Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibration with GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etc as required. |
| 2 | Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. |
| 3 | 0.60 mm |
| 4 | 0.80mm |
| 5 | 1.00mm |
| 6 | Supplying, installing, testing and balancing of double louvered of extruded Aluminium Powder coated supply/return air grills of various sizes, Each grill shall be with fixed aerofoil shaped horizontal front bar at 0 deflection and back adjustable vertical louvers, air distribution grid for straightening the air flow through the collar and register including fixing with steel screws etc. complete in all respect. |
| 7 | Supply air grill with key operated volume control damper |
| 8 | Return air grill without volume control damper |
| 9 | Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. |
| 10 | Supply Air Diffuser with Volume Control damper |
| 11 | Return Air Diffuser without Volume Control damper |
| 12 | Supplying, installing and balancing of extruded Aluminium powder coated fresh air inlet louvers with bird screen & volume control damper fixing with steel screws etc. complete in all respect. |
| 13 | Supply and fixing of acoustic lining of ducts with chemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire property Water Vapour absorption 0.002 gm / Sqcm, including cost of adhesive etc. complete in all respect. |
| 14 | 10 mm thick |
| 15 | Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapour diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. |
| 16 | 19mm thick for Outdoor Application with 26 SWG Aluminium Cladding |
| 17 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 18 | 25 mm |
| 19 | 32 mm |
| 20 | 40 mm |
| 21 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM must ensure that the cable is tested for complaince, either through their in house laboratory accrediated by NABL or by any Govt. laboratory accrediated by NABL and the laboratory's scope of accrediation should cover the requirements and testing procedure as per IS:10810. |
| 22 | Un Armoured |
| 23 | 4 core x 2.5 Sq.mm |
| 24 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 25 | 100 mm dia per running inch length |
| 26 | 150 mm dia per running inch length |
| 27 | 200 mm dia per running inch length |
| 28 | Providing and making wall openings in existing stone / Brick masonry partition wall complete with all requited T & P, Scaffolding and providing lintel of required size and strength, repairing, plastering and cleaning the site debris as required. |
| 29 | SITC of Condensate water Drain pump suitable to Install with Existing Split type AC Indoor unit , single phase, 230V, including all acessories of pump like discharge tube, filter, reservoir etc. as required. |
| 30 | SITC of BMS compatible, fixed speed multi compressors modular Air Cooled scroll type chillers of following Nominal cooling capacity complete with fixed speed multi compressors (Min. 2/3 per chiller) fully hermetic scroll compressors, 2/3 fan motor, starter, air-cooled condenser with fins, evaporator of Shell & Tube / PHE type, vibration isolators, inbuilt accumulator, environment friendly refrigerant R-410A, first charge of refrigerant and oil, wiring, all accessories as per specifications, automatic and safety controls, microprocessor control panel, all mounted on steel frame, all accessories and any other item required to make the system complete. Modular Design to allow connection of multiple machines to make them behave as one unit. And the overall set to continue working in case of break down of one module. modular unit should have master and slave arrangement to run in single circuit of required unit as one. including wired remote controller for each unit and master controller to operate all chiller in one circuit.Chilled water Leaving Temp.(6.67 deg. C) Chilled water Entering Temp.(12.2 deg. C) Evaporator fouling factor = 0.018 m2. ⁰C/kWCondenser air entering temp. : As per Site Dry Bulb Temperature Suitable for climatic Zone and Altitude as per location/site. |
| 31 | more than 24 TR to 36 TR with ISEER > / = 3.6 |
| 32 | SITC of following discharge and head, End suction chilled water/ Condensor water recirculation pumps complete with motor , base frame, vibration isolators, mechanical seal, Bronze/S.S. Impeller. The pump motor shall be suitable for 415 ± 10%, 50 cycles, 3 phase power supply, squirrel cage induction 1450 RPM TEFC, IE3 motor, class 'F' insulation, with vibration isolators on existing MS / RCC foundation. |
| 33 | Primary chilled water pump |
| 34 | Flow rate : 900 USGPM, Head : 15 Mtr. |
| 35 | Secondary chilled water pump with VFD (Stand alone or integrated) |
| 36 | Flow rate : 900 USGPM, Head : 25 Mtr. |
| 37 | SITC of factory assembeled Ceiling suspended double skin Air Handling Unit having specifications as per A, B, C, D & E |
| 38 | A. Pre filter section : Pre-Filter (EU-4) section complete with 50mm thick washable synthetic fibre filters. Velocity across the filters shall not exceed 500 FPM. Filters shall have efficiency not less than 90% down to 10 Microns (EU-4/MERV-8). Filter material shall be non combustible type. |
| 39 | B. Coil Section : Coil section with 6 rows (3+3)deep chilled water cooling coil/ DX cooling coil of copper tube & copper header and aluminium fins construction having wall thickness of tubes not less than 0.5mm. Drain pan shall be made out of 18 gauge SS-304 duly insulated with 13mm thick closed cell elastomeric insulation with class 'O' fire retardant properties. Face velocity across cooling coil shall not exceed 500FPM. - Space Provision for coil to be provided. Drain Pan with drain arrangement to be provided for coil at this stage. |
| 40 | C. Fan Section : Fan Section comprising of belt driven, DIDW forward / Backward curved AMCA certified centrifugal fan with maximum air outlet velocity of 10m/s suitable for required cfm at 40 mm static pressure (Total static of the unit shall be verified by the OEM before the design & supply of the units). Fan & Motor should be mounted over Aluminium channel of suitable thickness and should be isolated from the unit's bottom panel. |
| 41 | D. Motor : TEFC High efficiecny IE-3 class motors suitably designed for VFD with pulley, belt , Guard |
| 42 | E. The unit shall be fabricated with frame work hollow extruded aluminium profile with 0.80 mm preplasticised GSS on outside and 0.80mm 275gsm plain GSS on inside complete with 48 mm thick CFC free PUF insulation of minimum 40 kg/cum density sandwiched in between inner and outer skins. ,The AHU shall be with thermal break profile with internal coving section complete with inspection doors, marine light, limit switch and control wiring as required. AHUs shall have access for all parts. noise level shall not exceed 70 dB, necessary vibration Isolation arrangement like spring hanger etc. as required. |
| 43 | 500 cfm to 2000 cfm |
| 44 | more than 2000 cfm to 4000 cfm |
| 45 | more than 4000 cfm to 6000 cfm |
| 46 | 500 cfm to 2000 cfm with 8 Row deep coil for TFA |
| 47 | more than 2000 cfm to 4000 cfm with 8 Row deep coil for TFA |
| 48 | Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for chilled water / Condensor water applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger, vibration isolators and nuts bolts including cutting hole and chase in brick walls and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of desired shade (for condensor water only) complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). |
| 49 | 25 mm dia |
| 50 | 32 mm dia |
| 51 | 40 mm dia |
| 52 | 50 mm Dia. |
| 53 | 65 mm dia |
| 54 | 80 mm dia |
| 55 | 100 mm dia |
| 56 | 150 mm dia |
| 57 | 200 mm dia, 6.0 mm thick |
| 58 | 250 mm dia, 6.35 mm thick |
| 59 | Supplying & fixing of Thermal Insulation on Chilled Water Piping with Factory made Self Sleeve Tubes/ Pre cut Sheets of Class 'O' (FM Approved) Closed Cell Elastomeric Rubber Material, Glue, with 7 mil Glass Cloth with 3 coats of anti UV paint for thicknesses of 50/44/38/32 mm. Thermal Conductivity of this material is 0.035w/m.k. and having µ value ≥ 7000.0 - 65 mm dia : 32 mm thick , 80 -100 mm dia : 38 mm thick , 125 - 150 mm dia : 44 mm thick , 150 - 400 mm dia : 50 mm thick. (Up to 100mm dia Self Sleeve tubes &> 100 NB Pre cut sheets. etc. as required. |
| 60 | 20/ 25 mm dia |
| 61 | 32 mm dia |
| 62 | 40 mm dia |
| 63 | 50 mm Dia. |
| 64 | 65 mm dia |
| 65 | 80 mm dia |
| 66 | 100 mm dia |
| 67 | 150 mm dia |
| 68 | 200 mm dia |
| 69 | 250 mm dia |
| 70 | Supply of Chilled Water Ceiling Suspended Hydronic Cassette type fan coil unit, four(4) way directional flow, low noise, each complete with two(2) rows of deep chilled water cooling coil, multi-blade centrifugal fan, test reports from National Accreditation Board for Testing and Calibration Laboratories (NABL)/AHRI accerdited lab, electronic air cleaning system, required set of ball valves with & without strainers & 2 way Motorized valve, insulated condensate drain pans with drain pump assembly & drain pump failure alarm, pipe connections through copper pipes, Infra-red remote control, Liquid Crystal Display (LCD), four (4) speed motor , fan four(4) direction air flow, auto swing louver, decorative panel etc., condensation drain connections, All units shall be suitable for 220 +/- 10% Volts, 50 Hz, single phase power supply etc. complete as per specification. The wireless Remote temperature control / thermostat shall have memory back up for set point re- store in case of power failure and re-start. Four(4)hanger rods with required anchoring fasteners, hooks, washers etc.complete as directed by Engineer-in-charge. |
| 71 | 4.0 TR nominal capacity with 1600 Cfm air quantity. |
| 72 | 3.0 TR nominal capacity with 1200 Cfm air quantity. |
| 73 | 2.5 TR nominal capacity with 1000 Cfm air quantity. |
| 74 | 2.0 TR nominal capacity with 800 Cfm air quantity. |
| 75 | 1.5 TR nominal capacity with 600 Cfm air quantity. |
| 76 | Supplying and Fixing of PN 1.6 Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. |
| 77 | 50 mm dia |
| 78 | 80 mm dia |
| 79 | 200 mm dia Gear Operated |
| 80 | Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required. |
| 81 | 20 mm dia. |
| 82 | 25 mm dia. |
| 83 | 32 mm dia. |
| 84 | 40 mm dia |
| 85 | Supplying and Fixing of PN 16 Brass/GM Ball valves with integral Y strainer, screwed end, SS Ball including teflon tape etc. as required. |
| 86 | 20 mm |
| 87 | 25 mm |
| 88 | Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holes in existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets etc as required of following sizes. |
| 89 | 40 mm dia |
| 90 | 50 mm dia |
| 91 | 200 mm dia |
| 92 | SITC of PN25 rated threaded end Brass Pressure Independent control valves (PICV) with ON-Off / Modulating actuator including teflon tape etc. as required. |
| 93 | 20 mm with ON-Off Actuator |
| 94 | 25 mm with ON-Off Actuator |
| 95 | 32 mm with ON-Off Actuator |
| 96 | 40 mm with modulating Actuator |
| 97 | 50 mm with modulating Actuator |
| 98 | S & F of Auto air vent valve complete with socket, ball valve etc. as required. |
| 99 | Supplying and Fixing of PN 16 Cast Iron Double regulating flanged balancing valve with nozzle and hand wheel complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. |
| 100 | 80 mm |
| 101 | 200 mm |
| 102 | SITC of AHU temperature controller including making connections etc. as required. |
| 103 | Providing & fixing in position 15 mm 'V' shape mercury in glass industrial type thermometer including Making Drilling, socket in Existing MS Pipe Etc. as required. |
| 104 | Providing & fixing Stainless Steel pressure gauge with dial of 100 mm dia size and range 0 to 20 kg/sq.cm with 3 / 8 \\" BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, duly calibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS Pipe Etc. as required. |
| 105 | P & F of Expansion tank, of size 1000mm x 1000 mm x 1000 mm fabricated out of 5 mm thick MS plate construction, duly insulated and complete with 32 mm dia. Outlets for system connection and overflow make up connection, drain connection, drain valve, vent connections, valves and fittings as required, Expansion tank shall be insulatedwith 50 mm thick PUF insulation cladded with 0.80 mm thick aluminium cladding etc. as required. (On existing Foundation) |
| 106 | SITC of Paddle type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in HVAC chilled water pipeincluding making connections, making hole in pipe etc. as required. |
| 107 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. |
| 108 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 109 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 110 | Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding: |
| 111 | New work (Two or more coats applied @ 3.84 kg/10 sqm). |
| 112 | Providing and Fixing of PN16 Resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes. |
| 113 | 80 mm Dia. x 150 mm Oal |
| 114 | 200mm Dia. x 150 mm Oal |
| 115 | Gravelling of Transformer / RMU Yard with 100 mm Height Gravels of Size 20 to 25 mm including leveling, Dressing etc. as Required. |
| 116 | SITC of IP 54 OEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Coordination Chart and made out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection(for three phase pumps), Illuminated ON / OFF push buttons, ammeter, voltmeter, indicating lamps, 2P/4P MCB etc. suitable for following rating motors complete in all respect. |
| 117 | For Three phase Submersible / Mono block pump |
| 118 | 3.0 HP to 5.0 HP ( DOL starter ) |
| 119 | 12.5 HP to 15.0 HP ( Star / Delta starter ) |
| 120 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 121 | 10.0 Sq. mm |
| 122 | 4 core |
| 123 | 16.0 Sq. mm |
| 124 | 4 core |
| 125 | 25.0 Sq. mm |
| 126 | 3.5 core |
| 127 | 50.0 Sq. mm |
| 128 | 3.5 core |
| 129 | 70.0 Sq. mm |
| 130 | 3.5 core |
| 131 | 95.0 Sq. mm |
| 132 | 3.5 core |
| 133 | 185.0 Sq. mm |
| 134 | 3.5 core |
| 135 | 240.0 Sq. mm |
| 136 | 3.5 core |
| 137 | Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth. |
| 138 | Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 139 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 140 | 3.5 x 50.0 sq.mm |
| 141 | 3.5 x 70.0 sq.mm |
| 142 | 3.5 x 95.0 sq.mm |
| 143 | 3.5 x 185.0 sq.mm |
| 144 | 3.5 x 240.0 sq.mm |
| 145 | 4 x 10.0 sq.mm |
| 146 | 4 x 16.0 sq.mm |
| 147 | 3.5 x 25.0 sq.mm |
| 148 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required. |
| 149 | 100mm x 50mm x 1.6mm |
| 150 | 150mm x 50mm x 1.6mm |
| 151 | 300mm x 50mm x 1.6mm |
| 152 | 450mm x 50mm x 2.0mm |
| 153 | 600mm x 50mm x 2.0mm |
| 154 | S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required. |
| 155 | 3/3.5/4 x 185.0 sq.mm-300 sq.mm |
| 156 | SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 157 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 158 | (b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7 |
| 159 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 160 | (d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. |
| 161 | (e) Testing of earth resistance for value of 5 ohms or less as required. |
| 162 | (f) Test certificates for confirming above standards from OEM is mandatory. |
| 163 | 25 mm thick and 3 Mtr. Long |
| 164 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 165 | 25mm x 6mm G.I. ( Hot Dipped ) Strip |
| 166 | 32mm x6mm G.I. ( Hot Dipped ) Strip |
| 167 | 50mm x 6mm G.I. ( Hot Dipped ) Strip |
| 168 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 169 | 8 SWG G.I. ( Hot Dipped ) Wire |
| 170 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 171 | Single pole MCB (With B / C curve tripping characteristics) |
| 172 | 6 A to 32 A rating |
| 173 | Triple pole MCB (With B / C curve tripping characteristics) |
| 174 | 6 A to 32 A rating |
| 175 | Four pole MCB (With B / C curve tripping characteristics) |
| 176 | 6 A to 32 A rating |
| 177 | 50/63 A rating |
| 178 | Providing & Fixing of din rail mounting surge protection device confirming to IEC 61643-11 for Type 1 + 2 protection and Maximum discharge current 50 kA with following configuration in existing distribution board / sheet including making connections, testing etc. as required. |
| 179 | 3P + N |
| 180 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB up to 63 Amps. as outgoing ,made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with insulated 125/160/200/250 Amp. copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 181 | Double door IP-43 & IK-09 with Provision of Incomer MCCB up to 125 A Rating with Metal end box |
| 182 | 12 Way |
| 183 | SITC of Microprocessor based Draw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT installation 440/415 V, 50 Hz and having adjustable over load, short-circuit, Instantaneous, earth fault (LSIG) with separate LED indication or Fault details on display for each type of fault shall confirm to EMI/ EMC test , LCD/LED display, last 10 trip history, Inbuilt ZSI, Current metering, Provision for Communication, Thermal memory, trip free mechanism, modular design and suitable for ambient 50 degree and utilization catagary B. In built electrical & mechanical anti pumping feature , pollution degree 3, 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 30 ms. Provision for electrical & mechanical interlock between ACB sand other required accessories (Cost of accessories to be paid extra) Min.electrical operation 10000 upto 1600 A rating and 5000 for 2000 A to 4000 A. including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 184 | Manual spring charged type 4 Pole |
| 185 | 630/800 A Rating , 50 kA |
| 186 | 1250 A Rating ,50 kA |
| 187 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 188 | 3 pole MCCB With Thermal Magnetic release |
| 189 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 190 | 160 Amp , 25 kA, adjustable O/L & fixed S/C setting, |
| 191 | Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. |
| 192 | Direct Rotary Handle |
| 193 | Spreaders upto 125A, 3 Pole MCCB |
| 194 | Spreaders for 160A, 3 Pole MCCB |
| 195 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 196 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 197 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 198 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 199 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 200 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 201 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 202 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 203 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 204 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 205 | Electrolytic grade Aluminium bus bar 6010 grade |
| 206 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 207 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW + KVA + KVAR + KVARH + KWH + DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 Meter |
| 208 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 209 | Ring type tape wound CT |
| 210 | C T Class 1, Ratio 800/5 to 1200/5, Burden 15 VA |
| 211 | C T Class 1, Ratio 1500/5 to 3000/5, Burden 15 VA |
| 212 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 213 | Red/yellow/Green colour |
| 214 | Blue / white Colour |
| 215 | SITC of Air Curtain made out from Stainless steel 304, 120 CM width, suiatble for working 230 +-10 % with low & high voltage cutoff & 50 Hz frequency, single phase AC supply with maximum air velocity 18-22 m/s and noise level not more then 55 db including power cable and stand including fixing with T&P & Labour etc as required |
| 216 | Providing and fixing 12.5 mm thick tapered edge gypsum board conforming to IS 2095- Part I at all height false ceiling including providing and fixing of frame work made of special sections power pressed from M.S. sheet and galvanised in accordance with zinc coating of grade 350 as per IS : 277 and consisting of angle cleats of size 25mm wide x 1.6mm thick with flanges of 22mm and 37mm at 1200mm centre to centre one flange fixed to the ceiling with dash fastener 12.5mm diax40mm long with 6mm dia bolts to the angle hangers of 25x25x0.55mm of required length, and other end of angle hanger being fixed with nut and bolts to G.I. channels 45x15x0.9mm running at the rate of 1200mm centre to centre to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26mm each having clips of 10.5mm at 450mm centre to centre shall be fixed in a direction perpendicular to G.I. channel with connecting clips made out of 2.64mm diax230mm long |
| 217 | G.I. wire at every junction including fixing the gypsum board with ceiling section and perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450mm centre to centre with 25mm long drive-all screws @ 230mm interval including jointing and fixing to a flush finish of tapered and square edges of the board with recommended filler, jointing tapes, finisher and two coats of primer suitable for board as per manufactures specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of the Engineer in Charge but excluding the cost of painting. |
| 218 | Providing and fixing calcium silicate board false ceiling at all heights including providing and fixing of frame work made of special sections power pressed from M.S. sheet and galvanised in accordance with zinc coating of grade 350 as per IS : 277 and consisting of angle cleats of size 25mm wide x 1.6mm thick with flanges of 22mm and 37mm at 1200mm centre to centre one flange fixed to the ceiling with dash fastener 12.5mm diax40mm long with 6mm dia bolts to the angle hangers of 25x25x0.55mm of required length, and other end of angle hanger being fixed with nut and bolts to G.I. channels 45x15x0.9mm running at the rate of 1200mm centre to centre to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26mm each having clips of 10.5mm at 450mm centre to centre shall be fixed in a direction perpendicular to G.I. channel with connecting clips made out of 2.64mm diax230mm long |
| 219 | G.I. wire at every junction including fixing the calcium silicate board with ceiling section and perimeter channels 0.5mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450mm centre to centre with 25mm long drive-all screws @ 230mm interval including jointing and fixing to a flush finish of tapered and square edges of the board with recommended filler, jointing tapes, finisher and two coats of primer suitable for board as per manufactures specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed all complete as per drawing and specification and direction of the Engineer in Charge but excluding the cost of painting of thickness of calcium silicate board as below:- |
| 220 | 8 mm thick |
| 221 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 222 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 223 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 224 | Surface Mounting (with extruded alumn. Housing ) |
| 225 | Minimum lumen output 1950 lm |
| 226 | SITC of IP20, 2'x2' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmissivity UV stabilized Non -yellowish diffuser for uniform light distribution. operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V . High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection ( input 320VAC-48 hoursprotection,input 350VAC-2 hours protection) (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 227 | Recessed Mounting |
| 228 | Minimum lumen output 4800 lm |
| 229 | Surface Mounting (Driver should be Inside the Luminaire) |
| 230 | Minimum lumen output 4800 lm |
| 231 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : |
| 232 | Two or more coats on new work |
| 233 | Providing and fixing double scaffolding system on the exterior side, upto five story made with 4\\" wooden member 1.5 m c/c horizontal and vertical direction joining with rassi, clamps, challies. The scaffolding system shall be stiffened with bracing, runner, connection of building if necessary with all essential safty features for the workmen etc complete as per direction of EI.The lavation area of the scaffolding shall be measured for payment. The payment will be made once irrespective of duration of scaffolding.Note : This item to be used for maintence work judicially |
| 234 | Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. |
| 235 | 200 mm dia |
| 236 | Labour charges for dismentling, shifting & refixing of MS structure from Dhanwantri terrace to Main building terrace consisting of MS Angle, MS Channel, MS Girders, MS Plates, MS Flats, by removing the fastners etc breaking the welded joints with grinder, cutter and refixing with same size and fastners. |
| 237 | Labour charges for dismentling & refixing of Air Washer capacity of 15000 CFM to 30000 CFM with Removing the Air washer unit complete with diconnection of ducting by removing the thermocol plaster insulation,Canvass connection,pads, electrical cable connection, iron stand,water supply pipe disconnection with all valves .the dismanteled air washer is to be placed at the location specified by the site engineer/hospital engineer at S.M.S. Hopsital. |
| 238 | buyback of Air Washer capacity of 15000 CFM to 30000 CFM with Removing the Air washer unit complete with diconnection of ducting by removing the thermocol plaster insulation,Canvass connection,pads, electrical cable connection, iron stand,water supply pipe disconnection with all valves. The necessary tool & plant required for dismentalling of air washer is incucuded in this cost. (iron stand is not included in the buy back cost). |
| 239 | buyback of GI/AL ducting after dismentling & cutting the nut bolts, support with sand Cement plaster /thermocol with fiber cloth/nitrile rubber insulation with aluminium clading, etc as required and dumping the insulation garbage outside the premises around 10Km away. The necessary tool & plant required for dismentalling of ducting is incucuded in this cost. The measurement of this item will be done as per duct dimension. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
| 8 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail