| 1 | Supplying, installation , testing and commissioning of Air cooled ductable type Packaged air-conditioning units complete with Hermetically sealed Scroll compressors fitted inside the indoor unit & first charge of refrigerant R410A or equilant permitted green refrigerant & oil ,air cooled condenser, fan section with statically/dynamically balanced centrifugal blower driven by a Totally Enclosed Fan Cooled (TEFC) squirrel cage three speed motor, Multi rows cooling coil of copper with aluminium fins etc. The enclosures shall be fabricated of M.S. The Package unit shall be equipped with synthetic fiber filter, insulated drain pan, controls all encased in a unit. The casing shall be factory powder coated. Electrical panel board for Package units shall comprise of control and power panel with including all associries i/c Voltage scanner, overload, low voltage, high voltage & phase imbalance protection, along with VI Pads complete with all ancillaries including MS painted stand for Outdoor units of suitable size, foundation and allied minor civil works as per instructions of Engineer-in-charge of following ratings including electric control panel & fitting as per CPWD specifications and as per IS: 8148 complete as required. |
| 2 | 8.0 TR (2.8 EER) |
| 3 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 4 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 5 | Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
| 6 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm |
| 7 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm |
| 8 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 9 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 10 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 11 | Single pole |
| 12 | Triple pole and neutra |
| 13 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 14 | Supplying and Laying of 6C X 2.5 sq mm Single Core & Multicore Flexible Cable 1100V PVC insulated & Sheathed with Bare Annealed Copper Conductor etc complete as reqd at site. |
| 15 | Providing and making of Iron Angle Frame (Angle Bar Size: 40mmX40mmX5mm) of height not less than 500 MM size of 1DU as suitable etc complete a req at site. |
| 16 | Credit of dismantled items from above work |
| 17 | Ductable/Package AC units complete Set (Indoor & outdoor units) of assorted Capacity |
| 18 | All Acceseries as Copper pipe, Supports, Tray, Cables etc |
| 19 | SP MCB/DP MCB/Isolator (Assorted size ) Please Enable Macros to View BoQ information |