| 1 | Supply and fixing in replacement of Switch air break gang operated triple pole mechanically operated from ground level, mounted on insulators and steel frame (15 insulator type) outdoor type suitable for vertical installation single break provided with locking arrangement consisting of MS channel, HT post top porcelene insulator with drop out fuses operating Rod 20m dia GI pipe medium grade confirming to IS:1818 of 1972 and current rating 200 Amp and voltage 11 KV complete all as specified including jumpering, lead of wire/cable as directed at site completed as per directed and as specified. |
| 2 | Supply and fixing in replacement of Switch air break gang operated triple pole mechanically operated from ground level, mounted on insulators and steel frame (15 insulator type) outdoor type suitable for vertical installation single break provided with locking arrangement consisting of MS channel, HT post top porcelene insulator with drop out fuses operating Rod 20m dia GI pipe medium grade confirming to IS:1818 of 1972 and current rating 400 Amp and voltage 11 KV complete all as specified including jumpering, lead of wire/cable as directed at site completed as per directed and as specified. |
| 3 | Supply and fixing in replacement of 12 KV lightning arrestor station class 30 KA completed as per directed and as specified. |
| 4 | Supply & laying in front of HT panels, under GOD etc Rubber mats of size 1mtr x 2mtr x 19mm thickness 11 KV. completed as per directed and as specified. |
| 5 | Supply and fixing in replacement of anti climbing device, spikes type, fabricated out of MS bars (round, square or flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the poles, spike welded to flat iron, including on primer coat, one under coat and two finishing coats of silver aluminium paint including preparation of surfaces.completed as per directed and as specified. |
| 6 | Supply and fixing in repl of pin/post insulator HT 11 KV complete with all fittings and size 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed. |
| 7 | Supply & fixing in replacement of male contact (moving contact blade) as per sample approved by GE suitable for 11 KV 400 Amp rating GOD including cable lead/wires, thimbles and connected items etc,completed as per directed and as specified. |
| 8 | Supply & fixing in replacement of female contact as per sample approved by GE (fixed contact jaw) suitable for 11 KV 400 Amp rating GOD including cable lead/wires, thimbles and connected items etc,completed as per directed and as specified. |
| 9 | Supply & fixing in replacement of tinned copper flexible jumper suitable for 11 KV 400 Amp rating GOD,completed as per directed and as specified. |
| 10 | Demolition of Cement concrete (unreinforced) in Poles/ four pole/two pole/HT& LT pole/panel/approach path to sub station (below or above ground level) and removing all the demolished material outside cantt area. completed as per directed and as specified. |
| 11 | Supply and fixing in replacement of Danger notice plate of 1.6mm thick MS sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal Red colour and inclusive fixed with MS flat clamps 25x3mm 2 Nos, nuts, bolts for LT 440 volt of size 20x15cm completed as per directed and as specified. |
| 12 | All as per ser item No 12 above here-in-before but for HT 11000 Volt 25x20cm in size complete. completed as per directed and as specified. |
| 13 | M & L in replacement of Earthing complete with galvanised steel earth plate 600 x 600 x 6mm buried directly in ground vertically to a depth not less than 2.25 mtr below normal ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level connected to and including GI strip 25x4mm by means of nuts, bolts, washers etc made of and connected to test point and earth dolly as all shown in electrical plate No.3 of SSR Part-I 2009 and specified or indicated including excavation and earth work in any type of soil PCC (1:3:6) type C1 in chamber, pre cast RCC slab 50mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 kg/Sqm with cast iron frame, funnel, with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 15mm bore medium grade GI protection pipe, test point etc complete all as specified and directed. (Length of GI earth strip & Protection pipe is up to 7.5 RM including) Note : - If soil required in earthing shall be provided by contractor without any extra cost. No extra amount shall be given to contractor for extra earthing soil. completed as per directed and as specified. |
| 14 | M & L in replacemement of Earthing complete with galvanised steel earth plate 600 x 600 x 6mm buried directly in ground vertically to a depth not less than 2.25 mtr below normal ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level connected to and including GI wire of size 4 mm by means of nuts, bolts, washers etc made of and connected to test point and earth dolly as all shown in electrical plate No.3 of SSR Part-I 2009 and specified or indicated including excavation and earth work in any type of soil PCC (1:3:6) type C1 in chamber, pre cast RCC slab 50mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 kg/Sqm with cast iron frame, funnel, with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 15mm bore medium grade GI protection pipe, test point etc complete all as specified and directed. Note : - If soil required in earthing shall be provided by contractor without any extra cost. No extra amount shall be given to contractor for extra earthing soil completed as per directed and as specified. |
| 15 | Supply and fix in replacemement of GI Strip of size 25 x 4 mm along the wall, floor, ceiling etccompleted as per directed and as specified. |
| 16 | Supply and fixing in replacement of pin/post insulator HT 33 KV complete with all fittings completed as per directed and as specified. |
| 17 | Supply & fixing in replacement of cross Arms, bracings, supports, clamps, Angle etc fabricated from steel including nuts, bolts, washers, welding, bending, drilling holes for bolts in any shape or size as directed inclusive of one primer coat, one under coat and one finishing coat of aluminium paint incl Dismantling completed as per directed and as specified. |
| 18 | Material and Labour in replacement of Chain link MS Galvanised fencing of 4 mm dia wire of size 50 mm x 50 mm cold dip fixed to angle frame and flat iron with suitable nuts and bolts any size or typecompleted as per directed and as specified. |
| 19 | M & L for Plain cement concrete 1:4:8 type D-2 using 40mm graded crushed stone aggregate as in foundation of poles etc completed as per directed and as specified. |
| 20 | M & L for Plain cement concrete 1:2:4 type B-1 using 20mm graded crushed stone aggregate as in coping of poles/Transformer plinth etc including necessary form work completed as per directed and as specified. |
| 21 | Surface excavation not exceding 30 cm deep in soil soft/loose and averaging 15 cm deep and getting out green vegetation, roots, bushes, etc surrounding of 2 / 4 / 6 pole structure / substations / Panels complete all as specified and as directed. |
| 22 | Rendering 15 mm thick in CM 1:4 on brick wall surface or concrete surface finished even and fair without using extra cement upto any height complete all as specified and directed. |
| 23 | Dismantling concrete poles/ struts, any sizecompleted as per directed and as specified. |
| 24 | Dismantling insulators any type, any sizecompleted as per directed and as specified. |
| 25 | M & L for errection Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 metres long) completed as per directed and as specified. |
| 26 | M & L in replacement of Aluminium conductor, steel reinforced wisel/fereet for making bus bar on pole streching including taking down completed as per directed and as specified. |
| 27 | Servicing of HT 11KV indoor VCB panel and breakers of any make with mechanism comprising of the following:-(a) Decarburizing/cleaning complete 11kV HT Bus bar chamber with electrical connections, complete bus bar from the bus bar chamber , Cleaning with CTC and ensure proper decarburizing up to proper megger value, refixing the same after applying Backtol Red solution to the bus bar insulator and checking all the connections, tightening the nuts, bolts complete including replacement of defective rusted bolts and nuts all as specified and directed.(b) Servicing of spring loaded operating mechanism.(c) Servicing of spring charging motor.(d) Checking and servicing of gearbox, auxiliary switches, spring, limit switch etc complete.(e) Checking and repairing electrical and mechanical operations(f) Lubrication all moving parts with petroleum jelly and cleaning all bushing insulators with CTC (g) Tightening of all mechanical connections of mechanism(h) Proper Tightening all LV connection of VCB.After completion of above items HT 11 KV supply will be restored as per disconnecing order and testing, completed as per directed and as specified. Please Enable Macros to View BoQ information |
| 28 | Servicing of HT 11KV indoor VCB panel and breakers of any make with mechanism comprising of the following:-(a) Decarburizing/cleaning complete 11kV HT Bus bar chamber with electrical connections, complete bus bar from the bus bar chamber , Cleaning with CTC and ensure proper decarburizing up to proper megger value, refixing the same after applying Backtol Red solution to the bus bar insulator and checking all the connections, tightening the nuts, bolts complete including replacement of defective rusted bolts and nuts all as specified and directed.(b) Servicing of spring loaded operating mechanism.(c) Servicing of spring charging motor.(d) Checking and servicing of gearbox, auxiliary switches, spring, limit switch etc complete.(e) Checking and repairing electrical and mechanical operations(f) Lubrication all moving parts with petroleum jelly and cleaning all bushing insulators with CTC (g) Tightening of all mechanical connections of mechanism(h) Proper Tightening all LV connection of VCB.After completion of above items HT 11 KV supply will be restored as per disconnecing order and testing, completed as per directed and as specified. Please Enable Macros to View BoQ information |