Tender For Provn Of Avionics Engineering Complex (Aec) At Afs Tambaram
Tender Value
7.40 Crore
Estimated cost
Bid Submission
28 Jul 2026
16 days left
EMD
6.95 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Tambaram → Tamil Nadu
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Avionics Engineering Complex (Aec) At Afs Tambaram
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-Jul-2026 | AMENDMENT 01 | Date | 28-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | BOQ Dated Jun 2026 |
| 2 | GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to XII are prepriced by MES under Ser No. 1 to 12. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 3 | Lumpsum price worked out by the contractor for “(UNDER GROUND SUMP(FIRE FIGHTINGS HYDRANTS)\\" as listed in Schedule ‘A’ Part - I. |
| 4 | Lumpsum price worked out by the contractor for \\"INTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part - II. |
| 5 | Lumpsum price worked out by the contractor for \\" INTERNAL ELECTRIFICATION \\" as listed in Schedule ‘A’ Part - III. |
| 6 | Lumpsum price worked out by the contractor for \\"PAVER BLOCK PATH\\" as listed in Schedule ‘A’ Part - IV. |
| 7 | Lumpsum price worked out by the contractor for “SEWAGE DISPOSAL” as listed in Schedule ‘A’ Part – V. |
| 8 | Lumpsum price worked out by the contractor for “AREA DRAINAGE” as listed in Schedule ‘A’ Part – VI. |
| 9 | Lumpsum price worked out by the contractor for “RAIN WATER HARVESTING” as listed in Schedule ‘A’ Part – VII |
| 10 | Lumpsum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part –VIII |
| 11 | Lumpsum price worked out by the contractor for “EXTERNAL ELECTRIC SUPPLY AND RECTIFIER POWER SUPPLY” as listed in Schedule ‘A’ Part – IX |
| 12 | Lumpsum price worked out by the contractor for “LIGHTING ARRESTOR/PROTECTION” as listed in Schedule ‘A’ Part –X |
| 13 | Lumpsum price worked out by the contractor for “FIRE HYDRANT SYSTEM AND FIRE ALARAM” as listed in Schedule ‘A’ Part – XI |
| 14 | Lumpsum price worked out by the contractor for “AC PLANT/AIR CONDITIONING AND REFRIGERATION” as listed in Schedule ‘A’ Part – XII |
| 15 | Sch 'A' Part - :XIII \\"BLDG INCLUDING INTERNAL SERVICES\\" Design and Construction of Avionics engineering complex building in Single storey with permanent specification in RCC M-30 framed structure with ACC Block masonry including ATT, Pu based WPT etc complete all as specified and as shown on drawings |
| 16 | Design and Construction of pump house for avionics engineering complex in single storey with permanent specification in RCC M-30 framed structure ACC Block masonry including ATT,Pu based WPT etc complete all as specified and as shown on drawings |
| 17 | Design and Construction of covered shed 3m height with steel tubular trusses, pre painted high tensile steel galvalurme sheet of aluminium zinc alloy 0.6mm total coated thickness (refer design parameter) with necessary civil works complete all as specified and as shown on drawings |
| 18 | Sch 'A' Part - :XIV FITTING AND FIXTURES AND MISSLANIOUS ITEMS FIRE FIGHTING UG SUMP :- Supply and fix DI pipes 150mm dia with spigot and socket ends, vertically cast, class A, in any length complete all as specified and as directed |
| 19 | Supply and fix for Bends (any radius), diminishing pieces or tapers (larger bore measured) for 150mm dia complete all as specified and as directed |
| 20 | Material and labour for 75 mm thick PCC 1:3:6 type C-1 (using 20mm graded mechanically crushed stone aggregate ) for plinth protection ,finished even and smooth without using extra cement ,including necessary constructions joint filled with seailing compound complete all as specified and as directed |
| 21 | Material and labour for rubburised water bars, 300mm wide complete all as specified and as directed |
| 22 | Material and labour for FBEC coating for reinfocement bars complete all as specified and as directed |
| 23 | \\" INTERNAL ELECTRIFICATION\\" Supply and fix Hot dip Galvanized tray of size 150mm x50mm x 1.2 mm thick with cover tray,bracket and accerssories in floor / wall complete all as specified and as directed. |
| 24 | Supply and fix security light fitting LED luminares New generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP65 roadway luminaire with high power LED as light source with 35W LED 5000K lamp including connecting into electric circuit and testing complete all as specified and as directed. . |
| 25 | Material and labour for GI Bracket bend to shape in cold or hot 40mm bore medium grade and 1.50 M long with suitable MS clamps and nuts bolts etc, for fixing security light fittings to Bldgs complete all as specified and as directed. |
| 26 | Supply and fixing flood light fittings LED luminares New generation energy saving & environmental friendly long life versatile pressure die-cast aluminium IP65 roadway luminaire with high power LED as light source with 150W LED 5000K lamp including connecting into electric circuit and testing complete all as specified and as directed. . |
| 27 | Supply and fixing for MCB SP 06 to 32 Amps, 10KA 240 volts,50Hz complete all as specified and as directed. |
| 28 | Supply and fixing for MCB SPN 0- 40 Amps, 10KA 240 volts,50Hz complete all as specified and as directed. |
| 29 | Supply and fix Air Circulator fans 230 volts single phase oscillating 450 mm sweep suitable for wall mounting 3 star type energy saving including fixing arrangements complete all as specified and as directed. |
| 30 | Material and labour for providing maintenance free earthing with earth electrode of 50mm dia, 1.8mm thick ,3 mtr long, pure copper pipe, strips in pipe system fitted with pure copper strip 40X 6 mm from top to bottom, terminal hole of 12mm, pipe filled with conductive crystaline compound including 02 bags of earth life compound (25kgs each) as per IS 3043. Environmental test (salt mist test ), Bend test,Tensile strength , yeild /ratio ,electical resistivity test,complete with clamps, maintenence free,anti corrosive lead-free ,super conductive ,mineral based high grade earthing compound,to enhance soil conductivity.with resistence less than 0.5 ohms-meters, should be leak proof and sulphur free complete with earth inspection champer of dimension :width :320mm x 320mm , Height : 192 mm Weight :30 kgs, Including drilling of bore in any kind of soil complete all as specified and as directed. Note : The rate quoted is deemed to inclusive of soil resistance test, as per soil resistance test no of earth pits to be decide i) Earth resitance value shall be less than 0.5 ohmsii) Copper strip 2 x 3 mm for interconnection of earth pit (Brazing and copper bolt and nuts) shall be paid separtely under relavent item. |
| 31 | Supply and fixingTelephone / AF Net socket RJ 1, one module with shutter modular type complete all as specified and as directed. |
| 32 | Sypply and fixing electrical operated heavy duty automatic stainless steel body Hand Dryer 400/500W complete all as specified and as directed. |
| 33 | FOR FLAME PROOF AREA Supply and fixing Flame proof - weather proof switch socket & plug combined 25 A, 500 V(3P+Earth) complete all as specified and as directed. |
| 34 | Supply and fixing flame proof - weather proof fan regulator suitable for 1200/.1400mm sweep ceiling fans complete all as specified and as directed. |
| 35 | Supply and fixing flame proof type ceiling fans 1200 mm sweep, 230 V AC 50 HZ complete with down rod complete all as specified and as directed. |
| 36 | Supply and fixing flame proof type wall mounting fans AC single phase 230/ 240 V of size 450 mm sweep with mounting arangements complete all as specified and as directed. |
| 37 | Supply and fixing Stove enamelled steel conduit of size 25mm exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks complete all as specified and as directed |
| 38 | Supply and fix of GI Metal boxes 16guages 2/3 modules complete all as specified and as directed |
| 39 | Supply and fix of Information / AF Net socket one module (modular type) complete all as specified and as directed |
| 40 | SEWAGE DISPOSAL : Material and labour for 150 ID/ 172 OD mm dia DWCPE SN-4 pipes single socked in length with joints in trenches or in floors complete all as specified and as directed |
| 41 | EXTERNAL WATER SUPPLY :Material and labour for cutting of existing 150/100mm CI /DI pipe line and taking of 80 mm dia branch connection and including inserting Tee of suitable size to connect existing pipe line (except CI/DI specials) complete all as specified and as directed. |
| 42 | Material and labour for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed. |
| 43 | Material and labour for Construction of brick masonary valve chamber of size 900 x 900 x900 mm (internal dimensions) with PCC 1:4:8 foundation 150mm thick masonary built in CM 1:6 PCC 1:3:6 type C1 using 20mm graded stone aggregate coping mm thick plastering mm thick in CM1 :6 to all internal and exposed surfaces including excavation and earth work in hard /dense soil including provision of MS sheet cover 3mm thick with locking arragement embedded in PCC coping and painting with coats of synthetic enamal paint over one coat of red oxide primer etc complete all as specified and as directed . |
| 44 | EXTERNAL ELECTRIC SUPPLY/RECTIFIER POWER SUPPLY:Material and labour for LT UG cable route indicator duly painted with red colour synthetic enamel paint two coats over one coat of red oxide primer oval shape of size 10cm x 10cm x 5mm thick CI/GI plate with inscription there on , bolted/ welded to 35 mm x 35mm x 6 mm MS angle iron, 60 cm long including necessary PCC in 1:3 :6 typr C1 cement concrete 20mm aggregate all around below ground level 650mm x 300mm x 250mm embedded in PCC block complete all as specified and as directed. |
| 45 | Material and labour for DWC HDPE pipe of size 90/76 mm bore (OD X ID) for LT UG cable protection complete all as specified and as directed. |
| 46 | Material and labour for DWC HDPE pipe of size 110 mm bore (OD) for LT UG cable protection complete all as specified and as directed. |
| 47 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed. |
| 48 | Supply, install, testing & commissioning of factory made indoor LT Panel board of sutiable size for 3 phase 415 volt of both side opening double door with push type metal lock, heavy duty wide hinges, seperate common across cable aley, made out of 2 mm CRCA sheet with angle iron frame of size (50 x50 x 6 mm) and MC channel of size (75mm x 40mm) for panel base out door type , free standing cubical type totally enclosed weather dust and vermin proof with front and rear opening with locking arrangment of 440 Volts , 3 Phase 4 wire 50 Hz having Copper Bus bar of capacity 600 Amps duly insulated with IP 54 protection,with powder coating including PCC foundation complete with following switches, space for 1 No vacant cubical suitable for 250 A, including LT XLPE cable end terminations with glands and lugs: |
| 49 | Incoming:- (i) MCCB 4P ,400 A, 25KA adjustable type , 415 volts rating.- 1No . ( ii) On load change over switch 125 A 01 No iii) Multifunction LED meter complete with CT coil including set of indicating lamp RYB -1 set Bus - Bar 600 Amps capacity copper bus bar with sleeves. -4 Nos Outgoing :- (i) MCCB, 4 pole 200 Amps 25 KA ( Adjustable thermal & adjustable magnetic setting (For AC panel & Spare) - 02 No (ii) MCCB, 4 pole 40 Amps 16/25 KA( Out going + Lighting DBs ) -04 Nos (iii) Isolator TPN 40A - 5 Nos (UPS in) |
| 50 | Material and labour for earthing complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI earth strip of size 25 x 4 by means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt I. The work is inclusive of necessary earth work and PCC chamber in type CI (1:2:4) with 8 TMT bar reinforcement both ways at 140 mm centre to centre complete all as specified and as directed. Note:- GI earth lead beyond 7.5M shall be measured and paid separately |
| 51 | RECTIFIER POWER SUPPLY : Material and labour for copper cable single core standard, sheathed with heavy duty insulation un armoured for rectifier out put 28V DC 200 Amps connect with air craft male connector carrying capacity size 120Sq mm complete all as specified and as directed |
| 52 | Supply and fix female connector rating 2P+E heavy duty suitable for 28V DC 200AMps male connector of Air craft complete all as specified and as directed |
| 53 | Material and labour for installation testing and commissioning of 28 Volts 200 Amps DC Rectifier, copper wound, Indoor type, with first filling of transformer oil complete with the following protection.1) Input over/under voltage2) Phase fail/Reversal3) Output DC overload/short circuit4) output DC over voltage5) Over heat stop start features6) High speed fuses for power devices7) Snubber circuits for power devices. Indications: 1) Main ON 2) DC ON 3) Phase fails (4) Mains over/under voltage (5) DC over/under voltage (6) DC overload (7) Overheat. ENCLOSURE/COOLING: IP20 with forced air cooling |
| 54 | FIRE HYDRANT SYSTEM : Supply, install, test & commissioning of factory made Automatic motor control centre for 60 HP Hydrant / Jockey control LT Pannel board made out of CRCA sheet of 2mm thick ,indoor cubical type totally enclosed weather dust and vermin proof with front and rear opening 433Volts , 3 phase 4wire AC 50 cycles, having bus bar capacity of 400 Amps with aluminium bus bar RYB insulated with sleeved insulators complete with volmeter, ammeter with selector switches indicating lamps internal wiring with CT' s for measuring including grey colour powder coat painting all as specified. with and including the following controls complete all as directed.. |
| 55 | Incoming :- (i )MCCB, four pole, 25 KA ( adjustable ), 415 volts 250 Amps rating.- 1 No . (ii.)RYB LED indicating lamps with MCB. (iii) Digital Ammeter 0 - 400 Amps with selector switch and suitable rated current transformer - I No (iv) Digital voltmeter 0 - 500v with selector switch (v )Phase squence corrector - 1 No |
| 56 | Outgoing : (i) Feeder for Pump house lighting - 1No ii MCCB, four pole, 16 KA ( adjustable ), 415 volts 200 Amps rating.- 1No. iii Star delta starter with Auto and manual switch, over load relays, single phase preventor and indicating lamps ON / OFF push buttons complete. iv Automated selector switch - 1 No v Digital Ammeter 400Amps with selector switch and suitable rated current transformer - I No DIESEL ENGINE MAIN PUMP -1 No a) MCB, DP MCB - 2 No s b) Battery charger with transformer with rectifier resistance DC ammeter, DC voltmeter, Trickle / booster / off selector switch - 2 Nos c) Indicating lamps for the following: 1. Phase indication 2.Battery charger on 3.Over load relay 4.DC supply ON 5. Control switch ON 6. Fault communication 7. Engine fails to start 8. Pump ON 9. Low oil pressure 10.High water temprature 11. Auto manual selector switch |
| 57 | (d) Push button stations for the following: 1.Jockey pump start. 2. Jockey pump stop 3. Engine Start 4. Engine Stop 5. Engine - hooter ACK (e) Selector switches (Engine control, mode selector )- 1 No (f) Auxilary relays / contractors / timer for sequence operating for starting and stopping of the engine - 1 Set (g) Hooter for audio alarm ( industrial type) - 1No |
| 58 | Supply and fixing air release valve with two air out lets 50 mm dia bore and fixing up to ERW pipe main with suitable flanges and bolt , nuts. complete all as specified and as directed. |
| 59 | Supply and fixing Yard hydrant box made out of 18 gauge thick MS sheet of size 800 mm x 600mm x 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted with two coats of synetic enamel fire red paint out side and briliant white paint inside over a coat of red oxide primer and installed over PCC block with suitable length of 100mm dia GI pipe with and including the following : |
| 60 | (a) 63mm dia instantaneous Iinlet, made threaded out let Gun metal branch pipe , 15mm bore nozzle long -1 No (b) 63 mm hydrant valve heavy duty with cap and chain - 1 No (c) 30 mtr long 63mm dia rubber lined hose reel conforming to IS:884:1985 mounted on spool with brass shut off valve with coupling branch pipe and nozzle - 1 No (d) 63mm dia rubber lined canvas hose pipe conforming to IS 636 of 30m length with male and female coupling conforming to IS 903 -1No (e) 63mm dia rubber lined canvas hose pipe conforming to IS 636 of 7.5 mtr length with branch pipe and coupling -2 Nos Note : The rate excluding the cost of PCC block. |
| 61 | Supply and fixing Air cushioning tank (Air vessel) 250mm dia x 1000mm high with dished top, made of minimum 6mm thick MS pipe /plate complete with 20mm dia Brass air valve (ball type) 20mm dia stop valve pressure gauge with brass stop cock nipple tees elbows and all accessories complete all as specified and as directed. |
| 62 | Material and labour for Boring of holes under road /standing by trenchless technology using ultra sound technic and necessary machine for insertion of MS pipe of up to 200mm inner dia and 0.6 MPA working pressure complete all as specified and as directed. |
| 63 | Material and labour for LT UG cable route indicator duly painted with red colour synthetic enamel paint two coats over one coat of red oxide primer oval shape of size 10cm x 10cm x 5mm thick CI/GI plate with inscription there on , bolted/ welded to 35 mm x 35mm x 6 mm MS angle iron, 60 cm long including necessary PCC in 1:3 :6 typr C1 cement concrete 20mm aggregate all around below ground level 650mm x 300mm x 250mm embedded in PCC block complete all as specified and as directed |
| 64 | AC PLANT : Design, Supply, installation, testing & commissioning 36 HP outdoor unit with cooling of Variable Refrigerant Flow (VRF) system with multi indoor unit with outdoor units including individual controller for cooling type operation. Outdoor units equipped with highly efficient twin rotary compressors with inverter type compressor, special acryl precoated heat exchanger, low noise condenser fan, auto check function for connection error, having interconnected control wiring between indoor unit, outdoor unit & control panel and refrigerant piping housed in compact housing duly powder coated complete as required for trouble free operation, refrigerant should be R-410a complete all as specified and as directed.Note:- (i) 03 No's (i.e 3X36HP= 108HP - Overall Capacity)(ii) The number of units may vary subject to the oveall capacity of the plant |
| 65 | Indoor unit shall have the following :- (1). Indoor cassette unit of 2.5TR-06 Nos , 4 way equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outdoor cabinet, drain pan and drain pump, cordless remote, cabling, vibration isolation, earthing, necessary supports etc as per specifications complete all as specified and directed.(2). Indoor cassette unit not less than 4.0TR-05 Nos , 4 way equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outdoor cabinet, drain pan and drain pump, cordless remote, cabling, vibration isolation, earthing, necessary supports etc as per specifications complete all as specified and directed.(3) Indoor cassette unit not less than 14.0TR-03 Nos , 4 way equipped with pre-filter, fan section with low noise fan, multispeed motor, coil section with DX coil, outdoor cabinet, drain pan and drain pump, cordless remote, cabling, vibration isolation, earthing, necessary supports etc as per specifications complete all as specified and directed. |
| 66 | Note for Indoor units(a) Multi Level Filtration: Aesthetically superior with stylish design, very low noise, quiet operation, wide angle air flow to ensure even air distribution throughout the condition space.(b) Multi Speed fan: Various level of fan speed control are mus available for users comport and convenience.(c) Auto-Restart: Automatic re-start after power cut with all previous set parameters are restored.(d) Multimode functions: Various mode can be selected depending on the usage pattern and the comfort levels required. AUTO, COOL, DRY, SLEEP.(e) Flexible air flow patterns: Advanced louvers where swing can be adjusted to meet the needs air flow ventilation and direction required.(f) Cordless Remote Controller: Cordless remote controller having large LCD screen for better clarity, real time clock display, room temperature indication, displays of various mode-cool, fan, dry. Fan speed adjustable, inside room temperature adjustable from 16 degree to 30 degree centigrade.-16Nos |
| 67 | General Note:- (i) The size of the plant may be calculated after knowing the equipment load and number of persons present in the room(ii) However thr overall capacity not to exceed 86TR (108 HP)(iii) The contractor has to submit the detailed design for approval of accepting officer through proper channel(iv) The contractor has to get vetted from the IIT/NIT before forwarding to the approval of accepting officer |
| 68 | Outdoor unit:-(i) 03 No's (i.e 3X36HP= 108HP - Overall Capacity)Note for Out door unit:(i) Highly efficient Inverter Compressors: The unique design of the inverter compressor ensures that the refrigerant is directly injected in to the compressor chamber. The suction gas enters directly into the scroll, there is no super heat gain due to compressor motor assembly, this results in efficiency enhancement by upto 3%. (ii) VRF units are fitted with 100% inverter compressors. The unique logic of the system is that it optimally loads compressors in such a way that maximum efficiencies are achieved under any load condition. (iii) High COP and IPLV (Integrated Part Load Value).(iv) 100% capacity at 43 degree centigrade.(v) Non-stop operation even at 56 degree centigrade.(vi) Wide Operating Range: The system can operate from 10 degree centigrade to 56 degree centigrade in the cooling mode.(vii) Superior Accumulator Design: The VRF system is designed with the largest twin Accumulator in its class. This new design allows the system to perform seamlessly in low-load condition even below 30% without tripping. |
| 69 | (viii) Weather Proof Outdoor Unit Design: Outdoor unit is specifically designed to handle extreme climatic conditions, corrosion and polluted atmosphere.* Powder coated GI sheet metal cabinets.* All hardware of anti-rust quality.* Conformal coating on PCBs to protect from dust and humidity.* Hydrophilic blue fin for better corrosion resistance.* Weather-proof enclosures for critical components.* Emergency Backup Operation, the compressor backup in outdoor units that have two compressors, the VRF system can function or maintenance down time of one compressor. * Demand Control Mode or Economy Mode the capacity of the ODUs of the VRF can be set at 25%, 50% & 75% depending on the need.(ix) The system designed to operate across a wide voltage range from 320 volts to 460 volts resulting in high uptime even in erratic power conditions. |
| 70 | Supply and Installation of Refnet joints (Refrigerant branch kit) for taking branches between various indoors as per VRF scheme drawings. The refnet joint set consists of both liquid and gas line branch kits. Indoor - 16 NosOutdoor - 03 Nos VRF Central Controller - Supply, Installation, testing and commissioning of BMS compatible Network Interface and Central Remote Controller for monitoring and Controlling the VRF equipments in third party BMS as required basis. VRF LOW SIDE WORKS Installation , Testing, Commissioning and Handing over the VRF outdoor units -36.0 HP TOP DISCHARGE VRF ODU - 03 Nos Installation , Testing, Commissioning and Handing over of the following VRF Indoor Units : Cassette Unit.- 16 Nos |
| 71 | REFRIGERANT PIPING : Supply, Installation and Testing of Refrigerant piping, fittings and Y Branch with suitable thick tubular nitrile rubber insulation finished with laminated glass cloth.Suction line thickness - 19 mm and Liquid Line Thickness - 13 mm. All the tools and tackles required to install the refrigerant piping will have to be arranged by the vendor only without dependency on the client.Complete piping workmanship to be carried out as per recommended practice with the pipe sizes 1/4\\" to 1 5/8\\" of length 400RM ( Aprox)Nitrogen Pressure Testing at site complete as required and as direcrted. Nitrogen Pressure Testing at site complete as required and as direcrted Supply and First Charging of R-410 additional refrigerant gas complete as required and as direcrted. Supply and installation of communication cable carried out with 2 core x 1.5 sqmm shielded cable including PVC conduit, between indoor unit to outdoor unit complete all as required and directed - 450RM (Approx) VRF pipe protection finish for the exposed pipes (Suction & Liquid) : supply and application of one coat of Weatherprotekt coating, fixing 10 mil woven glass cloth, again one coat of Weatherprotekt coating and when finally dry complete with final coat of Weatherprotekt Coating complete all as required and directed - 350RM (Approx). Towards Charges for Anti Vibration Rubber Pads complete all as required and directed - 04 Nos (Approx) |
| 72 | DRAIN PIPING : Supply, Installation and Testing of PVC heavy class drain piping insulated out of 9 mm thick Class O closed cell elastomeric nitrile rubber material finished with laminated glass cloth of approved make as per specification complete with supports, consumables, fittings, pipe sleeves, U trap & leak arresting of following sizes. Size 25 mm dia - 200RM . Size 32 mm dia - 150RM. Size 40 mm dia - 100RMCABLE TRAYS :Supply and erection of following sizes Hot Dip Galvanized perforated type 16G thick cable tray made out of sheet steel folded to required shape with adequate number of supports for Insulated refrigerant pipe and cable conduits - 300 mm width x 50 mm height (as required sizes) - 400RM ( Approx) Inland transportation to site, Lifting and placing at the designated space complete all as specified and directed - 01 JobFABRICATED STEEL WORK :Supply, Fabrication , Cutting, Welding , Erection at site and painting of M. S. Angle structural steel work for outdoor unit location etc based on the approved drawings. The work should be carried out as per good manufacturing and installation practices in concurrence with approved drawing. Finally all steel work to be painted with one coat of zinc chromate primer and two coats of synthetic enamel paint complete all as required sizes / shapes - 700Kgs (Approx) |
| 73 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 0.5 KVA complete all as specified and as directed. |
| 74 | AIR CUTAIN : Supply, install, commissioning and testing of commercial Air curtain unit for prevention of dust and conditioned air losses, single phase, 220 V, 50 HZ, made out of MS/CRCA sheet of minimum thickness 18 gauge finished with two coats of red oxide primer and final coat of synthetic enamel paint (oven baked) with MS CRC 18 gauge square perforated suction grills, Aluminium alloy fans and single phase electric motor, nozzles etc, complete with fittings and accessories so as to produce 1 - 1.5 m/sec air velocity at floor level for door opening as specified door size 46\\" x 78\\" complete all as specified and as directed. |
| 75 | All as per Sl item No 59 herein before but door size 70\\" x 78\\" complete all as specified and a directed. |
| 76 | Supply, fix and testing of air curtain door sensor with motion sensor switch complete all as specified and as directed. |
| 77 | UPS Supply : Material and labour for supply, install, testing and commissioning of UPS for 30 min back up three phase AC input 300 to 450V and out put 415 V ± 1% of capacity 20 KVA, IGBT True on line with batteries with battery stand and inter connecting cables complete all as specified and directed . |
| 78 | Material and labour for supply, install, testing and commissioning of UPS for 30 min back up three phase AC input 300 to 450V and out put 415 V ± 1% of capacity 10 KVA, IGBT True on line with batteries with battery stand and inter connecting cables complete all as specified and directed . |
| 79 | Air Purifier :Supply, installation and commissioning of air purifier with space tech air purification technology with TOP2 module destroys bacteria, fungal spores, micro biological impurities, alergens etc & integrated H14 HEPA filter for cover area 50sq mtr complete all as specified and as dircted |
| 80 | STAND BY D G SET :-Supply, installation , testing and commisioning of Diesel Engine CPCB4 approved 100 KVA TP inbuilt with AMP panel generating 107 HP @ 1500 RPM , dirrectcoupled with 100 KVA three phase 415 Volts CG/LS Alternator and all accessories in housed in a acoustic enclosuresound proof canopy including necessary connection complete all as specified and directed |
| 81 | DIESEL ENGINE : Liquid cooled, electric start four stroke, six cylinder totally inclosed diesel engine developing 107HP at 1500 RPM at NTP. The engine is suitable for generating set application and fitted with the following standard accessories. Flywheel to suit coupling, suitable coupling, water cooling arragment,Radiator, Lub Oil Filter, Lube Oil Pump,Fuel Pump, Hose to fuel pump, Air cleaning assembly,Residential Heavy duty silencer, Engine fitted with low lube oil presure gauges.Engine monitoring, protection and diagnostics.(i) Lube oil pressure. (ii) Coolant Temperature. (iii) Engine Speed. (iv) Hours Run. (v) Battery voltage. (vi) Common Warning. (vii) Common shut down. (viii) High coolant temperature warining and shutdown. (ix) Low lube oil pressure warning and shut down(x) Low coolant level shutdown. (xi) Over speed shutdown. (xii) Charging failure indication. (xiii) AC metering and alternator protection.(xvii) Power factor. (xviii) Frequency. (xix) Over voltage. (xx) Under voltage. Please Enable Macros to View BoQ information |
| 82 | DIESEL ENGINE : Liquid cooled, electric start four stroke, six cylinder totally inclosed diesel engine developing 107HP at 1500 RPM at NTP. The engine is suitable for generating set application and fitted with the following standard accessories. Flywheel to suit coupling, suitable coupling, water cooling arragment,Radiator, Lub Oil Filter, Lube Oil Pump,Fuel Pump, Hose to fuel pump, Air cleaning assembly,Residential Heavy duty silencer, Engine fitted with low lube oil presure gauges.Engine monitoring, protection and diagnostics.(i) Lube oil pressure. (ii) Coolant Temperature. (iii) Engine Speed. (iv) Hours Run. (v) Battery voltage. (vi) Common Warning. (vii) Common shut down. (viii) High coolant temperature warining and shutdown. (ix) Low lube oil pressure warning and shut down(x) Low coolant level shutdown. (xi) Over speed shutdown. (xii) Charging failure indication. (xiii) AC metering and alternator protection.(xvii) Power factor. (xviii) Frequency. (xix) Over voltage. (xx) Under voltage. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 07, 2026
11:30 IST
Tender Published
Tender notice published.
Completed
Jul 28, 2026
18:00 IST
Corrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 16 daysJul 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysAug 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender