| 1 | 33 KV DP With Isolator-01 NosWPB (GI) Pole 160x152 (13Mtr. Long, 30.44KG/Mtr.)-DP(Total Pole Weight with Base Plate & Stiffner=395.72 KG+10.74 KG= 406.46 KG) |
| 2 | Top Channel(GI) 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 4.3 mtr., 2 no's Channel(GI)required =( 2x9.56x4.3) |
| 3 | Fish Plate(GI) 50x6 mm., 2.36 kg/Mtr., each 0.280 mtr. length, 6 no's required = (6x2.36x0.280) |
| 4 | Insulator Support Channel(GI) 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 4.3 Mtr., 1 no'sChannel(GI) required =( 1x7.14x4.3) |
| 5 | Isolator Support Channel(GI) 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 4.3 Mtr., 2 no'sChannel(GI) required =( 2x7.14x4.3) |
| 6 | Double Pole Belting Channel(GI) 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI) length 4.3 Mtr., 4no's Channel(GI) required =( 4x7.14x4.3) |
| 7 | 50x50x6mm.GI Bracing Angle(GI), 4.5Kg./mtr., each Angle(GI) length 4.927 mtr., 4 nos Angle(GI)required = (4*4.5*4.927) |
| 8 | Isolator Operating Down Pipe Support Channel(GI) 75X40X 4.8mm., 7.14KG/Mtr., each Channel(GI)length 0.8 Mtr., 1 no's Channel(GI) required =( 1x7.14x0.8) |
| 9 | Down Pipe Diagonal Support Angle(GI), 4.5Kg./mtr., each Angle(GI) length 0.388mtr., 1 nos Angle(GI)required = (1*4.5*0.388) |
| 10 | Down Pipe Base Support Angle(GI), 4.5Kg./mtr., each Angle(GI) length 0.34mtr., 1 nos Angle(GI)required = (1*4.5*0.340) |
| 11 | Isolator Support Side Channel(GI) 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 0.5 mtr., 2no's Channel(GI) required =( 2x9.56x0.5) |
| 12 | Danger Plate, 2 no's. |
| 13 | Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 2 no's =(2x0.59x0.510) |
| 14 | H.T. Stay clamp, 50x8 mm. Flat(GI), 3.14Kg/Mtr., 0.511 Mtr. Length, 2 no's qty. required ( 1 Pair) |
| 15 | H.T. Stay set (Complete ) |
| 16 | H.T. Stay Insulator Type-C (2 No's.) |
| 17 | 7/8 SWG Stay Wire 15kg /stay |
| 18 | Gi Pipe Earthing 40mm. 3 Mtr. Long |
| 19 | 50x6mm Flat(GI) for earthing, 2.36kg/mtr., (15 Mtr. For L.A, 4 Mtr for Isolator Body, 2.5 mtr. For meshformation and 2.5 mtr. For raising)= 24x2.36 |
| 20 | GI barbed wire anticlimbing device 3 Kg. Per support |
| 21 | Back Clamp for anticlimbing device 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 8 no's =(8x0.59x0.510) |
| 22 | Lightning Arrester(30KV,10KA) (Station Class,class-2) |
| 23 | 33 KV 1250 AMP Double break (Turn & twist center rotating) isolator without earth switch withPl(Polymer) |
| 24 | 33KV pin insulator polymer |
| 25 | H W fitting(B&S) 90KN,4 Bolt |
| 26 | Disc insulator (B&S) 90 KN polymer |
| 27 | Wedge connector for 232 sq.mm AAA conductor |
| 28 | Paddle clamp for wedge connector of 232 sq.mm AAA conductor |
| 29 | GI Nut , Bolt & Washer of different sizes (22.15 Kg each DP with Isolator) |
| 30 | POLYCARBONATE BIRD GUARD |
| 31 | Black Paint(GIS Numbering & Zebra Stripping) |
| 32 | Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background |
| 33 | Civil & Services- For 33 KV DP with Isolator-01 NosFixing of complete 33KV line Complete stay set includes1) Turn Buckle Assembly2) Stay Rod & Stay plate3) Stay Insulator4) Stay Wire.5)Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard.Note:- Excavation of earth will be done of size 500X500X1500 mm. |
| 34 | Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX2200mm) = 0.55Cu.mtr(Per Pole) |
| 35 | Couping ratio 1:1.5:3(M-20 Grade) with dimension (500X500X450)= 0.1125 Cu mtr(Per Pole) |
| 36 | Provide necessary civil material for construction of Earthing chamber, excavation & installation of incuding earthingpipe dia up to 100mm dia for length of 3Mtr.Scope also includes necessary nutbolt, 25 Kg Bentonide Power , connection & welding with incoming earth Flat(GI). The work to be executedas per TPCODL drawing & design |
| 37 | Supply and laying of 33kV 1CX400sqmm XLPE U/G cable with spare for length- 160 Mtrs.Supply of 33kV, 1Core, 400sqmm Aluminium, XLPE insulation UG Cable (SC rating of cable in kA- 37.7kA and SC rating of Armour in kA-20kA) |
| 38 | Supply of Outdoor termination kits Heat Shrinkable type suitable for 33kV, 1Core, 400sqmm, HT UG Cable kits for 1Core |
| 39 | Supply of Indoor termination kits Heat Shrinkable type suitable for 33kV, 1Core, 400sqmm, HT U/G Cable kits (Touch Proof) |
| 40 | Supply of materials for High Density Polyethelene (HDPE) pipe 110mm diameter, PE 80- PN8 for laying of 33kV U/G cable |
| 41 | Supply of 33kV 1Way RMU + AUXPTSupply of RMU 33KV 630A SINGLE BKR MODULE + AUXPT |
| 42 | EarthingEarthing Conductor: 50X6 mm (2.4kg./mtr.) Flat(GI) for equipment, structure etc.) |
| 43 | Pipe Earthing 40mm. GI Pipe |
| 44 | Erection, Commissioning & Testing of 33kV new line by 1Core, 400sqmm, XLPE UG cableLaying, Commissioning & Testing of 33kV, 1Core, 400sqmm, XLPE insulation (extruted type) UG cable in trefoil formation by open trench method. |
| 45 | Erection of Straight through jointing Kits/Outdoor termination kits/Indoor termination Kits Heat Shrinkable type suitable for 33kV, 1Core, 400sqmm, aluminium UG cable kits |
| 46 | Laying of 110mm dia PE 80-PN8, HDPE pipe inside open trench. |
| 47 | Erection, Commissioning, Wiring and Testing of 33kV RMUErection of RMU 33KV 630A SINGLE BKR MODULE + AUXPT |
| 48 | Civil works with supply of all materials like cement, MS tor rod, brick, coarse & fine aggregates and labour, T&P, etc for UG Cable TrenchEarth work excavation of soil |
| 49 | Earth work excavation of hard rock |
| 50 | Back filling with excavated soil outside and above the trench |
| 51 | Civil works with supply of all materials like cement, MS tor rod, brick, coarse & fine aggregates and labour, T&P, etc for HT Cable TrenchEarth work of excavation normal soil Trench Dimension: (1.6 mtr W X 1.775 mtr D) |
| 52 | Earth work of excavation hard rock Trench Dimension: (1.6 mtr W X 1.775 mtr D) |
| 53 | Backfilling with excavated soil outside and above the trench. |
| 54 | PCC (1:3:6(M-10 Grade)) below trench (width 1500mm, thickness 75mm throughout) |
| 55 | Supply and erection of materil for RCC partition slab 750mmX100mm (M-25 grade) |
| 56 | Supply and erection of material for RCC trench, 150mm thick (M-25 grade) |
| 57 | Supply and erection of rod, bending, cutting and binding of RCC trench (65.23 KG/cum) |
| 58 | Supply and erection of rod, bending, cutting and binding of RCC slabs (67.8 KG/cum) |
| 59 | Centring & shuttering for mass concrete |
| 60 | Structural steel work riveted (Channel(GI)- 75mmX40mmX4.8mm), (Flat(GI)- 75mmX6mm) |
| 61 | Civil works for Prefabricated RCC foundation with supply of all materialsPrefabricated RCC foundation of 33kV RMU |
| 62 | SITC of GI Fencing with Gate around each RMU |
| 63 | Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI)around pipe . |
| 64 | Supply and erection of GI Pipe of dia. 150mm, Class-B (8Mtr.) |
| 65 | Supply and Erection of Cable Route Marker along the cable route at an interval of 30mtrs with civil works |
| 66 | Construction of One No of 33 KV Outdoor Bay (Transformer)T-1 GI Column(7.25 mtr long, consisting of 2 Nos of 150X76X6.5 mm Channel(GI)) for 33kV incoming line, Nominal Unit Wt - 0.35 MT/column |
| 67 | T-2 GI Column (7.25mtr long, consisting of 2 Nos 175X75X6 mm Channel(GI)) for 33kV incoming line -1 no, Nominal Unit Wt - 0.42 MT/column |
| 68 | T-1A GI Column ( for 33 kv Bus) ( 6 mtr long, consisting of 2 Nos of 150X76X6.5 mm Channel(GI) jointed by plates) Nominal Unit Wt - 0.31 MT/column (0.31x2=0.62MT) |
| 69 | T-2A GI Column ( for 33 kv Bus) (6 mtr long, consisting of 2 Nos 175X75X6 mm Channel(GI) jointed by plates) Nominal Unit Wt - 0.37 MT/column (0.37x2=0.74MT) |
| 70 | G-3 GI Beam(5.05mtr long, consisting of 2 Nos 150X75 X5.7mm) for 33kV incoming line - (2 nos. Beam- one for Surge Arrester and other for Isolator, Nominal Unit Wt - 0.2 MT/Beam |
| 71 | G-2 GI Beam (6.1 mtr long, consisting of 2 Nos 125X65 X5.3 mm Channel(GI) jointed by plates) for 33kV Bus Stringing , Nominal Unit Wt - 0.175 MT)/Beam (0.175x2 = 0.35 MT) |
| 72 | G-1 GI Beam (6.1 mtr long, consisting of 2 Nos 125X65 X5.3 mm Channel(GI) jointed by plates) for 33kV Bus Stringing , Nominal Unit Wt - 0.175 MT)/Beam (0.175x2 = 0.35 MT) |
| 73 | Equipment Structures (GI) For 33 KV Isolator (Unit Wt of Equipment Structures per set - 0.33 MT) |
| 74 | GI Spikes with cone and GI ( 2 nos) base plate 10mm (50x3000 mm GI pipe) (Unit Wt=0.035 MT) (0.035x6 = 0.21 MT) |
| 75 | GI Pipe Earthing 40mm. 3 Mtr. Long |
| 76 | 50x6mm Flat(GI) for earthing, 2.36kg/mtr. |
| 77 | 232 sq.mm AAAC for 33kV side jumpering and Bus Formation etc. |
| 78 | 33 kV 1250 AMP Double break (Turn & twist center rotating) isolator with earth switch with PI(Polymer) |
| 79 | 33 kV 1250 AMP Double break (Turn & twist center rotating) isolator without earth switch with PI(Polymer) |
| 80 | 33KV Outdoor VCB-1250 A, 25 KV/3 sec Gang operated type |
| 81 | outdoor CR PANEL FOR Transformer Protection 33KV Outdoor VCB |
| 82 | 33KV, Single Phase, Outdoor, OILCOOLED CT , 25KA/3sec CTR-200-400-800/1-1-1 A(Accuracy Class-PS/0.2S/5P20,Burden -/30VA/30VA |
| 83 | 33KV, Single Phase, Outdoor, OILCOOLED PT 33000/√3/110/√3 Volt (Accuracy class 3P/3P/0.2, Burden-100/100/100 VA |
| 84 | Lightening arrester 33 kV, 10 kV, CL III. (with surge counter) |
| 85 | Control Cable 12Core x 2.5 mm2 |
| 86 | Control Cable 16Core x 2.5 mm2 |
| 87 | Control Cable 4Core x 2.5 mm2 |
| 88 | Control Cable 7Core x 2.5 mm2 |
| 89 | Disc insulator (B&S) 90 KN polymer |
| 90 | H W fitting(B&S) 90KN,4 Bolt |
| 91 | Wedge connector for 232 sq.mm AAA conductor |
| 92 | Paddle clamp for wedge connector of 232 sq.mm AAA conductor |
| 93 | GI Nut , Bolt & Washer of different sizes |
| 94 | Civil & ServicesConstruction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI)around pipe . |
| 95 | VCB FoundationExcavate & remove the debris and provide necessary Tools,Machinery & Manpower for the activity. |
| 96 | Back fill the excvated site with same earth and provide necessary Tools,Machinery & Manpower for the activity. |
| 97 | Supplying and spreading, filling other works with fine sand under floors,ground etc as per EIC instruction. Scope of work also includes watering, ramming, consolidating and dressing complete and other works if required at site . |
| 98 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:3:6(M-10 Grade)) in foundations, Trench and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 99 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:1.5:3(M-20 Grade)) in foudations and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 100 | Centring and shuttering including struttting , propping etc.and removal of form for Foundations, footings, bases of columns etc. for mass concrete |
| 101 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all copmplete, cold twisted bars/TMT as per TPCODL specification (Scope also include supply of material) |
| 102 | CT & PT FoundationExcavate & remove the debris and provide necessary Tools,Machinery & Manpower for the activity. |
| 103 | Back fill the excvated site with same earth.BA will provide necessary Tools,Machinery & Manpower for the activity. |
| 104 | Supplying and spreading, filling other works with fine sand under floors,ground etc as per EIC instruction. Scope of work also includes watering, ramming, consolidating and dressing complete and other works if required at site . |
| 105 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:3:6(M-10 Grade)) in foundations, Trench and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 106 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:1.5:3(M-20 Grade)) in foudations and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 107 | Centring and shuttering including struttting , propping etc.and removal of form for Foundations, footings, bases of columns etc. for mass concrete |
| 108 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all copmplete, cold twisted bars/TMT as per TPCODL specification (Scope also include supply of material) |
| 109 | Column as per Drawing Schedule-Excavate & remove the debris and provide necessary Tools,Machinery & Manpower for the activity. |
| 110 | Back fill the excvated site with same earth and provide necessary Tools,Machinery & Manpower for the activity. |
| 111 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:3:6(M-10 Grade)) in foundations, Trench and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 112 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:1.5:3(M-20 Grade)) in foudations and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 113 | Centring and shuttering including struttting , propping etc.and removal of form for Foundations, footings, bases of columns etc. for mass concrete |
| 114 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all copmplete, cold twisted bars/TMT as per TPCODL specification (Scope also include supply of material) |
| 115 | IsolatorExcavate & remove the debris and provide necessary Tools,Machinery & Manpower for the activity. |
| 116 | Back fill the excvated site with same earth and will provide necessary Tools,Machinery & Manpower for the activity. |
| 117 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:3:6(M-10 Grade)) in foundations, Trench and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 118 | Providing and laying Plain Cement Concrete (PCC) of proportion (1:1.5:3(M-20 Grade)) in foudations and plinths using approved quality of cement, 20mm size hard crusher broken granite stone metal and screened, washed sharp sand for mortar of approved quality and from approved quarry, including hoisting, lowering, laying concrete, ramming, watering and curing etc. complete to required levels in layers not exceeding 15cm thick in each layer including cost, conveyance, loading, unloading, royalties and taxes, cess, of all materials & cost of all labours, sundries, T&P and all other machinaries required for the work etc., as directed by Engineer-in-Charge. |
| 119 | Centring and shuttering including struttting , propping etc.and removal of form for Foundations, footings, bases of columns etc. for mass concrete |
| 120 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all copmplete, cold twisted bars/TMT as per TPCODL specification (Scope also include supply of material) |
| 121 | Land Leveling & Compaction/ Gravels sprading :Supply all materials required for backfilling and has to carry out the job of backfilling with earth, as per TPCODL standards |
| 122 | Supplying, Laying, spreading and compacting with hand roller stone aggregate of specified sizes: 63 mm to 45 mm size stone aggregate to WBM specifications in uniform thickness, hand picking to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate, watering and compacting to the required density . .Scope of work also includes of jungle such as grass,small tree,plant etc. |
| 123 | 1000 KVA , 33/ 0.4 KV (Cu) Transformer Supply of 33kV, 3Core, 400sqmm Aluminium, XLPE insulation UG Cable with spare (SC rating of cable in kA- 37.7kA and SC rating of Armour in kA-20kA) |
| 124 | Supply of Indoor termination kits Heat Shrinkable type suitable for 33kV, 3Core, 400sqmm, HT U/G Cable kits (Touch Proof) |
| 125 | Supply of Outdoor termination kits Heat Shrinkable type suitable for 33kV, 3Core, 400sqmm, HT UG Cable kits |
| 126 | LT Cable raising Channel(GI) 75x40x4.8 mm GI Channel(GI) (1000 mm long)(7.14Kg./Mtr., 9 No's.) (Each 9x1.000x7.14= 64.26 Kg) |
| 127 | 50x6mm Flat(GI) for earthing, 2.36kg/mtr., (2.5x8 mtr. For mesh formation, 5x2 mtr. for DTR Nutral, (1.3+4.5) mtr. For DTR Body, 0.500 mtr for LTDB, 3 mtr. for Fencing, 10 mtr. For RMU, 10 mtr. For LA) ( Each 59.3 x 2.36= 139.95 Kg) |
| 128 | 1000 KVA , 33/ 0.4 KV (Cu) Transformer with Tap Changer BIS Energy Loss level II, Ammendment-4 |
| 129 | LT DISTRIBUTION BOX (GI)with LT ACB, 50kA 3Pole(I/C-2000 Amp), 2500Amp Aluminium Busbar for 6 Bay with HRC fuse (O/G-1 ,630 Amp, O/G-2, 630 Amp,O/G-3, 630 Amp,O/G-4,630 Amp,O/G-5,630 Amp,O/G-6,630 Amp ). LT ACB should have integrated protection for Overload, Short circuit & earthfault.The GI enclosure thickness must be 3mm thickness & IP55 compiled. |
| 130 | 1 Cx 630 mm2 LT XLPE Cable(Un-Armoured) |
| 131 | HT & LT Cable Supporting Channel(GI) 100 X 50 X 6 MM GI Channel(GI) (2000 mm long)(9.56 Kg./Mtr., 2 No's.) (Each 2x2x9.56x2= 76.48 Kg) |
| 132 | HT & LT Cable Supproting Angle(GI), 50x50x6mm.GI 4.5Kg./mtr., each Angle(GI) length 2 mtr., 4 nos Angle(GI) required = (4.5x4x2x2= 72 Kg) |
| 133 | 40 mm Nominal bore GI pipe (medium gauge) earthing device with 3 mtr .Long |
| 134 | GI Nuts & Bolts of Assorted size |
| 135 | Name plate |
| 136 | Structure Numbering and Marking(a) Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background |
| 137 | (b) Black Colour Paint(GIS Numbering & Zebra Stripping) for numbering |
| 138 | Civil and Services Works(As per Technical Specification)Laying, Commissioning & Testing of 33kV, 3Core, 400sqmm, XLPE insulation (extruted type) UG cable by open trench method. |
| 139 | PCC ratio 1:3:6(M-10 Grade) For DSS Area (3.5X3.5X0.1)= 1.225 Cu. mtr. |
| 140 | Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earthresistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI)around pipe . |
| 141 | LTDB Plinth |
| 142 | DTR Plinth upto 1000 KVA |
| 143 | Laying of 1.1kV cable from 400 to 1000sqmm |
| 144 | SITC and Erection of GI Fencing with Gate |
| 145 | Supply of AL Lugs suitable for 630 sq mm cable/conductor, Crimping with cable and Fixing/connecting include supply and erection of PVC Tape as per voltage requirement. |
| 146 | Supply of AL Lugs suitable for 400 sq mm cable/conductor, Crimping with cable and Fixing/connecting include supply and erection of PVC Tape as per voltage requirement. |
| 147 | Supply and erection of double Compression Flameproof Type Glanding for armored Cable 1C 300-1000 sqmm including making hole in Base plate and dressing of cable along with vermin proofing properly .Supply to be done as per TPCODL Spec and approved make dowells. |
| 148 | Supply and erection of double Compression Flameproof Type Glanding for armored Cable 3.5/4C 120-185sqmm including making hole in Base plate and dressing of cable along with vermin proofing properly .Supply to be done as per TPCODL Spec and approved make dowells. |
| 149 | SITC of 1 MVA Transformer LT Control Panel.Cost of 16/ 18 SWG panel box 2*(87*87+87*40+40*87) sq. inch for single door made out of CR sheet of 16/ 18 SWG and boarder angle frame to provide above pannel with proper space ,hinges, and other accessories hinged door etc. |
| 150 | Provision of internal wiring to equipment installed in the pannel board with required size of copper multistrand single core cables duly crimped with copper lugs and all connections 2*(87*87+87*40+40*87) including cost of copper conductor and other fittings like gasket ,screw, nut and bolt, insulating materials etc. |
| 151 | Cost of Powder Coating 4*(87*87+87*40+40*87) |
| 152 | Cost of Copper flat (As per instruction of Engineer-in-charge) |
| 153 | Cost of Drum Insulator (400 - 1000A) |
| 154 | Cost of CT Coil (1500/ 5 Amp) |
| 155 | Cost of 4 Pole Spreaders link (a) 63 - 250A |
| 156 | (b) 400A |
| 157 | (c) 630A |
| 158 | Supply & laying of 1C X 630 mm2 LT XLPE Cable (Unarmoured) . |
| 159 | INCOMING BUSBARSupply and fixing of 4pole ACB with Thermal Mangnetic Protecton unit in existing cubicle panel board including drilling holes in cubcle panel, making connections, etc. as required.(Make- Legrand/ Hager/ Simens/ schneider)1600 AMP, 65 KA |
| 160 | OUTGOING BUSBARSupply and fixing of DPX3 4pole MCCB with Thermal Mangnetic Protecton unit in existing cubicle panel board including drilling holes in cubcle panel, making connections, etc. as required.(Make- Legrand/ Hager/ Simens/ schneider)(a) 500 - 630 Amp, 50 KA |
| 161 | (b) 200 -250 Amp, 36 KA |
| 162 | (c) 100 -125 Amp, 36 KA |
| 163 | Cost of Indicator lamp with trangular switch |
| 164 | S/F of Digital Voltmeter (Make - Legrand/ Or equivalent) |
| 165 | S/F of Digital Ameter (Make - Legrand/ Or equivalent) |
| 166 | S/F of Digital PF Meter (3ph VAF=PF) (Legrand/ Or equivalent) |
| 167 | Supply and fixing of Multifunction meter with selector switch including all connections |
| 168 | Floor rubber mat 6'x4' x 6mm |
| 169 | Supply and fixing of Shock Treatment Chart including all accessories. |
| 170 | Supply and fixing of Danger Board (200mmx150mmx2mm) |
| 171 | Inspection Fees |
| 172 | Gi Fencing with Gate Please Enable Macros to View BoQ information |