm size with PTMT nuts of length 450 mm suitable for Water coolers/Geysers complete all as specified and directed. Note: PVC connections shall be taken in charge by MES through RV. |
| 51 | Supply only PVC connections 15 mm size with PTMT nuts of length 600 mm suitable for Water coolers/Geysers complete all as specified and directed. Note: PVC connections shall be taken in charge by MES through RV. |
| 52 | Supply only of apparatus plate (Geyser Assembling Unit) with rubber gasket including nuts, bolts and washers consisting of 6/9 Nos of holes suitable for existing geysers complete all as specified and directed. Note: Appratus shall be taken in charge by MES through RV. |
| 53 | Supply only heating element of geyser 2.0/1.5 KW as existing pattern complete all as specified and directed. Note: Heating elements shall be taken in charge by MES through RV. |
| 54 | Supply only Inner tank of geyser of capaciy 25 Ltr as existing pattern incl taking down and refixing complete all as specified and directed. Note: Inner Tanks shall be taken in charge by MES through RV. |
| 55 | Supply only outer body cover of geyser of capaciy 25 Ltr as existing pattern including taking down and refixing complete all as specified and directed. Note: Outer body cover shall be taken in charge by MES through RV. |
| 56 | Supply only LED indicator (Red & Green) with wire for connection for geyser complete all as specified and directed. Note: LED indicator shall be taken in charge by MES through RV. |
| 57 | Supply only electric geyser safety valve as per existing complete all as specified and directed. Note: Electric geyser safety valve shall be taken in charge by MES through RV. |
| 58 | Supply only thermostat 7'/11' for geyser with adjustable temperature setting range complete all as specified and directed. Note: Thermostat shall be taken in charge by MES through RV. |
| 59 | Supply only PVC plug top 3 pin 16 amps suitable for 230 volts AC supply complete all as specified and directed. Note: plug top shall be taken in charge by MES through RV. |
| 60 | Material and labour for cutting brick wall, making a hole suitable for fixing exhaust fan of sweep upto 600 mm and making good distyrbed surface complete all as specified and directed. |
| 61 | Supply and fixing for wall mounted fan 400 mm sweep,1400 RPM, heavy duty motor with double ball bearing, aerodynamicaly design blades with provision of flexible cord 3 core stranded copper conductor of size 0.50 sqmm from connector block to fan complete incl taking down old u/s complete all as specified and directed. Note- old u/s material shall be property of MES. |
| 62 | Supply and fixing for exhaust fan metalic body size 300 mm sweep with louvers, operated on 230/240V AC Single phase electric supply 900 RPM complete including connecting with 3 core stranded copper conductor cable cord of size 0.5 sqmm from ceiling rose to fan connector incl taking down old u/s exhaust fan complete all as specified and directed. Note- old u/s material shall be property of MES. |
| 63 | Supply and fixing for exhaust fan made of sturdy Engineering plastic size 250 mm sweep with louvers and shutter, voltage 230/240V, 50Hz, AC single phase electric supply 1200 RPM complete including connecting with 3 core stranded copper conductor cable cord of size 0.5 sqmm from ceiling rose to fan connector incl taking down old u/s exhaust fan complete all as specified and directed.Note- old u/s material shall be property of MES. |
| 64 | Supply and fixing for of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, minimum air delivery 210 CM/Min (Minimum), class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, with remote for on/off and speed control and all remaining accessories including safety pin, nut bolts, washers,suitable for 230/240V, 50 Hz, single phase AC Supply, earthing etc including taking down old u/s complete all as specified and directed.Note- old u/s material wil be property of MES. |
| 65 | Supply only pvc electrical insulation tape size 6 meter with fire retardant and water proof complete all as specified and directed.Note:- tape shall be taken in charge by MES through RV. |
| 66 | Material and labour in replacement printed circuit board (PCB) after dismantling, taking down and refixing after repairing of BLDC fan any type any size incl dismantling and taking down and refixing the same after repairing complete all as specified and directed. |
| 67 | Supply only remote for BLDC ceiling fan (25-38 W) for 1200 mm sweep suitable for Bajaj/Orient/Crompton/Havells fan as per sample without batteries complete all as specified and directed. Note: Remote shall be taken in charge by MES through RV. |
| 68 | Supply only PVC gang box suitable for one switch & socket 6/16 Amps complete with screw and necessary arrangement complete all as specified and directed.Note:- gang box shall be taken in charge by MES through RV. |
| 69 | Material and labour for earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth electrode connected connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 incl PCC earth pit with CI frame and RCC cover including testing and dismantling ,taking down old unser earthing complete all as specified and directed Note: (i) Rate of Earth work, Earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead upto 7.5 mtr, char coal dust, common salt, watering pipe, earth lead protection pipe, porcelain insulator,PCC earth Pit, RCC cover, funnel with wire mesh shall be deemed to be included in the unit rate quoted. |
| 70 | Material and labour for wet servicing of split AC by highly skilled technician incl both Indoor and outdoor units using water and specialized cleaning agents to throughly clean the cooling coils, condenser coils, outside panels, drain and fillet pipes by using pressure jet ,jet pump, jackets cover to prevent spills, cleaning foam, blowers, brush,cleaning cloths etc complete servicing with additional checks as: (i) Check for Gas Pressure (ii) Check for Power Consumption (iii) Check for level of indoor unit for proper water flow (iv) Check Thermostat (v) Check all electrical connections and tighten them. |
| 71 | Material and labour for wet servicing of window AC by highly skilled technician using water and specialized cleaning agents to throughly clean the cooling coils, condenser coils, outside panels, drain and fillet pipes by using pressure jet ,jet pump, jackets cover to prevent spills, cleaning foam, blowers, brush,cleaning cloths etc complete servicing with additional checks as:(i) Check for Gas Pressure (ii) Check for Power Consumption (iii) Check for level of indoor unit for proper water flow (iv) Check Thermostat (v) Check all electrical connections and tighten them. Please Enable Macros to View BoQ information |
| 72 | Material and labour for wet servicing of window AC by highly skilled technician using water and specialized cleaning agents to throughly clean the cooling coils, condenser coils, outside panels, drain and fillet pipes by using pressure jet ,jet pump, jackets cover to prevent spills, cleaning foam, blowers, brush,cleaning cloths etc complete servicing with additional checks as:(i) Check for Gas Pressure (ii) Check for Power Consumption (iii) Check for level of indoor unit for proper water flow (iv) Check Thermostat (v) Check all electrical connections and tighten them. Please Enable Macros to View BoQ information |