| 1 | Safe carriage loading unloading with proper stacking of following material from ESC Daliganj to Work Site/JE dump store. |
| 2 | 11 KV 3x70/120/185 Sqmm XLPE Cable |
| 3 | 11 KV 3x70/120/185 Sqmm O/D I/D S/T Kit |
| 4 | STP Pole 9/11 Mtr. |
| 5 | ACSR Weasel/Rabbit/Dog Conductor |
| 6 | 11 KV Pin Insulator |
| 7 | PCC Pole 8.5/11 Mtr. |
| 8 | 11.04 KV TF 250 KVA |
| 9 | LT Cable 1x400 sqmm. |
| 10 | LT ABC 3x120 sqmm. |
| 11 | Top Channel |
| 12 | Dropper Channel |
| 13 | 11 KV Disc Insulator With Fitting |
| 14 | Earthing Rod Complete |
| 15 | T-Off Channel |
| 16 | V Type X arm |
| 17 | Stay Set Complete |
| 18 | Cross Channel |
| 19 | Stay Wire 7/8 Swg |
| 20 | M.S. Angle 75x75x6x2028 mm |
| 21 | 11 KV VCB for CTR 200/100/5A 350 MVA (1250 Amp.) |
| 22 | All Decentralized Items Provided/Fixing/ Erection/Installation/Laying/Foundation with earthing by the contractor as on his own cost as per RESPO Narms.33 KV LINE ERECTION WORKMinimum depth of laying from ground surface to the top of cable as per IS is1)Low Voltage (1.1KV) and control cable 0.75 Mtr2) 3.3 KV to 11 KV Cables 0.90 Mtr3) 22 KV to 33 KV Cable 1.05 Mtr4) Cables at Road Crossing 1.00 Mtr5) Cable at Railway Laval Crossing ( measured from bottom 1.00 Mtr Of sleepers to top of pipe) Note- 1- The depth may be increased but not more than 1.6 Mtr 2- The Standard depth and width for laying the cable are also attached ( as per letter No 561/Director(Tech)/MVVNL/Camp/Dt 09.01.2026 with the tender form) |
| 23 | Well type/Bore type earthing of with 60 Fit Deep boring and providing GI Pipe 1.5\\" dia (\\"B\\" Class) and earthing must be joint by G.I. Strip of 32x5 mm thick long attached with nut & bolts and GI pipe cap. All material and labour shall be supplied the contractor. |
| 24 | Supply & Fixing of Al. Long Leg Barrel off Size. |
| 25 | Supply & Fixing of Copper L Piece For 250 KVA T/F. |
| 26 | Laying Stringing & sagging of 3 Phase 3 wire 11 KV New Line on ACSR Wesal/Racoon/Dog/Rabbit conductor as per RESPO Specification and direction on E/I. All material exept ACSR wesal/Racoon/Dog/Rabbit conductor shall be supplied by the contractor. |
| 27 | Ordinary earthing by 11 KV MS earth Rod 2500mm long as per RESPO Schedule. All material supplied by the contractor. |
| 28 | Wiremess fencing of 11/0.4 KV S/S shall be made of rectangular of size as per site requirement not exceeding 3 meter fabrication 45x45x5 mm angel the frame is also have 1 no. Horizontal runner of MS flat 40x5 welded in middle to support of wire mesh. Rectangular welded type wire mess of size 50x25 made of 12 S.W.G. wire mess shall be welded all along the periphery of the frame as well as on horizontal runner to give extra strength of welding to wire mess welded on the frame. Diagonal bracing of all the frame panel will be welded with Ms flat of size 25x3mm to support as per RESPO specification & direction of E/I. |
| 29 | Construction of T/F plinth of size 2x2x1.2 mtr with the help first class brick & masonry in the ratio 1:4 cement & sand coarse. Filling the structure completely per norms with RCC to 1:2:2 cement & stone grit with MS bar and MS channel for resting transformer. |
| 30 | Construction of masonry/metallic type distribution pillar of size 1x1.5x2.5 mtr. with supply & fixing of fabricated 4 nos. doors (2ft.x4ft.) made of BP sheet of 18 SWG with locking arrangement, 2 Nos. Straight MS angle 50x50x6mm (1800 mm long) 2 nos. 500 Amp, 3 Nos. 300 Amp Henley Type tailless fuse Unit, 3 Nos copper bus bar of size 1000x50x6 mm and one No. Alum busbar 1000x50x6 mm including all civil material required for work. All material shall be supplied by contractor. |
| 31 | Proper laying & commissioning of (3X95/3X120 sq.mm) Aerial Bunched Conductor. Only ABC Provided by deptt. |
| 32 | Dragging of ST/PCC Pole digging of pit erection of sub-station type double pole structure on ST/PCC Pole with fixing of necessary item such as Top Channel, along with grouting (As per RESPO Norms) Dropper Channel, 11 pin insulator with Pin & 11 KV Disc Insulator with fitting, DO Fuse set its ramming, as per RESPO Specification. Only Pole and insulator will be Provided by the Department. |
| 33 | Dragging of ST/PCC Pole to pit site, diging of pit erection and grouting (As per RESPO Norms) of 11 KV line with fixing of necessary item, such as V-type X-arm, F-bracket, 11 KV Pin insulator, Gaurding angle (1.8 mm 65x65x6) with Nut & bolts its ramming as per RESSPO Specification. Only Pole and insulator will be Provided by the Department. |
| 34 | Supply & Fixing of 11 KV D.O Fuse Set. |
| 35 | Ordinary earthing by 11 KV MS earth Rod 2500mm long as per RESPO Schedule. All material except Complete earthing Rod shall be supplied by the contractor. |
| 36 | Laying of 3X70/120/185 sq.mm 11 KV XLPE cable by Drill method Double Circuit as per RESPO Norms. Only 11 KV XLPE cable supplied by Department. |
| 37 | Grouting & Nuzzling of 11 KV stay set complete including fixing of necessary clamps. Accessories required including its grouting by civil material (Sand, Brick blast & cement). All material except stay wire and stay rod shall be supplied by the contractor. |
| 38 | Cable Hosting of 11 KV 3x70/3x120/3x185 sq. mm XLPE Cable at the following including jumpering etc complete with help of GI Pipe as Per RESPO Norms. GI pipe and other required material shall be supplied by contractor. |
| 39 | High pressure testing of 11 KV 3x70/3x120x3x185 XLPE cable along with arrangement of High Pressure equipment. Please Enable Macros to View BoQ information |