| 1 | Supply and laying XLPE insulated armoured cable (heavy duty) electric cable with aluminium stranded conductor 1100 volts grade of following size after taking down complete all as specified and directed by Engr-in-charge :- |
| 2 | 10 Sqmm x 2 Core |
| 3 | 16 Sqmm x 4 Core |
| 4 | 50 sqmm x 3.5 core |
| 5 | 70 Sqmm x 3.5 Core |
| 6 | 95 Sqmm x 3.5 Core |
| 7 | 120 Sqmm x 3.5 Core |
| 8 | 185 Sqmm x 3.5 Core |
| 9 | 240 Sqmm x 3.5 Core |
| 10 | 400 Sqmm x 3.5 Core |
| 11 | Supply, installing, testing and commissioning factory made LT panel ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved manufacturer, factory assembled Outdoor Feeder Pillar type, weather proof, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 100 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-65 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40 X 40 X 6 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including masonry of blocks of PCC 1:2:4 type B1 of block size 30x30x30 cm and rendering in CM 1:4 with comprising of the following:- |
| 12 | BUS BAR CHAMBER :- (a) 100 Amps 3 Strips & Neutral Strip 50 Amps, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :- (i) MCCB 63 Amps 16 KA 3 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., Make of MCCB:-L&T/ Schneider / HPL/ Havells.INSTRUMENT FEEDER :- (a) Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-100 A, with Amp meter Selector switch- 01 Set. (c) C.T's 100/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. |
| 13 | OUTGOING SUPPLY :- (i) MCB SPN 32 Amps, 230 volts, 50Hz, rupturing capacity 10 KA C Curve = 3 Nos. Make of MCB:- L&T/ Schneider / HPL/ Havells.(ii) MCB TPN 32 Amps, 230 volts, 50Hz, rupturing capacity 10 KA C Curve = 3 Nos. Make of MCB:- L&T/ Schneider / HPL/ Havells.The panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011)2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011)3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V5. ISO 9001 CERTIFIEDContractor will get the copy of above certificates from manufacturer and submit to Engineer-in-charge/AGE(I) before erection of panel on ground. |
| 14 | Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge. |
| 15 | Supply, installing, testing and commissioning factory made LT ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved, factory assembled LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 300 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40 X 40 X 5 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. embedded in ground with and including masonry of blocks of PCC 1:2:4 type B1 of block size 30x30x30 cm and rendering in CM 1:4 comprising of the following:- (LOCATION :-DGRE RDC MANALI) |
| 16 | BUS BAR CHAMBER :- (a) 300 Amps 4 Strips Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INCOMING SUPPLY :- (i) MCCB 200 Amps 36 KA 4 Pole with Adjustable thermal & fixed magnetic release 415 volts , 50Hz,=01 No., Make of MCCB:- L&T/ Siemens / Legrand/ Havells/HPL.INSTRUMENT FEEDER :- (a) Multifunction meter Class, 1.0, three phase flush mounted of accuracy class-I for measurement of voltage , current, frequency etc. having programmable CT ratio- 01 Set. (b) C.T's 200/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(c) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).(d) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. |
| 17 | OUTGOING SUPPLY :- (i) MCCB 100 Amps 25 KA 3 Pole with Adjustable thermal & fixed magnetic release 415 volts , 50Hz,=04 Nos., Make of MCCB:- L&T/ Siemens / Legrand/ Havells/HPL. Make of Panel: Adlec/ Schneider / Universal Switch Gear Control/ Tricolite.The panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011)2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011)3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V5. ISO 9001 CERTIFIEDContractor will get the copy of above certificates from manufacturer and submit to Engineer-in-charge/AGE(I) before erection of panel on ground. |
| 18 | Note : Unit rate quoted by the contractor here-in-before also includes for installation of panel on suitable PCC foundation and PCC plat form incl necessary earth and PCC work all as per manufacturer instructions and as directed by the Engr-in-Charge. |
| 19 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required above 185 sqmm upto 400 sqmm complete all as specified and as directed by Engr-in-charge. |
| 20 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required above 95 sqmm upto 185 sqmm complete all as specified and as directed by Engr-in-charge. |
| 21 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required above 35 sqmm upto 95 sqmm complete all as specified and as directed by Engr-in-charge. |
| 22 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required upto 35 sqmm complete all as specified and as directed by Engr-in-charge. |
| 23 | M & L for Heat Shrinkable 1.1 KV XLPE Straight Joints of following size including taking down complete all as specified and directed by Engr-in-charge:- |
| 24 | 10 sqmm to 50 sqmm size |
| 25 | 70 sqmm to 95 sqmm size |
| 26 | 120 sqmm to 185 sqmm size |
| 27 | 240 sqmm to 400 sqmm size |
| 28 | Arranging fault locating machine to locate the fault in underground electric power cable of any length & any type of 11 KV/1.1 KV grade HT/ LT cables & pin point the fault, it also include testing of the cable after locating fault and cutting the cable at Fault to fix the joint including excavation and earth wotrk in any type of soil complete Note : Cable joint shall be measured and paid separately under respective of Sch 'A' (ii) If fault is not rectifed within 24 hours after receivng message, the contractor shall be charged penalty for Rs 500/- per Hours & the same has been deducted from his account during RAR. |
| 29 | Supply & fixing in repair of moulded case circuit breaker four pole 630 Amps 50 KA capacity 415V 50Hz with adjustable thermal and magnetic relay incl replacement of lugs & disconnecting and taking out the old unservicable MCCB from panel/DBs/ etc complete all as specified and directed by Engr-in-charge and directed. |
| 30 | All as per item No 10 above but 400 amps 4 pole 36 KA Capacity 415V 50 Hz. |
| 31 | All as per item No 10 above but 250 amps 4 pole 36 KA Capacity 415V 50 Hz. |
| 32 | All as per item No 10 above but 200 amps 4 pole 36 KA Capacity 415V 50 Hz. |
| 33 | All as per item No 10 above but 100 amps 3 pole 16 KA Capacity 415V 50 Hz. |
| 34 | All as per item No 10 above but 125 amps 3 pole 16 KA Capacity 415V 50 Hz. |
| 35 | All as per item No 10 above but 160 amps 3 pole 16 KA Capacity 415V 50 Hz. |
| 36 | S & F in repair of old unserviceabel digital voltmeter of range 0-500 volts suitable for LT Panel complete all as specified and directed by Engineer-In-Charge. |
| 37 | S & F in repair of old unserviceabel digital Ampere meter of range 0-630 Amps suitable forLT Panel complete all as specified and directed by Engineer-In-Charge. |
| 38 | S & F in repair of old unserviceable indication lamp( R,Y,B) for LT Panel complete all as specified and directed by Engineer-In-Charge. Please Enable Macros to View BoQ information |