| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil all as specified and as directed. |
| 2 | Returning filling in excavated soil upto a depth of 30 cm after riddling of excavated soil (in lieu of sand) for cushioning of cable and refilling of trenches with left over normal excavated soil including spreading, levelling, watering and well ramming in layers complete all as specified and directed |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and directed. |
| 4 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 flat, size 250 mm x 150mm x 40mm complete all as specified and as directed. |
| 5 | Supply and laying in trenches, LT underground cable of size 16 Sqmm 4 core XLPE insulated armoured and PVC sheathed 1100 Volts grade with aluminium conductor multistranded including cable connecting lugs, glands,jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall including taking down complete all as directed. |
| 6 | All as per item No 5 here-in-before but 25 Sqmm 3.5 core |
| 7 | All as per item No 5 here-in-before but 35 Sqmm 3.5 core |
| 8 | All as per item No 5 here-in-before but 50 Sqmm 3.5 core |
| 9 | All as per item No 5 here-in-before but 70 Sqmm 3.5 core |
| 10 | All as per item No 5 here-in-before but 95 Sqmm 3.5 core |
| 11 | All as per item No 5 here-in-before but 120 Sqmm 3.5 core |
| 12 | All as per item No 5 here-in-before but 240 Sqmm 3.5 core |
| 13 | All as per item No 5 here-in-before but 300 Sqmm 3.5 core.Note for Sl No 5 to 13: Necessary excavation and connected items shall be measured and paid separately under respective items of this schedule. |
| 14 | M&L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine including GI pipe of 50/80/100mm dia suitable for 0.4mpa working pressure complete all as specified and directed |
| 15 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc.for protection of UG cable complete all as specified and directed |
| 16 | Supply and laying GI tubing light grade 80mm dia in trenches/fixing on pole /wall/crossing in drain etc.for protection of UG cable complete all as specified and directed |
| 17 | Supply and fix danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT, 20x15cm size including taking down old unserviceable one complete all as specified and directed |
| 18 | Supply and fix in repair 40 to 100 Amp rating, 415V, 10KA 'C' curve miniature circuit breaker (MCB) of four pole in the MCB DB complete with connection testing and commissioning complete all as specified and directed. |
| 19 | Supply and fix in repair 32 Amps rating, 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of Single Pole and Neutral, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed. |
| 20 | Supply and fix in repair 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed. |
| 21 | Supply and fix cable route indicator made out of 3 mm thick MS sheet of size 30 cm x 20 cm duly painted with two coats black paint over a coat of red oxide primer and writing cable direction, capacity, size of cable with white paint, mounted on angle iron 50x50x3 mm, angle height 60 cm, (30cm below ground level) with PCC 30cmx30cmx30cm all as specified and as directed. |
| 22 | Supply, installation and commissioning in repair LT out door loop in loop out terminal box with sloping canopy of size 600x450x250mm made out of 3 mm thick CRCA sheet duly painted with two coats of synthetic enamel paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4:8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 63 Amps 4 pole, 415 Amps, 50 Hz of breaking capacity 16 KA as incomer including taking down old terminal boxes complete all as specified and directed. |
| 23 | Supply and fix in repair bus bar box of size 450x300x500mm fabricated by 3 mm thick MS sheet outdoor type, dust/vermin proof, mounted/fixed on angle Iron frame of MS equal angle size 40x40x6mm of height 0.90 mtr, erected in ground with PCC foundation 1:4:8 with 40mm stone aggregate and including aluminium bus bar flat of size 50x6 mm fixed as bus bar over the insulators, sleeved for three phase and neutral and spray painting the box with two coats of enamel paint over a coat of metal primer including necessary excavation, PCC for fixing the box complete all as specified and directed. |
| 24 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size including lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following: INCOMING:- MCCB 4 pole 160 Amps 35 kA - 01 Nos OUTGOING:- MCCB 4 pole 125 Amps 25 kA - 01 Nos MCCB 4 pole 100 Amps 25 kA - 01 Nos MCCB 4 pole 63 Amps 25 kA - 02 Nos MCB DP 32 Amps 10 kA - 01 Nos Multifunctional VAF meter, PF meter - 1 No RYB Neon indicating lamp -1 set for each outgoing and incoming MS work incl angle iron frame and PCC work Space for mounting of additional MCB In future. Internal wiring including copper lugs |
| 25 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators .The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following:-INCOMING:(a) 4 Pole ATS 250Amp, 50 Hz, 415 V with rupturing capacity 36 KA, Incomer -1 NoOUTGOING(b) 4 Pole MCCB 200Amp 25 KA - 01 Nos (c) 4 Pole MCCB 100 Amp 16 KA -01 Nos (d) 3 Pole MCCB 40 Amps 16KA-02 Nos (b) Digital Volt meter (0-500 V)-01 No(c) Digital Ammeter-01 No(d) CT's 250/5- set of 3 No(e) LED type Indication lamps (RYB)-one set |
| 26 | Supply, install, testing and commissioning of LT Panel board CPRI approved outdoor type, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars duly insulated by insulation of RYB colour 300 Amps rating mounted on porcelain insulators. The panels shall be factory made, double door, made out of 3.15 mm thick MS sheet totally enclosed dust, vermin and rust proof front operated, front and rear opening with locking arrangement fixed with MS angle iron frame of size 50X50X5 mm duly embedded in PCC platform and duly powder coated with 7 tank process with colour as directed including internal wiring with multistranded copper conductor cable of suitable size including lugs and cable gland to incoming and outgoing cable all as directed at site and comprising of the following: -INCOMING:(a) 4 Pole ACB 630 Amps 50 Hz, 415 V with rupturing capacity 50 KA, Incomer -1 NoOUTGOING(b) 4 Pole MCCB 400Amp 36 KA - 02 Nos (b) Digital Volt meter (0-500 V)-01 No(c) Digital Ammeter-01 No(d) CT's 400/5- set of 3 No(e) LED type Indication lamps (RYB)-one set |
| 27 | Supply and jointing straight through joint outdoor type 1100 volts grade heat shrinkable type suitable for 3.5x 25 sqmm to 3.5x 95 sqmm LT XLPE cable and testing after jointing complete all as specified and as directed. |
| 28 | Supply and jointing straight through joint outdoor type 1100 volts grade heat shrinkable type suitable for 3.5x 120 sqmm to 3.5x 240 sqmm LT XLPE cable and testing after jointing complete all as specified and as directed. |
| 29 | Servicing, cleaning and repairing of existing LT panel boards/feeder pillar boxes of various sizes including replacing the unserviceable CTs, Voltmeters, Ammeters, Selector switches, MCBs, MCCBs, indicator lamps etc. all as specified and as directed.Note:(i) Cleaning of inside/outside of LT panels/Feeder pillar boxes shall be done by using through suitable Blower. (ii) Spare parts like CTs, Voltmeters, Ammeters, Selector switches, MCBs, MCCBs, indicator lamps etc shall be measured and paid separately under relevant items of the schedule. |
| 30 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 400 to 630 Amps all as specified and as directed. |
| 31 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 250 to 320 Amps all as specified and as directed. |
| 32 | Supply and fix in repair CTs suitable for existing LT panel board of capacity 63 to 200 Amps all as specified and as directed. |
| 33 | Supply and fix in repair LED indicator lamps (R Y B ) suitable for existing panel all as specified and directed. |
| 34 | Supply and fix in repair MCCB 400 Amps, 4 pole 415 Volts, 50 Hz, 36 KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 35 | Supply and fix in repair MCCB 350 Amps, 4 pole 415 Volts, 50 Hz, 36 KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 36 | Supply and fix in repair MCCB 200 Amps, 4 pole 36 KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 37 | Supply and fix in repair MCCB 125 Amps 4 pole 25KA, adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 38 | Supply and fix in repair MCCB 100 Amps 4 pole 25KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 39 | Supply and fix in repair MCCB 63 Amps 4 pole 16KA adjustable thermal setting type and confirming to IEC 60947-II complete all specified and directed. |
| 40 | Supply and fix in repair digital ammeter 500Amps range suitable for mounting existing panel all as specified and directed |
| 41 | Supply and fix in repair digital voltmeter 500 Volts range suitable for mounting existing panel all as specified and directed |
| 42 | Supply and fix in repair selector switches suitable for ammeter/voltmeter all as specified and as directed. |
| 43 | Servicing, cleaning and repairing by dismantling and taking out air circuit breaker 400/630/800 amps capacity 3 pole 415 volts 50 Hz and removing mechanical assembly fixed and moving contact set and replacing mechanical parts like spring, bushes, levers and checking for worn out contacts, overvoltage and under voltage settings and replacing the following electrical parts (i) fixed contact assembly (ii) moving contact assembly, (iii) pole assembly (iv) Arc chute . Reassembling, testing and commissioning complete all as directed.Note:- Replacement of unserviceable electrical parts will be measured and paid for separately under relevant items of this schedule. |
| 44 | Supply & fix contact assembly for 630/800 Amps 3 pole 415 volts ACB all as specified and as directed. |
| 45 | Supply & fix contact assembly for 400 Amps 3 pole 415 volts ACB all as specified and as directed. |
| 46 | Supply & fix moving contact assembly for 630/800 amps 3 pole 415 volts ACB all as specified and as directed. |
| 47 | Supply & fix moving contact assembly for 400 amps 3 pole 415 volts ACB all as specified and as directed. |
| 48 | Supply & fix pole assembly for 630/800 amps 3 pole 415 volts ACB all as specified and as directed. |
| 49 | Supply & fix pole assembly for 400 amps 3 pole 415 volts ACB all as specified and as directed. |
| 50 | Supply & fix Arc chute for 630/800 amps 3 pole 415 volts ACB all as specified and as directed. |
| 51 | Supply & fix Arc chute for 400 amps 3 pole 415 volts ACB all as specified and as directed. |
| 52 | Supply & fix charging motor for 630/800 amps 3 pole 415 volts ACB all as specified and as directed. |
| 53 | Supply & fix charging motor for 400 amps 3 pole 415 volts ACB all as specified and as directed. |
| 54 | Supply & fix control relay for charging motor for 630/800 amps 3 pole 415 volts ACB all as specified and as directed. |
| 55 | Supply & fix control relay for charging motor for 400 amps 3 pole 415 volts ACB all as specified and as directed. |
| 56 | Supply and fix aluminium lugs suitable for UG cable of size 6 Sqmm to 25 Sqmm all as specified and as directed. |
| 57 | Supply and fix aluminium lugs suitable for UG cable of size 35 Sqmm to 50 Sqmm all as specified and as directed. |
| 58 | Supply and fix aluminium lugs suitable for UG cable of size 70 Sqmm to 95 Sqmm all as specified and as directed. |
| 59 | Supply and fix aluminium lugs suitable for UG cable of size 120 Sqmm to 185 Sqmm all as specified and as directed. |
| 60 | Supply and fix aluminium lugs suitable for UG cable of size 240 Sqmm to 300 Sqmm all as specified and as directed. |
| 61 | M&L for preparing old faded surface of existing LT panel/feeder pillar located at various places by rubbing and removing the old paint complete and painting with two coats of super enamel paint over a coat of red oxide primer including writing of incoming and outgoing feeder details as required size of letters complete all as specified and directed. |
| 62 | M&L for repairing and testing of Servo Controlled Stabilizer capacity 10/20 KVA at reputed workshop including disconnecting the LT cables complete and taking out the core and checking the continuity and insulation value of coils for all three phases, inspecting and reinsulating coils if required, repair and, replacing the wornout parts if any, all as specified and as directed.Note : The rate shall also deemed to be include the rate for :(i) Technician, Electrician and labours. (ii) Rewinding of coils (iii) Minor spares/parts. (iv) Transportation charges upto workshop and back. Please Enable Macros to View BoQ information |
| 63 | M&L for repairing and testing of Servo Controlled Stabilizer capacity 10/20 KVA at reputed workshop including disconnecting the LT cables complete and taking out the core and checking the continuity and insulation value of coils for all three phases, inspecting and reinsulating coils if required, repair and, replacing the wornout parts if any, all as specified and as directed.Note : The rate shall also deemed to be include the rate for :(i) Technician, Electrician and labours. (ii) Rewinding of coils (iii) Minor spares/parts. (iv) Transportation charges upto workshop and back. Please Enable Macros to View BoQ information |