| 1 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 2 | 20 mm |
| 3 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 4 | 1 x 1.5 sq.mm |
| 5 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 6 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 7 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 8 | Single pole MCB (With B / C curve tripping characteristics) |
| 9 | 6 A to 32 A rating |
| 10 | Double pole MCB (With B / C curve tripping characteristics) |
| 11 | 40 A rating |
| 12 | Triple pole MCB (With B / C curve tripping characteristics) |
| 13 | 50/63 A rating |
| 14 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 15 | 4 pole MCCB With Thermal Magnetic release |
| 16 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 17 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for MCB / RCCB/ RCBO up to 63 Amp and SP / TP MCB upto 32 Amp. as outgoing ,made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3 complete with insulated 100 A rating copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 18 | Double door IK-09 & IP-43 with Metal end box |
| 19 | 6 Way (8 Incomer +18 Outgoing) |
| 20 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB up to 63 Amps. as outgoing ,made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with insulated 125/160/200/250 Amp. copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 21 | Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal End Box |
| 22 | 6 Way |
| 23 | P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 24 | P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 25 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 26 | Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 27 | Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 28 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 29 | Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required. |
| 30 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant virgin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including making connections, testing etc as required. |
| 31 | 10 A one way switch |
| 32 | 16 Amp. 2 Module switch With Led Indicator |
| 33 | Providing & Fixing of IS:1293 marked modular type lockable feature socket with CM/L no. printed duly made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 34 | 6 A 3 pin shuttered socket |
| 35 | 6/16 A shuttered socket |
| 36 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required. |
| 37 | 5 step fan regulator 2 Module |
| 38 | Rewinding of ceiling fan motor (starting and running winding) including all necessary material. The motor is to be wound taking no. of coils, turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. (New model ceiling fan) |
| 39 | 900/1200 mm sweep (New model ceiling fan) |
| 40 | Labour charges for removing and refixing of Ceiling fan/ Exhaust fan from site |
| 41 | Charges for oiling, overhauling of ceiling fan, table fan, pedestal fan irrespect to the size of fan including removing,refixing of fan from site and testing etc. as required. |
| 42 | Fans with Removing & Refixing at Suitable Location |
| 43 | Providing and Replacement of ball bearing of ceiling/ exhaust fan and refixing the same at suitable location as requiredand as per OEM recommendations. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material shall be retained by the contractor. |
| 44 | P & F of submercible pump set suitable for 18/24 \\"Desert coolers. |
| 45 | Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capallary and strainer/ filter. |
| 46 | 1.5 TR Window/ Split A.C. |
| 47 | 2.0 TR Window/ Split A.C. |
| 48 | Servicing of 1.0/1.5/2.0 TR capacity Split/ Window type air conditioner |
| 49 | S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper wire. |
| 50 | Running capacitor |
| 51 | 2.5/3.15 micro farad |
| 52 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 53 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 54 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 55 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 56 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 57 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 58 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 59 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 60 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 61 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 62 | Electrolytic grade Aluminium bus bar 6010 grade |
| 63 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 64 | 35.0 Sq. mm |
| 65 | 3.5 core |
| 66 | 70.0 Sq. mm |
| 67 | 3.5 core |
| 68 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 69 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 70 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 71 | Add @ 18 % GST Please Enable Macros to View BoQ information |