| 1 | Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr deep in soft/loose soil and getting out for taking down cables of any description and in any position complete all as specified and directed. |
| 2 | Returning, filling in, excavated soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 Mtr & depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed. |
| 4 | Taking down old unserviceable LT cable of any size and any type from tranches/ walls /floor etc complete all as specified and as directed. |
| 5 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sqmm 4 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 6 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm 2 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 7 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm 4 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 8 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 9 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 10 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 11 | Supply and laying insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 12 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 13 | Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 Sqmm 3.5 Core, ISI marked as per IS 7098 (Part-I) in trench/floor/on pole/wall complete all as specified and directed. |
| 14 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 50mm outer diameter and 38 mm inner Diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed. |
| 15 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 75 mm outer diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed. |
| 16 | Supply and fix Double wall Corrugated High Density Polymer Ethyl (HDPE) pipe For laying of Electric cable of size 110 mm outer diameter with IS 14930 (part 2):2001 laid in trenches,wall,floor,pole including bends, sockets and other connected accessories complete all as specified and directed. |
| 17 | Supply, Installation , testing and commissioning of LT Distribution Panel (CPRI Approved) cubicle type IP-65, Outdoor type conforming to IS 5039 of 1983 factory fabricated prewired made out of 3.15mm thick CRCA sheet outer & 2mm thick CRCA sheet inner of suitable size to accommodate all accessories / fittings compartmentalized in construction to accommodate the incoming/outgoing MCCB and TPN bus bars and outgoing feeders. The TPN bus bars shall be insulated with colour coated heat shrinkable sleeve and shall be mounted on DMC support. The incoming as well as outgoing MCCBs shall have extersion links of current carrying cap not less than 1.5 times the rated capacity of individual feeders. The extension links shall be supported on DMC support having provision for termination of incoming and outgoing cables. All extension links/ interconnections shall colour coated sleeves. The cubicle shall have frame work, at bottom of MS channel MC100 fixed to the top of platform. The platform of LT Panel shall be pedestal type of suitable width and 600mm height above ground level and minimum 400 mm below the ground level constructed with bricks (sub class'B') work duly plastered in CM 1:3 and PCC coping (1:2:4) not less than 50mm thick over brick pedestal with adequate opening for entry of cable complete as per manufacture recommendation and directed by the Engr-in-Charge. A detacheable gland plate of thickness not less than 3 mm thick should be used at the botom for entry of armoured cable of adequate size compression glands, the panel shall be painting with powder coated finish with RAL 7032 SIEMENS GRAY Structure after seven tank phosphating treatment, front & back opening type, and fixing 2 Nos danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT Panel with voltage and danger indicated in Hindi and English with double door shutter and shall have lourvers and airvent gasket for natural flow of air Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following :-Note:- SLD diagram for LT Panel will be got approved from GE before placing the order |
| 18 | All as per item No 17 here-in-before but comprising of the following :-Incoming(a) TPN 04 nos aluminium busbar in equal size 3 phase and neutral 600 amp rating duly insulated fitted on heat shrinkable insulation and covered with colour sleeve.(b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microporcessed based type overload setting (Min 70% to 100%) - Qty -01 No (c) Onload Changeover Switch 400 Amps FP - 01 NosOutgoing (a) MCCB, 4 pole having current ratings 125 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with adjustable type overload setting (Min 70% to 100%) - Qty -01 Nos (b) MCCB 4 pole having current ratings 100 Amps, AC 415 Volts, with Ics = 16 KA, Ics = 100% of Icu, with thermal release and adjustable overload setting (Min 70% to 100%)- 02 Nos. (c) Onload Changeover Switch 100 Amps FP - 02 Nos (d) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) - 03 Nos (e) Multifunction meter for measure,current of Amp, Voltage and Frequency. (f) LED Indicator lamp - 01 (Set of Three). |
| 19 | All as per item No 17 here-in-before but comprising of the following :-Incoming(a) TPN 04 nos aluminium busbar in equal size 3 phase and neutral 600 amp rating duly insulated fitted on heat shrinkable insulation and covered with colour sleeve.(b) MCCB, 4 pole having current ratings 400 Amps, AC 415 Volts, with Icu= 36 KA , Ics = 100% of Icu, with microprocessed type overload setting (Min 70% to 100%) - Qty -01 No Outgoing (a) MCCB 4 pole having current ratings 100 Amps, AC 415 Volts, with Ics = 16 KA, Ics = 100% of Icu, with thermal release and adjustable overload setting (Min 70% to 100%) - 02 Nos (b) Onload Changeover Switch 100 Amps FP - 02 Nos (c) MCCB, 4 pole having current ratings 63 Amps, AC 415 Volts, with Icu= 16 KA , Ics = 100% of Icu, with thermal magnetic release and adjustable overload setting (Min 70% to 100%) - 04 Nos (b) Multifunction meter for measure,current of Amp, Voltage and Frequency. (c) LED Indicator lamp - 01 (Set of Three). |
| 20 | Supply and fix in replacement including testing and commissioning of 50 A / 415 volts, 3 phase AHF Panel (Active Harmonic Filter and Automatic Load Balancer) as per IEEE 519-2014, Power factor compensation 100% (Lead / Lag), Load Balancing : Negative Sequence Compensation (Zero Sequence compensation in 4 P / 4 W range), Reaction time: <0.3 ms, Interface (Communication) GSM, MODBUS RTU, USB, Ethernet, Profibus Compatible, IP-65, air cooling, overheating protection including necesary excavation and foundation work, complete all as specified and directed. |
| 21 | M&L in replacement Copper strip 32 x 6mm for connection of cable to the studs of transformer HV/LV, complete all as specified and directed |
| 22 | Supply and fixing of Smart integrated 30 Watt Smart Bright, All in one Solar Street Light ,Overcharged & deep discharge protection for battery, MPPT solar charge controller, LiFeP04 lithium Ferro Phosphate battery, maintenance free system 12.8 V (30A), 150 lumen/watt, Efficiency 90%, inbuilt BMS system, IP-65, lumen output ≥ 1500 Lm, Colour temp 5700K, Surge protection 5 KV, 50000 burning hrs (min), including nuts, bolts, washers. |
| 23 | Supply and fixing in replacement PVC insulated 1.5 sqmm copper conductor three core cable, 1100 volt grade, ISI marked for submerceble pumping set etc complete all as specified and directed |
| 24 | M&L for drilling suitable dia horizontal bore holes for insertion/ laying of upto 110mm bore HDPE pipe of any description below/under existing road surfaces/apron /floors etc with using mechanical and / or manual devices as required at site including making good the disturbed surfaces to match with the existing strata after laying pipes complete all as specified and directed. NOTE : (i) Pipes shall be laid minimum 60 cm below/under existing road surfaces/ apron /floors etc). (ii) Equipment, tools and plant material (horizontal boring rig machine) required for boring shall be arranged by contractor withut any extra cost to the Govt. |
| 25 | Supply and fix in repairs ABS Junction Box, Waterproof Box Enclosure Case, Outdoor of size (100 x 100 x 70 mm) with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 5-32 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of lugs etc, bakelite connector 4 way, 20 amp, dust and vermin proof, complete all as specified and as directed. |
| 26 | Supply and fix in repairs thermoplastic cable entry junction boxes of size 250 x 220 x 135 mm and IP-65 protection level with metric knock out fixed on poles with MS clamps, nuts, bolts and washers including MCB SPN, 5-32 amps, 'C' series, breaking capacity 10 KA, 'C' curve 240 volts, 50Hz including necessary incoming and outgoing electric connection with suitable size of copper lugs etc., separate (detachable) gland plate, bakelite connector 4 way 20 amp, dust and vermin proof, front door opening with hinges and locking arrangement, complete all as specified and as directed. |
| 27 | M&L for Earthing Complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.5 metre below ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using earth strip 25 x 4 mm by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and other end of the earth wire connected to main switch board protected by galvanised iron medium grade pipe 40mm bore in wall/floor/and GI Pipe 20 mm bore light grade for watering with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover including necessary excavation and earth work in any type of soil, returning slurry approved soil and disposed of surplus soil to a distance not exceeding 50 Mtr away all as shown in electrical plate No 3 of SSR 2009 ( Part-I).Notes :-(a) The unit rate shall include for GI protection pipe, GI watering pipe, wire mesh, funnel and excavation, RCC pit cover, test point, galvanised iron strip from top of earth plate upto 7.5 metres above ground level and if GI protection pipe is less than 7.5 metres, no price adjustment shall be made.(b) PCC pit shall be provided at least 50cm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fittings, junction, elbow etc shall be deemed to be included in the unit rate.(c) If the testing result of earthing work is not found satisfactory then the contractor shall do another earthing work at his own cost and nothing shall be permissible on this account. |
| 28 | Supply & fixing , Rigid non-metallic PVC conduit of size 20mm exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, pole clapms etc, complete all as specified and directed. |
| 29 | Supply and fix street light timer switch with voltage mounting device enclcosed in CRC sheet Enclosure for automatic and manual switching of street light based on LUX level of natural light , The sensor along with suitable power contactor MCB support terminal shell be housed in enclosure complete made out of anti rust/ shock proof/ termite proof/ confirming to IP 54 and IS/IEC 61439 & 60529 suitable for 12 KW (63 Amp) load compete all as specified and directed. |
| 30 | M&L for maint free safe earthing system burnished copper earthing electrolyte grade 5 centimeter dia closed with 5 centimeter electrolyte plate set of four separate electrode to be used as grid earthing each pit complete with 01 Number approved/CPRI tested copper bonded (copper cladded earth rod with C microns of copper cladding) earth rod with 1.7 centimeter mm dia 3.0 centimmetr long electrode buried in ground to bore holes 120 mm dia vertically to a depth not less than 3500 mm deep blow ground level or L shape in case of Rocky condition (2 ft deep and 8 ft horizontol) with top edge of earth electrode at a depth not less than 500mm below normal ground level, provision of copper bus bar of size 200mm x 25mmx6mm for inter connection with copper earth lead strip 25mm x 3mm and further connected to test point terminal block alongwith the protection pipe of size 25mm bore med grade all as directed. each earth pit shall include minimum 50kg (two bags of 25kg each) NABL lab Certified back fill compound and 6 kg (two container of 3kg Each) NABL Lab Certified conductive gel compound for filling bore holes with mother soil mixed in 1:3 ratio (one part of back fill compound and three part of mother soil), so as to achieve earth resistance below 1 Ohm including exacavation of polypit chamber with polyplastic pit cover (cost of poly pit chamber with polyplastic pit cover shall be deemed to be included in the rate quoted) complete all as specified and as directed. Note : (a) Copper strip beyond test point shall be measured and paid separately(b) Contractor shall give guarantee of minimum 5 yrs for the earting carried out by him. (c) The rate quoted is inclusive of test point made of phosphorous bronze of size 75x75x25mm, drilled and screwed including 3 Nos 8mm dia 25mm long brass nuts and bolts complete all as directed. (d) Any other fittings /fixtures if technically required for archieving desired results (if not included above) shall be provided by contractor without any extra cost to the Govt. (e) On testing after completion if the desired resistenance i.e below 1 Ohm is not obtained the contractor shall redo the earthing without any extra cost of department. Please Enable Macros to View BoQ information |
| 31 | M&L for maint free safe earthing system burnished copper earthing electrolyte grade 5 centimeter dia closed with 5 centimeter electrolyte plate set of four separate electrode to be used as grid earthing each pit complete with 01 Number approved/CPRI tested copper bonded (copper cladded earth rod with C microns of copper cladding) earth rod with 1.7 centimeter mm dia 3.0 centimmetr long electrode buried in ground to bore holes 120 mm dia vertically to a depth not less than 3500 mm deep blow ground level or L shape in case of Rocky condition (2 ft deep and 8 ft horizontol) with top edge of earth electrode at a depth not less than 500mm below normal ground level, provision of copper bus bar of size 200mm x 25mmx6mm for inter connection with copper earth lead strip 25mm x 3mm and further connected to test point terminal block alongwith the protection pipe of size 25mm bore med grade all as directed. each earth pit shall include minimum 50kg (two bags of 25kg each) NABL lab Certified back fill compound and 6 kg (two container of 3kg Each) NABL Lab Certified conductive gel compound for filling bore holes with mother soil mixed in 1:3 ratio (one part of back fill compound and three part of mother soil), so as to achieve earth resistance below 1 Ohm including exacavation of polypit chamber with polyplastic pit cover (cost of poly pit chamber with polyplastic pit cover shall be deemed to be included in the rate quoted) complete all as specified and as directed. Note : (a) Copper strip beyond test point shall be measured and paid separately(b) Contractor shall give guarantee of minimum 5 yrs for the earting carried out by him. (c) The rate quoted is inclusive of test point made of phosphorous bronze of size 75x75x25mm, drilled and screwed including 3 Nos 8mm dia 25mm long brass nuts and bolts complete all as directed. (d) Any other fittings /fixtures if technically required for archieving desired results (if not included above) shall be provided by contractor without any extra cost to the Govt. (e) On testing after completion if the desired resistenance i.e below 1 Ohm is not obtained the contractor shall redo the earthing without any extra cost of department. Please Enable Macros to View BoQ information |