| 1 | Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 240 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed. |
| 2 | S & F of Air break gang operated switch triple pole mechanically operated out door with all fitting/ accessories mounted on and including 11 KV porcelain insulator and steel channel frame GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically or horizontal operated as per site requirement including locking arrangement for operating handle complete suitable for current rating 200 Amps, HT 11 KV 50 cycle AC working pressure with 9 Insulators complete all as specified and directed. |
| 3 | S & F XLPE cable end termination, cold shrinkable, outdoor type, suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core 240 sqmm complete all as specified and as directed. |
| 4 | S & F cable jointing kit for 6.35 kV/ 11 kV (Earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm complete all as specified and as directed. |
| 5 | M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed. |
| 6 | Supply and installation (above ground) including testing HT Joint box 2 way outdoor type of size 1500 x 1000x900mm (overall) made out of 3.15 mm thick CRCA sheet with support of angle iron frame of size 40 x 40 x 6 mm with KIOSK BOX and comprising of 03 Nos HT porcelain bushing and copper round bus bar 12 mm dia rigidly mounted on bakelite sheet 12mm thick to support insulators of suitable size and shape including providing necessary electric connection and applied two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces (internally & externally) including PCC foundation based of size 1700 mm x 400 mm x 1400 mm height (700 mm above GL & 500 mm below GL) with PCC 1:3:6 type C1 using 20mm graded aggregate complete including necessary excavation and earth work for foundation and necessary electric connection complete all as specified and as directed. |
| 7 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed. |
| 8 | Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed. |
| 9 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. |
| 10 | Removing excavated material not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 11 | Supply & laying Sand coarse dry as in cushioning of underground electric cable in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. Note :- Only punned down sand shall be measured. |
| 12 | Supply & laying unreinforced precast concrete cable cover class HVP type 1, with peak shape, dimension 300 mm X 180 mm X 40 mm and 65 mm peak thickness as per IS 5820: 1970 complete all as specified and directed. |
| 13 | Supply and laying of HDPE Pipes PN 10 of dia 100 mm complete all as specified and directed. |
| 14 | M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and directed. |
| 15 | S & F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 mm X 6 mm galvanised mild steel strip complete all as specified and directed. |
| 16 | M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) seamless type, including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of bituminious paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed. Note- Earthwork and PCC shall be measured and paid seperately. Volume occupied by steel pole shall be deducted to derive the quantity of PCC. |
| 17 | M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 18 | M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 19 | M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed. |
| 20 | Suppply and fix Precast cement concrete cable route marker indicator of size 600mx 350mm x50mm having \\"MES HT CABLE\\" written by embossing or engraved over surface of the route marker duly painted in red colour, fixing over the route of existing HT cable complete all as specified and directed. |
| 21 | M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine including insertion of HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed. Please Enable Macros to View BoQ information |