| 1 | Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying UG cable/steel tubing etc and getting out in soft/loose soil complete all as specified and directed. |
| 2 | Returning, filling in, including spreading levelling, watering and well ramming in layers not exc 25 cm thick with soil complete all as specified and directed. |
| 3 | Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed. |
| 4 | Taking up or down steel tubing and connections of size 25mm dia bore including cleaning for refixing or removal to store complete all as specified and directed. |
| 5 | All as per item No. 4 here in above but of size 32mm dia bore |
| 6 | All as per item No. 4 here in above but of size 40mm dia bore |
| 7 | All as per item No. 4 here in above but of size 50mm dia bore |
| 8 | All as per item No. 4 here in above but of size 80mm dia bore |
| 9 | All as per item No. 4 here in above but of size 100mm dia bore |
| 10 | All as per item No. 4 here in above but of size 150mm dia bore |
| 11 | Supply and laying and testing of medium grade galvanised iron steel tubing of size 25mm dia bore, ISI marked, including GI fittings such as unions, reducer sockets, socket reducing bends, elbows, tees, checknuts, caps, plugs etc complete laid in trenches/floors etc complete all as specified and directed. |
| 12 | All as per item No. 11 here in above but of size 32mm dia bore |
| 13 | All as per item No. 11 here in above but of size 40mm dia bore |
| 14 | All as per item No. 11 here in above but of size 50mm dia bore |
| 15 | All as per item No. 11 here in above but of size 80mm dia bore |
| 16 | All as per item No. 11 here in above but of size 100mm dia bore |
| 17 | All as per item No. 11 here in above but of size 150mm dia bore |
| 18 | Supply and mix alum conforming to IS complete all as specified and directed. |
| 19 | Supply,laying in replacement and testing of Ductile pipe of 100 mm dia double flanged,ISI marked, including rubber gasket not less than 3mm thickness, fittings such as reducing flanged bends,elbows,tees,checknuts & hexagonal nuts boits,caps,plugs etc complete laid in trenches/floors/supporting on pedestal etc all as specified and directed. |
| 20 | Supply and laying in replacement and testing of ductile iron of 150 mm K9 , including flange etc laid in ground or above ground level complete all as specified and directed. |
| 21 | Taking up or down CPVC pipe and connections of size 25mm dia bore complete all as specified and directed. |
| 22 | All as per item No. 21 here in above but of size 32mm dia bore |
| 23 | Supply and fix in replacement 3-layer CPVC concealed pipes SDR 11 and Plain CPVC SDR 11 for hot and cold water supply including all CPVC plain and brass threaded polypropylene random fittings fixed of size 25mm dia bore complete to walls,ceillings or in floors or in trenches complete all as specified and directed |
| 24 | All as per item No. 27 here in above but of size 32mm dia bore |
| 25 | Taking up or down UPVC(Unplasticised PVC)pipe and connections of size 25mm dia bore including cleaning for refixing or removal to store complete all as specified and directed. Note :Excavation and earth work shall be measured and paid separately |
| 26 | All as per item No. 25 here in above but of size 32mm dia bore |
| 27 | All as per item No. 25 here in above but of size 40 to 50mm dia bore |
| 28 | All as per item No. 25 here in above but of size 80mm dia bore |
| 29 | Supply and fix replacement 3-layer UPVC(ASTM) pipes of pressure rating 10 kgf/sqr cm having thermal stability including all UPVC plain and brass threaded polypropylene random fittings fixed for size 25mm dia bore complete to walls,ceillings or in floors complete all as specified and directed |
| 30 | All as per item No. 29 here in above but of size 32mm dia bore |
| 31 | All as per item No. 29 here in above but of size 40mm dia bore |
| 32 | All as per item No. 29 here in above but of size 50mm dia bore |
| 33 | All as per item No. 29 here in above but of size 80mm dia bore |
| 34 | Repairs/ servicing to sluice valve by taking out unserviceable spindle along with worn-out check nuts from the sluice valve of size 80mm dia bore of bore after removing the top cover and stuffing box of sluice valve spindle, and refixing with new spindle with check nut, gland packing, gasket, replacing of rusted unserviceable nuts/ bolts/ washers with SS with new nuts, bolts, gaskets etc for arresting all leakages/ smooth operation complete all as specified and directed.Note :- Spindle along with check nuts and nuts/ bolts shall be measured and paid separately. |
| 35 | All as per item No. 34 here in above but of size 100mm dia bore |
| 36 | M&L for Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, length of bolt exceeding 5 cm but not exceeding 10 cm and dia of neck 5 to 10mm complete all as specified and directed. |
| 37 | Taking up or down PP-R pipe and connections of 25mm sizes including cleaning for refixing or removal to store complete all as specified and directed.Note: Excavation and earth work shall be measured and paid separately |
| 38 | All as per item No. 37 here in above but of size 32mm dia bore |
| 39 | All as per item No. 37 here in above but of size 40mm dia bore |
| 40 | All as per item No. 37 here in above but of size 50mm dia bore |
| 41 | All as per item No. 37 here in above but of size 75mm dia bore |
| 42 | Supply and fix replacement 3-layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings fixed for 25mm bore sizes complete to walls, ceilings or in floors complete all as specified and directed |
| 43 | All as per item No. 42 here in above but of size 32mm dia bore |
| 44 | All as per item No. 42 here in above but of size 40mm dia bore |
| 45 | All as per item No. 42 here in above but of size 50mm dia bore |
| 46 | All as per item No. 42 here in above but of size 75mm dia bore |
| 47 | M & L for attending water supply break down by cutting and removing carefully damaged cast iron/ galvanised iron water pipe line of size 80mm dia bore without damaging other service lines and supply and fixing new cast iron/ GI pipe of length upto 1 to 5m and making joints with old pipelead joints/ welding works etc and pressure testing on completion of work and restoring the water supply complete all as specified and directed. Note:- Rates shall be deemed to be inclusive of Excavation welding & Jointing material such as unions bends etc before taking up the work. Excavation & earth work shall be also included in unit rate. |
| 48 | All as per item No. 47 here in above but of size 100mm to 150mm dia bore |
| 49 | S & F in replacement of Gun metal globe or gate valve with iron wheel head, screwed both ends for iron pipe of size 25mm dia bore and conforming to IS 778 of 1984 complete all as specified and directed. Make : Leader/Kirloskar/Zoloto |
| 50 | All as per item No. 49 here in above but of size 32mm dia bore |
| 51 | All as per item No. 49 here in above but of size 40mm dia bore |
| 52 | All as per item No. 49 here in above but of size 50mm dia bore |
| 53 | S & F in replacement of CI sluice valves of size 80mm dia bore, flanged, heavy duty, class PN 1.6, as per IS-14856 including brass spindle, with hand wheel, nuts bolts and gaskets complete all as specified and directed. Make Leader/Kirloskar/ Bir |
| 54 | All as per item No. 53 here in above but of size 100mm dia bore |
| 55 | All as per item No. 53 here in above but of size 150mm dia bore |
| 56 | All as per item No. 53 here in above but of size 200mm dia bore |
| 57 | S & F in replacement of Non return (Reflux) Valve, cast iron, of size 80mm dia bore, flanged, with GM working parts as per IS - 5312, with nuts bolts and gaskets complete all as specified and directed. Make Leader/Kirloskar/Normax |
| 58 | All as per item No. 57 here in above but of size 100mm dia bore |
| 59 | S & F in replacement of gun metal non return valve of 50 mm dia bore, screwed complete all as specified and directed.Make:leader/ Kirloskar/ zoloto |
| 60 | S & F in replacement of CI foot valve Ball type flanged end of size 50mm dia bore, flanged/as per IS - 4038 with nuts, bolts and gaskets etc complete all as specified and directed. Make Normax,/Kirloskar/ Leader |
| 61 | All as per item No. 60 here in above but of size 80mm dia bore |
| 62 | All as per item No. 60 here in above but of size 100mm dia bore |
| 63 | All as per item No. 60 here in above but of size 150mm dia bore |
| 64 | S & F in replacement of DOL starter suitable for induction motor of current rating 2 to 6 A, 3 Phase 415 Volts, 50 Hz AC complete all as specified and directed. Make: L&T/ siemens/Schineder |
| 65 | S & F in replacement of fully automatic Star Delta Starter suitable for induction motors of current rating 6 to 20 A, 3 Phase 415 Volts 50 Hz AC, with single phase protection complete all as specifified and directed. |
| 66 | All as per item No.65 here in above but current rating 18 to 28 A Make Type of ML 1.5F of L&T or M Contactor or equivalent in/Seimens/Schineder. |
| 67 | All as per item No.65 here in above but current rating 28 to 35 A Make Type of ML 1.5F of L&T or M Contactor or equivalent in/Seimens/Schineder. |
| 68 | All as per item No.65 here in above but current rating 35 to 75 A Make Type of ML 3F of L&T or M Contactor or equivalent in/Seimens/Schineder. |
| 69 | S & F in replacement of 3 pole power contactor, 415 V 50 Hz AC with 1 NO/1 NC auxiliary contact suitable for starters of contactor rating 18A of motor complete all as specified and directed. Make:L&T type MNX 18 or Equivalent in/Seimens/Schineder. |
| 70 | All as per item No. 69 here in above but contactor rating 25A Make :L&T type MNX 25 or Equivalent in /Seimens/Schineder. |
| 71 | All as per item No. 69 here in above but contactor rating 40A Make :L&T type MNX 40 or Equivalent in /Seimens/Schineder. |
| 72 | S & F in replacement of thermal over load relay of range 6 to 10 A complete all as specified and directed.Make L&T Type MN or equivalent in / Seimens/ Schineder |
| 73 | S & F in replacement of thermal over load relay of range 13 to 20 A complete all as specified and directed.Make L&T Type MN or equivalent in / Seimens/ Schineder |
| 74 | S & F in replacement of thermal over load relay of range 24 to 39 A complete all as specified and directed. Make L&T Type MN or equivalent in / Seimens/ Schineder |
| 75 | S & F in replacement of single phase preventer for 3 phase 415V AC power supply complete all as specified and directed. Make Minilac/ L&T / BCH |
| 76 | S & F in repairs thermostat suitable for 100 Ltr capacity solar water heater complete all as specified and directed. |
| 77 | Dismantling three phase 440 volts motors of 0.5 HP capacities, cutting and removing burnt motor winding, cleaning the slots and rewinding with approved quality super enamelled copper conductor winding wire of existing size and capacity including insulating materials, varnishing baking etc and reinstalling in existing position, testing etc complete all as specified and directed. |
| 78 | All as per item No. 77 here in above but 1HP capacity |
| 79 | All as per item No. 77 here in above but 3HP capacity |
| 80 | All as per item No. 77 here in above but 5HP capacity |
| 81 | All as per item No. 77 here in above but 10HP capacity |
| 82 | All as per item No. 77 here in above but 15HP capacity |
| 83 | All as per item No. 77 here in above but 20HP capacity |
| 84 | All as per item No. 77 here in above but 25HP capacity |
| 85 | All as per item No. 77 here in above but 30HP capacity |
| 86 | All as per item No. 77 here in above but 40HP capacity |
| 87 | M & L for servicing of centrifugal pump sets of 0.5HP capacities including replacement of ball bearing, mechanical seal and greasing,impeller,gland packing, inlet outlet flange, shaft etc complete all as specified and directed. |
| 88 | All as per item No. 87 here in above but 1HP capacity |
| 89 | All as per item No. 87 here in above but 3HP capacity |
| 90 | All as per item No. 87 here in above but 5HP capacity |
| 91 | All as per item No. 87 here in above but 10HP capacity |
| 92 | All as per item No. 87 here in above but 15HP capacity |
| 93 | All as per item No. 87 here in above but 20HP capacity |
| 94 | All as per item No. 87 here in above but 25HP capacity |
| 95 | All as per item No. 87 here in above but 30HP capacity |
| 96 | All as per item No. 87 here in above but 40HP capacity |
| 97 | S&F in repairs UPVC flat submersible, water proof cable, 3 core 6Sqmm copper conductor, multi stranded 1100V grade complete all as specified and directed.Make:Finolex/Plaza/ Polycap |
| 98 | M&L for Lifting the submersible pump set of 3HP capacity from UG Sumps/shallow well of depth 10 Mtr ,and , transporting to a reputed workshop for repairs,openingup the pump set assembly completely and replace unserviceable spare parts such as water seals, bearing, Impeller,bushes,shaft assembly ,gland packing, gasket etc, and applying two coats of synthetic enamel paint over one coat of suitable primer& transporting back, lowering in to the shallow well connecting as the existing system and testing, complete all as specified and directed.Note : Rates are deemed to be inclusive of any other misc. items/spares required for satisfactory completion on job. |
| 99 | All as per item No. 98 here in above but 5HP capacity |
| 100 | All as per item No. 98 here in above but 7.5HP capacity |
| 101 | All as per item No. 98 here in above but 10HP capacity |
| 102 | S & F in replacement of flexible rubber coupling disc suitable for 40 HP pump set after removing the motor from pump and making alignment for smooth functioning complete all as specified and directed. |
| 103 | Supply and fix capacitor in replacement of metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible nonlinear load 15% of 5 KVAR capacity all as specified and directed. |
| 104 | Supply and fix capacitor in replacement of metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible nonlinear load 15% of 10 KVAR capacity all as specified and directed. |
| 105 | M&L Servicing of solar water heater system of 100 ltr capacity complete by cleaning and flushing out solar panel, arresting leakage in the system, replacing hot water hose pipe & PUF insulation of pipe , painting the solar panel frame with one coats of synthetic enamel paint and writing MES No etc with approved paint complete all as specified and directed |
| 106 | Supply and fix in replacement of on load change over switch 4 pole 415 volt AC, 50/60Hz, 250 A all as specified and directed. Make:LT or Havells/Schneider |
| 107 | S & F in repairs gun metal non return valve of 32 mm dia bore, screwed, ISI marked complete all as specified and directed. |
| 108 | Supply and fix in replacement of capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible nonlinear load 15% of 15 KVAR capacity all as specified and directed. |
| 109 | Supply and mix of calcium based granular disinfectant for water treatment, high stable (65 to 70%) in packing for dosing system during pumping/distribution lines to maintain calcium 1-2 PPM complete all as specified and directed Make Declibac or Aquafit manufacturer by M/S Sree Rayala seema , |
| 110 | S & F in repairs gun metal non return valve of 25 mm dia bore, screwed, ISI marked complete all as specified and directed. |
| 111 | M & L for plain cement concrete 1:3:6 type C1 using 20mm graded aggregate laid in foundations/ valve chamber filling, support of pipe laying and mass concrete etc complete all as specified and directed. |
| 112 | M & L for construction of brick masonry valve chamber of size 1200mm x 900 mm x 900 mm with foundation in PCC 1:4:8 type D2, brick work built in cement mortar 1:4 with 15 mm plastering both internal complete and external surfaces (15cm below GL) and floor finished using plastering over PCC 1:4:8 including provn of MS sheet cover 5 mm thick surrounded by MS angle iron of size 40 x 40 x 6 mm framework embedded in PCC coping of 1:3:6 type C2, painted with two coats of synthetic enamel paint over one coat of red oxide primer on steel surface including earth work and excavation complete all as specified and directed. |
| 113 | M & L for replacement of damaged valve pit by brick masonry work built in cement mortar 1:4 with 15 mm plastering both internal complete and external surfaces (15cm below GL) and floor finished using plastering over PCC 1:4:8 including cement based paint all as specified or as directed by Engr In Charge including demolition existing pit and earth work and excavation complete all as specified and directed. |
| 114 | M& L for taking our old valve pit covers and M& L for valve pit cover with MS sheet cover 5 mm thick surrounded by MS angle iron of size 40 x 40 x 6 mm framework embedded in PCC coping of 1:3:6 type C2, painted with two coats of synthetic enamel paint over one coat of red oxide primer on steel surface including earth work and excavation complete all as specified and directed. Note : PCC and angle iron will be measured and paid separately. |
| 115 | S&F for replacement of chlorine dozing pump 0-6 LPH ,Discharge pressure 3.5 to 4 kgs/sqm suitable for existing dozing system its equivalent complete all as specified and directed. |
| 116 | Collecting the drinking water sample from Pump Houses & Shallow well&User End for testing the water at Public Health Department, Kerala Government as per the Government norms and submitting the Lab Test Report in the name of Garrison Engineer (AF) Trivandrum and submit the test report complete all as specified and directed |
| 117 | Supply and fixing replacement of MCCB, 415 volts, 3 pole of capacity 63 Amps, 25 KA, adjustable thermal- magnetic release, including spreader terminals, phase barriers, thimbles of suitable size etc and making electric connections and taking down old unserviceable MCCB, complete all as specified and directed. Make: Legrand/ L&T Indoasian/Havells. |
| 118 | All as per items No. 117 here-in-before but four pole 63 Amp capacity, 25 KA |
| 119 | All as per items No. 117 here-in-before but three pole 100 Amp capacity, 25 KA |
| 120 | All as per items No. 117 here-in-before but four pole 100 Amp capacity, 25 KA |
| 121 | All as per items No. 117 here-in-before but four pole 125 Amp capacity, 25 KA |
| 122 | All as per items No. 117 here-in-before but four pole 160 Amp, 25 KA capacity |
| 123 | All as per items No. 117 here-in-before but four pole 200 Amp, 25 KA capacity |
| 124 | All as per items No. 117 here-in-before but four pole 250 Amp, 25 KA capacity |
| 125 | Supply&Mix bleaching powder stable conforming to IS complete all as specified and directed. |
| 126 | M& L for servicing maintenance of bleaching dozer installed at pump house of existing make including cleaning, oiling & greasing. Check serviceability of bleaching dozer and injector check valve and minor parts. Note : Contractor will ensure that complaint will be attended with 2 hrs and rectified within 24 hrs for smooth functioning of the system. Major spares ie dossing pump and injector valve will be measured and paid separately under relevant items, all as specified and directed. |
| 127 | Dismantling Booster pump/pressure pump motors of capacity up to 1HP from its existing location, cutting and removing burnt motor winding, cleaning the slots and rewinding with approved quality super enamelled copper conductor winding wire of existing size and capacity including insulating materials, varnishing baking etc and reinstalling in existing position, testing etc complete all as specified and directed. Note: rates are included for taking down and refixing of motors after rewinding and transportation to civil workshop and back to site. |
| 128 | S & F in replacement of Air release Valve, cast iron, of size 100mm dia bore, flanged, with GM working parts as per IS - 5312, with nuts bolts and gaskets complete all as specified and directed. Make Leader/Kirloskar/Normax |
| 129 | Supply and fix in replacement of Pressure tank for Booster pump & pressure pump/Global 24 Ltr Hydro Pneumatic Pressure pump all as specified and directed. |
| 130 | S&F in replacement of PTMT ball valve, high pressure, with polyethene float and fly nut complete, screwed for iron pipe of brass ferrule of 25mm dia bore complete all as specified and directed. |
| 131 | M&L for iron removal plant of 50 cum/hr capacity by removing existing filter media completely and supply and lay the media as per manufacturer recommendation in layers vertically from bottom to top as recommendation by OEM and testing complete with back wash of iron removal plant Iron removal filter to function all as specified and directed. |
| 132 | M&L for activated carbon filtration plant of 50 cum/hr capacity by removing existing filter media completely and supply and lay the media as per manufacturer recommendation in layers vertically from bottom to top as recommendation by OEM and testing complete with back wash of carbon filtration plant to function all as specified and directed. |
| 133 | M&L for dual media filtration plant of 50 cum/hr capacity by removing existing filter media completely and supply and lay the media as per manufacturer recommendation in layers vertically from bottom to top as recommendation by OEM and testing complete with back wash of dual media filtration plant to function all as specified and directed. |
| 134 | M&L for replacement of Storage tank suitable for 100 ltr capacity, outer body made out of high engineering plastic and inner container made out of SS 304 L Plasma TIG welded and insulated with PUF insulation complete with heating element 2 KW with thermostat including hoisting to the inlet and outlet connections from solar panel complete all as specified and directed. |
| 135 | M&L for replacement of solar plate collector with 4mm thick glass, frame made of aluminium section complete panel of approx. size 1.00 mtr X 2.00 mtr maximum working pressure 245 Kpa (2.45 Bar) including necessary water connection all as specified and directed. |
| 136 | M & L for making CD Joints through JIFFY COUPLING complete with GI nut, bolts, rubber O ring & all accessories and arresting the leakage for pipes of size 100mm dia bore dia of bores complete all as specified and directed. Please Enable Macros to View BoQ information |