| 1 | Dismantling of existing U/S PCC/Struts pole of any size & type from its position carefully and removing from the site and necessary excavation and earth work in any soil/strata, demolation of complete concrete from its base foundation, disconnection of conductor/wires/cables/street light brackets/street light of any type fom pole etc. complete all as directed.Note : (a) Old street light fittings retreived shall be deposited to E/M store(b) The rate quoted shall also be deemed to include the cost for making good the existing surface after removal of old poles/debris. |
| 2 | Supply and errect 9 mtr octagonal pole hot dip galvanised conforms to BS EN - ISO 1461, top -70-bottom 155 mm – 3 mm thickness ,shaft material hot rolled steel plate conform to IS 2062/BSEN 10025 or equivalent , Flange /Gussets /Door stiffener as per IS -2062/bsen 10025 or equivalent grade , Foundation bolt EN8 grade including 1.5 MTR SINGLE ARM BRACKET, FOUNDATION BOLT M24x750 MM J TYPE Including necessary foundation and coping all as per OEM specification/drawings complete all as specified and as directed also including provision of the followings:-(a) MCB,SP,10A,230V, C series, 10KA mounted on and including 3mm thick plastic laminated sheet-01No.(b) 4 way connector, bolt type having locking arrangement, weather proof and water proof control space : 01 No.Notes: (a) The rate quoted shall also be deemed to include the cost for provision of 50mm bore PVC pipe from cable trench to centre of the pole concrete of the pole concrete.(c) The rate quoted shall also be deemed to be inclusive of providing necessary foundation and coping all as per OEM Specifications/approved drawingsMake:- Bajaj/Utkarsh or equivalent as approved by GE |
| 3 | Supply and fixing LED street light fitting 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete |
| 4 | S& F in replacement XLPE insulated armoured and pvc sheated heavy duty electric cable size 4 core ,16 Sqmm cross sectional area with aluminium conductor 1100 volt grade as per IS 7098 (Part-1) 1988 with latest amendment laid in trenches/duct passing through pipes including fixing with necessary clamps testing complete note- rate is inclusive of cable gland & cable lugs Make- Havells/FINOLEX/CCI/KEI/POLYCAB |
| 5 | Excavation in trenches in hard /dense soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC poles/stays and struts etc and getting out including trimming sides and forming bottom surface all as specified and directed at site. |
| 6 | Returning, filling in including spreading, leveling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested, poles, stays , struts have been erected and tested , all as specified and directed at site |
| 7 | Removing excavated surplus soil (Soft/hard soil) obtained from excavation to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed. |
| 8 | M & L for Cutting the existing PCC floor/road/foot path not exeeding 15cm width,30 cm depth for laying of UG cable/protection of pipe all as directed. |
| 9 | M & L for PCC type B1,1:2:4 using 20 mm graded stone aggregate all as specified and directed. |
| 10 | S& F in replacement of laying of Double Walled Corrugated (DWC) HDPE pipe of following size 40/32 mm outer/inner dia of conforming to IS 16205 Part -24 including necessary bends,coupling ,tees, reducers, spacers,end caps, rubber rings etc having pressure rating not less than 450 N through trenches/wall/floor/on pole in any type of soil for protection of electric cable complete all as directed by Engr-In Charge Make:-ASTRAL TELEREX /eqivalent as approved by GE |
| 11 | S& F in replacement of PVC junction box of size inside dimenssion 250x200x100 mm complete with industrial connector, including clamp made out of MS flat iron 30x5 mm , nut, bolts, washer etc , MCB 6-10Amps complete all as specified & directed Make:Sintex cat no : GS JB 2520 |
| 12 | S& F in replacement of PVC insulated 3 core 1.5 sqmm multistranded Copper conductor cable on pole for security light from junction box to street light fititng including making necessary hole on surface of pole for insertion of 3 core pvc cable inside the pole upto street light fitting as specified & directed. etc complete all as specified and directed. Make:- Polycab/Havells/Gloster/KEI/Finolex |
| 13 | S& F in replacement of Steel tubing GI light grade for cable protection passing under road /floor or for fixing to poles all as specified and as directed of size 50 mm dia along with necessary clamp duly painted with silver aluminuim paint nut bolt etc, including PVC bend of required size for cable entry at bottom of pole complete all as specified and directed. Make -TATA / JINDAL /SWASTIK |
| 14 | M& L for replacement of Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly including chemical powder for earhing and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel iron as eartlung lead all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion |
| 15 | M & L for marking of pole numbers with radium yellow/ black paint /sticker in round shape suitable dia with letter writing 5 cm height 5 mm width etc. complete all as specified and directed at site.by Engineer-in-Charge |
| 16 | Demolition of concrete of any description and in any position not otherwise specifically provided for cement concrete (unreinforced) complete including removing debries ouside MD land all as specified and directed |
| 17 | M & L cement conc 1:4:8 type D-2 (40mm graded agg) in foundation filling and concrete complete all as specified and as directly by Engineer-in-Charge |
| 18 | M & L for sand filling under paver blocks for cushion Complete all as specified and directed. |
| 19 | M&L for machine presssed precast concreate interlocking paver block any shape and size confirming to IS 15658-2006 of 60mm thickness, M-35 Grade with grey cement pigment to match, Complete all as specified and directed. |
| 20 | All as per above Except interlocking tiles including filling with sand cushioning (where ever required ) including levelled with Existing tiled surfaces Complete all as spd and directed by Engineer in Charge (Note :- Sand and PCC shall be paid and measured Separtely) Please Enable Macros to View BoQ information |