| 1 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1.2 x 1.5 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters (compatible with smart meter size space) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 07 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :- (a) Aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated Al strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) incoming MCCB, four pole, 415 volts, 100-125 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No. (c) outgoing MCB SPN, 40 Amp,10 KA C-Curve - 07 Nos. (d) Multifuction meter(0-500) Volts with inbuilt selector - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note:- (I) Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge(II) charges for old meter taking down carefully from old panel refixing done in new panel is included in qouated rate |
| 2 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1 x 1 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters (compatible with smart meter size space ) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 05 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :- (a) Aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated Al strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) incoming MCCB, four pole, 415 volts, 63-100 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No. (c) outgoing MCB SPN, 40 Amp,10 KA C-Curve - 05 Nos. (d) Multifuction meter(0-500) Volts with inbuilt selector - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note:- (I) Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge(II) charges for old meter taking down carefully from old panel and refixing done in new panel is included in qouated rate |
| 3 | Supply & fix in replacement of sheet metal enclosure indoor type of size 1.5 x 1.1 x 0.25 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for three phase smart energy meters (compatible with smart meter) and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment 05 Nos duly crimped with copper thimbles, duly powder coated complete incl taking down old meter panel all as specified and directed by Engr-in-charge and consisting with the following :- (a) aluminium Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) incoming MCCB, four pole, 415 volts, 125 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No. (c) outgoing MCB TPN, 63 Amp,10 KA C-Curve - 05 Nos. (d) Multifuction meter(0-500) Volts with inbuilt selector - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note:- Before manufacuring of eletric meter panel drawing should be passed through Engineer-in- Charge |
| 4 | Taking down carefully sub-main wiring any type including dismantling of accessories and making good disturbed surfaces to match the existing complete all as specified and directed. |
| 5 | M&L for sub-main wiring along with earth continuity conductor, using PVC insulated FRLS, multi-stranded copper conductor cables, colour-coded, drawn into and including concealed rigid non-metallic PVC conduit, medium grade, ISI marked, ivory colour, complete with all conduit accessories such as bends, tees, junction boxes, inspection boxes, saddles/clamps etc including cutting chases, making good disturbed surfaces to match existing finish complete in all respects of the following nominal sizes:–(a) 2x4 sqmm + 1x4 sqmm earth wire in 20 mm dia conduit. |
| 6 | All as item No 05 above but size 2x6 sqmm + 1x6 sqmm earth wire in 25 mm dia conduit complete all as specified and directed. |
| 7 | All as item No 05 above but size 2x10 sqmm + 1x10 sqmm earth wire in 25 mm dia conduit complete all as specified and directed. |
| 8 | S&F sub main wiring with two single core PVC FRLS insulated multistranded copper conductor of size 4 sqmm nominal cross sectional area and one run of 4.0 sqmm nominal cross sectional area PVC FRLS insulated multistranded copper conductor green colour as continuous earth wire drawn in and including not less than 20mm dia 'medium grade' PVC existing conduits (ISI marked) and fittings complete all as specified and directed.NOTE:- One unit length shall measured as two run of main wire and one run of conduit & earth wire. |
| 9 | Supply and fixing in replacement for 1.5 sqmm single core copper, multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed. |
| 10 | Supply and fixing in replacement for 2.5 sqmm single core copper, multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed. |
| 11 | S & F in replacement of three core PVC insulated FRLS sheathed cable with 1.5 sqmm stranded copper conductor complete all as specified and directed. |
| 12 | S&F in replacement 1100V grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connection ,one twin core cable flat or circular strande 10 sqmm aluminiuam conductor complete all as specified and directed. |
| 13 | S&F in replacement of MCB Distribution Board, factory-assembled type, fabricated from powder-coated CRCA steel sheet, recess-mounted, complete with reversible double door, having a minimum degree of protection IP-43 and mechanical impact resistance IK-09, conforming to IS 61439 (Low-voltage switchgear and controlgear assemblies), provided with insulated tinned copper busbar of 100 Amp rating, separate neutral busbar and earth busbar, DIN rail, detachable gland plate, complete with all internal interconnections, earthing connections, and blanking plates for all unused ways/spaces, complete in all respects, suitable for the following ratings and number of ways:–(a) SPN, 240 volts, 4 ways. |
| 14 | All as item No 13 above but SPN, 240 volts, 8 ways complete all as specified and directed. |
| 15 | All as item No 13 above but SPN, 240 volts, 12 ways complete all as specified and directed. |
| 16 | All as item No 13 above but TPN, 415 volts, 4 ways complete all as specified and directed. |
| 17 | Supply and fixing in replacement of modular type AC box with socket plug top and MCBs with two pin and one pin for earth plug and socket complete with one single pole MCB 20 Amp complete all as specified and directed. |
| 18 | S&F in replacement of sheet metal enclosure distribution board triple pole and neutral (VTPN),double door, AC, 440 volt, 04 way with 200 Amp rated copper bus bar and metal door with IP 54 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete and comprising of the following:- (a) MCCB, 100-125 Amp, 04 pole, AC, 415 Volt of 16 KA breaking capacity complete - 01 No. (b) MCB, SP, AC, 240 volt of 06 to 32 Amp, \\"C\\" curve, 10 KA breaking capacity - 12 Nos. |
| 19 | S&F in replacement of sheet metal enclosure distribution board triple pole and neutral (VTPN),double door, AC, 440 volt, 06 way with 200 Amp rated copper bus bar and metal door with IP 54 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete and comprising of the following:- (a) MCCB 63-100 Amp, 04 pole, AC, 415 Volt of 16 KA breaking capacity complete - 01 No. (b) MCB, SP, AC, 240 volt of 06 to 32 Amp, \\"C\\" curve, 10 KA breaking capacity - 16 Nos. |
| 20 | M&L for earthing with galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanised earth lead wire 4 mm dia by means of steel bolts, nuts, check nuts and washers all as shown in electrical plate no 3 of MES SSR Part-I (2009) connected to earthing point and testing on completion with and including 15 mm bore light grade G.I. protection pipe (upto 7.5 metre beyond outer edge of earth pit) PCC pit in mix 1:3:6 type C1 with RCC 1:2:4 type B-1, earth pit cover 40 mm thick reinforced with 6 mm dia M.S bars 3 Nos both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work complete all as specified and directed. |
| 21 | S&F in replacement of MCBs of ‘C’ series, with breaking capacity 10 kA, ISI marked, complete with making wiring connections using suitable size copper lugs, tightening, testing and commissioning, installed inside MCB distribution boards complete in all respects of the following current ratings:–(a) SP 6 to 32 Amp. |
| 22 | All as item No 21 above but SPN (or DP) 10 to 32 A complete all as specified and directed. |
| 23 | All as item No 21 above but SPN (or DP) 40 to 63 Amp complete all as specified and directed. |
| 24 | All as item No 21 above but TPN (or FP) 40 to 100 Amp complete all as specified and directed. |
| 25 | S&F in replacement of MCCB, four-pole, 63 Amp, with minimum breaking capacity 16 kA (Icu = Ics), thermally adjustable type with thermal overload setting range from 70% to 100% of rated current, and fixed magnetic short-circuit protection, with spreader links (set of four) for cable connections, suitable cable lugs, nuts, bolts and washers including making all electrical connections complete all as specified and directed. |
| 26 | S&F in replacement of MCCB, four-pole, 100 Amp, with minimum breaking capacity 16 kA (Icu = Ics), thermally adjustable type with thermal overload setting range from 70% to 100% of rated current, and fixed magnetic short-circuit protection, with spreader links (set of four) for cable connections, suitable cable lugs, nuts, bolts and washers including making all electrical connections complete all as specified and directed. |
| 27 | S&F in replacement of MCCB, four-pole, 125 Amp, with minimum breaking capacity 16 kA (Icu = Ics), thermally adjustable type with thermal overload setting range from 70% to 100% of rated current, and fixed magnetic short-circuit protection, with spreader links (set of four) for cable connections, suitable cable lugs, nuts, bolts and washers including making all electrical connections complete all as specified and directed. |
| 28 | S&F in replacement of MCCB, three-pole, 63 -100 Amp, with minimum breaking capacity 16 kA (Icu = Ics), thermally adjustable type with thermal overload setting range from 70% to 100% of rated current, and fixed magnetic short-circuit protection, with spreader links (set of four) for cable connections, suitable cable lugs, nuts, bolts and washers including making all electrical connections complete all as specified and directed. |
| 29 | M & L in replacement of Air termination, single pointed aluminium rod 12mm dia and 300mm long complete all as specified and directed. |
| 30 | M & L in replacement of Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 nos, 8mm dia 25mm long hex. head screw complete all as specified and directed. |
| 31 | S&F in replacement of Galvanised iron strip 25 x 3 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground with rectangular blocks below the strip complete all as specified and directed. |
| 32 | Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cable crossed linked polyethylene (XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. |
| 33 | All as item No 32 above but of size 10 Sqmm 4 core complete all as specified and directed. |
| 34 | All as item No 32 above but of size 25 Sqmm 4 core complete all as specified and directed. |
| 35 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in soft/loose soil complete all as specified and directed. |
| 36 | Returning, filling in, including spreading, levelling, and well ramming in layer not exceeding 25 cm thick in soft/loose soil complete all as specified and directed. |
| 37 | Removing excavated material ( soils) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified. |
| 38 | Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete as specified and directed .Note :- Punned thickness shall only be considered for payment |
| 39 | M&L laying well burnt old size bricks, sub class \\"B\\" bricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection complete all as specified and directed. |
| 40 | Boring/Drilling ( horizontally) manually under existing road ( maximum 10 M in width) suitable for passing GI tubing of 40 to 100 mm bore complete all as specified and directed. |
| 41 | S & F GI tubing 'Light' grade 40 MM for cable protection fixed in poles/walls/laid under roads/crossing etc incl taking out the rusted pipes of following sizes, complete all as specified and directed. Please Enable Macros to View BoQ information |