| 1 | Schedule 'A' |
| 2 | Supply, laying and fix in repair/replcement of LT Cable laid in trenches, passing through pipes and fixed on wall/floor/ceiling with proper saddles , including testing of XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size |
| 3 | 240 sqmm 3.5 core |
| 4 | 120 sqmm 3.5 core |
| 5 | 95 sqmm 3.5 core |
| 6 | 70 Sqmm 3.5 core |
| 7 | 50 Sqmm 3.5 core |
| 8 | 16 Sqmm 4 core |
| 9 | S& F in replacement of laying of Double Walled Corrugated (DWC) HDPE pipe of following size of conforming to IS 16205 Part -24 including necessary bends,coupling ,tees, reducers, spacers,end caps, rubber rings etc having pressure rating not less than 450 N through trenches/wall/floor/on pole in any type of soil for protection of electric cable complete all as directed by Engr-In Charge Make:-ASTRAL TELEREX /eqivalent as approved by GE |
| 10 | 40/32 mm outer/inner dia |
| 11 | 50/38 mm outer/inner dia |
| 12 | 63/50 mm outer/inner dia |
| 13 | 90/75 mm outer/inner dia |
| 14 | Excavation in trenches in hard /dense soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC poles/stays and struts etc and getting out including trimming sides and forming bottom surface all as specified and directed at site. |
| 15 | Returning, filling in including spreading, leveling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested, poles, stays , struts have been erected and tested , all as specified and directed at site |
| 16 | Removing excavated surplus soil (Soft/hard soil) obtained from excavation to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed. |
| 17 | Supply & JOINT cable jointing kitheat shrinkable 1.1KV XPLE straight through joint of size 16 sqmm 3.5 core to 50 sqmm 3.5 core cable size complete. Make:-Denson/3M/Raychem |
| 18 | Supply & JOINT cable jointing kit heat shrinkable 1.1KV XPLE straight through joint of size 70 to 120 sqmm 3.5 core cable size complete. Make:-Denson/3M/Raychem |
| 19 | Supply & JOINT cable jointing kit heat shrinkable 1.1KV XPLE straight through joint of size 240 sqmm 3.5 core cable size complete. Make:-Denson/3M/Raychem |
| 20 | Supply , install, Design testing and commissioning in replacement of CPRI approved factory made and tested outdoor type floor mounted LT panel board, cubical type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with air insulated PVC sleeved Copper bus bar of rating 600 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 3.15 mm CRCA MS sheet with projected globe roof for rain water protection Dust & Vermin proof, including Neoprene rubber gasket, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and 50 X 50 X 6 mm thick MS angle iron frame 60 cm above and 60 cm below normal ground level work front & back opening double door type of adequate size for housing LT switchgear and measuring instruments duly powder coated after seven tank process on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size but not less than 4.0 sq mm, cable lugs,MCCB Spreaders links, cable glands and PCC foundation in cement concrete 1:3:6 (20 mm graded stone aggregate, testing after installation including complete all as specified & directed and comprising of followings:- |
| 21 | (A) Incoming:- (a) Copper bus bar Four Pole 600 Amps - 01 Set (b) Voltmeter 3 phase class .5 -01 Nos (c) Ammeter 3 phase class1 -01 Nos (d) Phase indicating lamp R, Y, B LED - 01 Set (e) CT 100X5 - 3 Nos (f) MCCB 400 A 4P 25 kA with thermal magnetic release -01 Nos (g) Danger notice plate/ sticker of suitable size on front panel board -01 No (B) Outgoing:-(a) MCCB 200 A 4P 25 kA with thermal magnetic release -04 Nos (b) MCCB 160 A 4P 25 kA with thermal magnetic release -04 Nos(c) All out going LT feeders name with radium stickers -09 Nos Note:- MCCB Make:- Legrand(DPX series)/L&T(d-sine series) /Schenider. (d) All MCCB to be connected through busbar only, no pvc wire is allowed |
| 22 | Supply and fixing in replacement of ON load change over switch with sheet steel Enclosure 415 V, 4 pole, 400 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed. Make : L&T/ C&S/ Havells |
| 23 | Supply , install, Design testing and commissioning in replacement of CPRI approved factory made and tested outdoor type LT panel board, cubical type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with air insulated PVC sleeved Copper bus bar of rating 400 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 3.15 mm CRCA MS sheet with projected globe roof for rain water protection Dust & Vermin proof, including Neoprene rubber gasket, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and 50 X 50 X 6 mm thick MS angle iron frame 60 cm above and 60 cm below normal ground level work front & back opening double door type of adequate size for housing LT switchgear and measuring instruments duly powder coated after seven tank process on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size but not less than 4.0 sq mm, cable lugs,MCCB Spreaders links, cable glands and PCC foundation in cement concrete 1:3:6 (20 mm graded stone aggregate, testing after installation including complete all as specified & directed and comprising of followings:- |
| 24 | (A) Incoming:- (a) Copper bus bar TPN 400 Amps - 01 Set (b) Voltmeter 3 phase class .5 (L &T Model No-WL131020OOOO ) -01 Nos (c) Ammeter 3 phase class1 (L &T Model No-WL132020OOOO ) -01 Nos (d) Phase indicating lamp R, Y, B LED (L &T Model No-EPL R/Y/B/240VAC ) - 01 Set (e) CT of suitable ratio (f) Danger notice plate/ sticker of suitable size on front panel board -01 No (g) Incoming MCCB 250A 4P 36 kA -01 No (B) Outgoing:- (a) MCCB 125 A 4P 25 KA -02 No (b) MCCB 63 A 4P 25 KA -2 Nos (c) All out going LT feeders name with radium stickers. Note:- MCCB Make:- Legrand/L&T (d-sine series) /Schenider Note: All MCCBs to be connected through busbar only. |
| 25 | Supply , install, Design testing and commissioning in replacement of CPRI approved factory made and tested outdoor type floor mounted LT panel board, cubical type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with air insulated PVC sleeved Copper bus bar of rating 400 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 3.15 mm CRCA MS sheet with projected globe roof for rain water protection Dust & Vermin proof, including Neoprene rubber gasket, Bottom detachable Gland Plate comp-lete with suitable size Zinc Chromium Plated Nuts, Bolts and Washers, etc. and 50 X 50 X 6 mm thick MS angle iron frame 60 cm above and 60 cm below normal ground level work front & back opening double door type of adequate size for housing LT switchgear and measuring instruments duly powder coated after seven tank process on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size but not less than 4.0 sq mm, cable lugs,MCCB Spreaders links, cable glands and PCC foundation in cement concrete 1:3:6 (20 mm graded stone aggregate, testing after installation including complete all as specified & directed and comprising of followings:- |
| 26 | (A) Incoming:- (a) Copper bus bar Four Pole 400 Amps - 01 Set (b) Voltmeter 3 phase class .5 -01 Nos (c) Ammeter 3 phase class1 -01 Nos (d) Phase indicating lamp R, Y, B LED - 01 Set (e) CT 100X5 - 3 Nos (f) MCCB 250 A 4P 25 kA with thermal magnetic release -01 Nos (g) Danger notice plate/ sticker of suitable size on front panel board -01 No (B) Outgoing:-(a) MCCB 63 A 4P 16 kA with thermal magnetic release -02 Nos (b) MCCB 100 A 4P 16 kA with thermal magnetic release -05 Nos(c) All out going LT feeders name with radium stickers -08 Nos Note:- MCCB Make:- Legrand(DPX series)/L&T(d-sine series) /Schenider. (d) All MCCB to be connected through busbar only, no pvc wire is allowed |
| 27 | Supply & installation in replacement of Chemical Earthing Jef Ecosafe Maintenance free and Environment Friendly Earth Electrode set comprising of 17.2mm dia 3 mtrs long rod of Low carbon steel, molecular Copper Bonded for a thickness of 250 microns, highly conductive ANSI NSF STD 60 Certified, with 1Bags(50P) of environment friendly carbon based backfill compound, according to BS 7430 & IEEE 80 and with suitable Clamp in 100mm dia bore hole complete all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |