| 1 | Dismentling / Taking down old Aluminium conductor steel rainforced any type and size. |
| 2 | Dismentling / Taking down old insulator any type and size for 1100 volts grade. |
| 3 | Dismentling / Taking down of Cross arms of MS channels or angle section complete. |
| 4 | Dismentling of old stay assembly complete. |
| 5 | Supply & Laying in repair cable XLPE insulated PVC bedded ,galvanized steel strip or wire armoured ,electric power cable heavy duty 1100 volts grade with stranded aluminum conducter of following sizes:- Make :- Polycab/ Gloster/KEI |
| 6 | 10 Sqmm x 4 Core |
| 7 | 25 Sqmm x 4 Core |
| 8 | 35 Sqmm x 3.5 Core |
| 9 | 70 Sqmm x 3.5 Core |
| 10 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth and getting out Soft / loose all as specified and directed :- |
| 11 | Excavation in trenches for errection of poles etc.,n. exc 1.5m wide, exc 1.5m and n. exc 3.0m in depth and getting out in soft / loose soil complete all as specified and directed by Engr-in-charge. |
| 12 | Returning, filling in soil, including spreading, leveling watering and well ramming in layers not exceeding 25 cm all as specified and directed. |
| 13 | Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point of any type of excavation all as specified and directed by Engineer -in-Charge. |
| 14 | M & L in repair HDPE DWC pipe ISI Marked fixed on walls, ceilings or in floors, trenches etc. for cable protection of the following outer dia :- Make:-Infra/Supreme/Prince |
| 15 | All as per item no 10 here in before but size of cable 50 mm dia |
| 16 | All as per item no 10 here in before but size of cable 80 mm dia |
| 17 | M& L for GI tubing 50 mm dia light grade for cable protection |
| 18 | M&L for road cutting and making good with PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) complete all as directed by Enger -in- charge. |
| 19 | Taking down unserviceable pole and Supply & Erect in repair in position steel tubular pole swagged type as per IS 2713 complete with MS base plate finial tapper plug cap bolt, nut, screws etc all as specified for swaged pole of type 410 SP 31 , 09 mtrs long incl painting with two coats of aluminium paint over a coat of red oxide paint all as directed including removing existing pole.( Note :- Excavation and earth work and PCC in foundation shall be measured and paid separately)Make : Electrosteel/ Indian Pole/ Singh Profiles/ Kalki tubes & Poles |
| 20 | Supply and fix in replacement of fibre looping box with connector and MCB SP 2 to 6 Amps of size 250x200x100 mm including making connections all as specified and directed by .Make - United / National / Sintex |
| 21 | Taking down unserviceable street light fitting and supply and fixing LED street light fittings 60W 5700K with DPD energy saving & environmental friendly long life Versatile pressure die-cast aluminium IP66 roadway luminaire with necessary Bracket 50 mmGI Pipe with extended arm ,with Clamp ,nut& Bolts complet all as directe.Make:Havells, Bajaj,Philips |
| 22 | Demolition of PCC coping , base , etc any type |
| 23 | M&L for provision of PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and as directed. |
| 24 | M & L for plain cement concrete 1:3:6 type C1 (using 20mm graded stone aggregate) as in plinth, platforms, pole coping etc., all as specified and as directed. |
| 25 | M & L for plain cement concrete 1:2:4 type B1 (using 20mm graded stone aggregate) as in plinth, platforms, pole coping etc., all as specified and as directed. |
| 26 | Design Fabricating supply and errecting connecting and testing totally enclosed LT cubicle panel board 3 Phase 4 wire system outdoor double door front and sloped canopy (Hood) on top , incoming and out going feeders duly marked on revited plates etc complete CPRI approved factory made fabricated out of 3mm thick CRCA sheet duly treated through 7 tank pre treatment process and painted with epoxy powder coated mat finish of SIEMENS GREY structural RAL 7032 shade colour,built in industrial type locking arrangement on front and back ,and pre wired with PVC insulated multi stranded copper conductor for controls and monitors, PVC sleeved aluminium strip for connecting MCCBs ,Panel mounted on Anle iron frame of sutable size 45 CM above ground level & 30 CM below gland consisting of following;- Busbar Chamber: Electrically grade Bus bar aluminium of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears duly insulated with colour coded heat shrinkable sleeve and mounted on suitable size of 'F' class insulators made of non hygroscopic,non combustible,track resistant high strength FRP insulators for phases and neural set of 4 for RYB &N - 01 set Digital Voltmeter -01NoDigital Ammeter with CT set-01NoIndicating lamp RYB -01SetIncommerMCCB 4 Pole 63A, 16 KA thermal & magnetic release. |
| 27 | M & L in repairs for earthing with galvanised steel earth plate electrode 60cmx60cmx6.3mm burried directly in ground earth pit not less than 2.25 m deep below normal ground level with top edge of the plate vertically to depth of not less than 1.2m below ground level connected to and including GI strip of size 25 x 4 mm as earthing lead welded with earth electrode (excluding GI protection pipe) and connecting to equipments by means of earthing lead connecting to equipments by means of GI bolts & nuts etc. with provision of char-coal and salt etc. all as per electrical plate No. 3 of SSR Part I, 2009 including RCC cover and MS angle iron frame watering arrangement with GI pipe 20mm dia (medium grade) & MS funnel, concrete pit including excavation and earthwork and testing on completion etc complete all as specified and directed by Engr-in-Charge.Note: Rate quoted deemed to be including excavation by compressor M/C for Soft disintegrated rock to required depth. |
| 28 | Supply instal testing and commissioning of CPRI approved factory make LT panel board , outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side double door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3.15 mm thick CRCA sheet with powder coated finished suitable length and size. High conductivity 3 phase and neutral copper bus bar of 400 Amps capacity duly mounted on pre cast insulators including earth work excavation, PCC foundation necessary coping work, nuts and bolts and connecting electrically with suitable copper cable lug, cable glands etc complete all as specified and directed to accomodate the following itemsIncoming:-(A) MCCB 160 amps 4 pole 25 KA thermal & magnetic release - 1 Nos.(B) Advanced Multi functional meter 4420 series LCD meter C1 with RS 481 MAKE :- CAT No WC442011OOOO of L&/Seimens/Schiender(C) LED type indication lamp for RYB.Outgoing:(a) MCCB 100 amps 4 pole 16 KA thermal & magnetic release- 02 Nos.(b) MCB 63 amps TPN - 02 Nos. (c) MCB 40 amps TPN - 04 Nos Please Enable Macros to View BoQ information |