| 1 | M&L for taking down OH ACSR conductor of any type/size including all the connected accessories such as cross arms, channels, angles, brackets, insulators etc complete all as specified and directed. |
| 2 | Dismantling of existing unserviceable/cracks PCC poles of any size and type from its position from the site and taking away from site including necessary excavation and earth work in any type of strata,demolition of concrete, disconnecting of street light fitting etc complete all as specified and directed. |
| 3 | Supply, erecting and fixing in, true vertical position of steel tubular swaged pole, 9 mtr long complete with cast iron base plate, finial taper plug, bolt, nuts and screws as specified and of type 410 SP-31, conforming to relevant IS, including one primer coat of red oxide and two coats of aluminium paint and two coats of bituminous paint inside and outside of bottom portion up to 1.8 mtr length complete all as specified and directed. Make :-National tubing co ,Kanpur / Ridi poles,Varodara / Sohanlal & Sons Ghaziabad |
| 4 | Supply laying & testing 70 sqmm 3.5 core cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor,1100 volts grade, complete all as specified and directed. |
| 5 | All as per srl item No 4.00 but for 95 sqmm 3.5 core |
| 6 | All as per srl item No 4.00 but for 120 sqmm 3.5 core |
| 7 | All as per srl item No 4.00 but for 50 sqmm 3.5 core |
| 8 | All as per srl item No 4.00 but for 25 sqmm 3.5 core |
| 9 | All as per srl item No 4.00 but for 16 sqmm 2 core |
| 10 | All as per srl item No 4.00 but for 10 sqmm 2 core |
| 11 | Material & labour for cable route indicator made out of CI plate 100 dia, 6 mm thick & fixed over angle iron of size 60 x 60 x 6 mm, 120 cm in length duly pianted with aluminium paint suitable for LT cable all as specified & including embedded in PCC (1:3:6) type C1 of size 30 x 30 x 20 cm in ground complete all as specified and directed. |
| 12 | Excavation in trenches n. exc. 1.5 Mtr width n.exc 1.5 Mtr in depth for laying of cables & foundation of poles, stay assembly and getting cut in any type of soil complete all as specified and directed. |
| 13 | Returning, filling in including spreading levelling, watering and well ramming in layers not exc. 25cm in any type soil complete all as specified and directed. |
| 14 | Removing of surplus excavated soil to a distance not exc. 50m and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed. |
| 15 | M/L for brick work with FLY ASH BRICKS(As Per IS-13757(1993) burnt clay fly ash building bricks), (OLD SIZE BRICKS) with width equal to the length of the brick laid dry & flat abutted with each other with gap between adjacent bricks not exc 10 mm over UG cable for protection and complete all as specified & directed. |
| 16 | M/L for sand cushioning to PVC UG cable with approved quality of sand complete all as specified and directed. |
| 17 | Supply & lay GI tubing light grade 80 mm dia bore in protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc complete all as specified and directed. |
| 18 | Cutting of road / hardstanding upto a size not exceeding 20 cms in width and not exceeding 60 cms in depth for laying of LT UG cable protection pipe line making good the disturbed portion so as to match existing finishing or with PCC 1:2:4 type C1 complete all as specified and directed.. |
| 19 | Material and Labour in replacement of straight through joint suitable for LT XLPE cable of size 70 Sqmm 3.5 core armoured 1100 volt grade heavy duty complete all as specified and directed. |
| 20 | Material and Labour in replacement of straight through joint suitable for LT XLPE cable of size 120 Sqmm 3.5 core armoured 1100 volt grade heavy duty complete all as specified and directed. |
| 21 | Material and Labour in replacement of straight through joint suitable for LT XLPE cable of size 95 Sqmm 3.5 core armoured 1100 volt grade heavy duty complete all as specified and directed. |
| 22 | Material and Labour in replacement of straight through joint suitable for LT XLPE cable of size 50 Sqmm 3.5 core armoured 1100 volt grade heavy duty complete all as specified and directed. |
| 23 | Material and Labour in replacement of straight through joint suitable for LT XLPE cable of size 25 Sqmm 4 core armoured 1100 volt grade heavy duty complete all as specified and directed. |
| 24 | Material and Labour in replacement of straight through joint suitable for LT XLPE cable of size 10 Sqmm 2 core armoured 1100 volt grade heavy duty complete all as specified and directed. |
| 25 | M&L for earthing complete with galvanized steel earth plate 600 x 600 x 6 mm thick, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized iron wire 4 mm as earthing lead by means of bolts, nuts, check-nuts, and washers of galvanized iron or steel besides welding at all joints as shown in drawings and including excavation and earth work, GI pipe light grade 15 mm bore for protection of GI wire from earth electrode to and including the earth test point of galvanized Iron/steel of size 75 x 75 x 25 mm, supplying and laying charcoal dust, common salt, PCC 1:2:4 type B-1 chamber and MS angle iron frame 40 x 40 x 3 mm and RCC cover 40 mm thick (1:2:4) type B-1 using 20 mm graded stone aggregate reinforced with 6 mm dia round bars @ 75 mm C/C both ways with MS handle 12 mm dia, GI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in Plate No. 3 of SSR Part I of 2009 and connected to earth test point including testing complete all as specified & directed. |
| 26 | S&F in repair street light bracket made to shape at required angle made out of 32 mm dia (light grade)/suitable size for fitting of security light GI tubing of length not less than 1.2 mt long suitable for fixing /holding street light fittings including mild steel flat iron 32 x 3 mm clamp 02 Nos with bolts, nuts and washer complete all as specified and directed. |
| 27 | M&L for galvanized steel tubing light grade of 40mm bore with & including all fittings complete all as specified and directed. |
| 28 | Supply, installing and testing out door wheather proof bus bar chamber of size 60cmx45cmx45cm made out of 3.15mm MS sheet having two side openable hinged door shutter with locking arrangement &provn of two Nos 60cm long 50x50x6mm angle iron legs welded and 4 Nos Aluminium bus bar of 200 Amp rating and incoming MCCB 100 Amps,25KA,4 pole,415 Volt adjustable thermal magnetic release type complete errected on ground with necessary PCC 1;3;6 type C-2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland, lugs/thimbles complete all as specified and directed. (a) Incoming MCCB 100 Amps, 25KA, 4 pole, 415 Volt adjustable thermal magnetic release type-01 Nos(b) Indication Lamp-01 Set(c ) Voltmeter with Selector Switch 0-500V-01Nos(d) Ammeter with selector Switch 0-500 Amp -01 Nos(e) MCCB 4 Pole 63 Amp,440 Volts 25 KA-01 Nos (Outgoing)(f) Space and MCB Channel for 20 Nos MCB SPN |
| 29 | Supply, installing, testing and commissioning factory made, floor mounted outdoor type LT feeder panel board, cubicle type, of size 120cm X 100cm X 50cm suitable for 415 Volts, 3 Phase, 4 wire, 50 Hz, AC supply system, and tested at CPRI, having bus bar chamber with insulated Aluminium bus bar of 800 amps four wire system, colour coded for each phase and neutral, insulated on epoxy type insulators. The bottom of the outer shell contains a detachable plate having provn for entry of cable of adequate size with glands, The panel shall be dust and vermin proof, IP-65 class protection and made 3.2 mm CRCA MS sheet, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, both side opening type, including internal wiring with PVC insulated solid copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size (but not less than 2.5 sqmm) including grouting of panel 45 cm above ground level by providing 90 cm long angle iron frame of size 50x50x6 mm, welded on all the four corners, embedded in pcc 1:2:4 using 20 mm stone aggregate upto 30 cm above ground level complete all as specified and directed including the following accessories :- INCOMING(i) Adjustable thermal magnetic MCCB 4 pole 630 Amps, 36 KA - 01 Nos(ii) Digital Combined Ammeter & Voltmeter (10/0-400/500)A/V rating - 01 Nos(iii) Aluminium bus bar 800 Amps with insulator - 04 Nos(v) Instrument control fuses and indication lamp (RYB). OUTGOING(i) Adjustable thermal magnetic MCCB 3 pole, 500 Amps 36 KA - 01 Nos ( + One space for 01 No MCCB) (ii) Adjustable thermal magnetic MCCB 3 pole, 100 Amps 25 KA - 03 Nos(iii) Adjustable thermal magnetic MCCB 3 pole, 80 Amps 25 KA - 01 Nos |
| 30 | All as per srl item No. 29.00 but for bus bar of capacity 600 amps, incoming and outgoing capacity are as under :-INCOMING(i) Adjustable thermal magnetic MCCB 3 pole 400 Amps, 36 KA - 01 Nos(ii) Digital Combined Ammeter & Voltmeter (10/0-400/500)A/V rating - 01 Nos(iii) Aluminium bus bar 400 Amps with insulator - 04 Nos(v) Instrument control fuses and indication lamp (RYB).OUTGOING(i) Adjustable thermal magnetic MCCB 3 pole, 160 Amps 25 KA - 02 Nos (ii) Adjustable thermal magnetic MCCB 3 pole, 100 Amps 25 KA - 02 Nos( + One space for 01 No MCCB) |
| 31 | All as per srl item No. 29.00 but for bus bar of capacity 600 amps, incoming and outgoing capacity are as underINCOMING(i) Adjustable thermal magnetic MCCB 3 pole 400 Amps, 36 KA - 01 Nos(ii) Digital Combined Ammeter & Voltmeter (10/0-400/500)A/V rating - 01 Nos(iii) Aluminium bus bar 600 Amps with insulator - 04 Nos(v) Instrument control fuses and indication lamp (RYB).OUTGOING(i) Adjustable thermal magnetic MCCB 3 pole, 250 Amps 36 KA - 01 Nos (ii) Adjustable thermal magnetic MCCB 3 pole, 160 Amps 25 KA - 02 Nos(iii) Adjustable thermal magnetic MCCB 3 pole, 100 Amps 25 KA - 01 Nos |
| 32 | Supply Installation Testing and Commissioning in replacement of Lithium based Solar LED Security light System with built in Battery and PV Panel and LED lamp in FRP/Aluminium body including taking down of old unserviceable light fitting of any size/capacity complete all as specified and directed. System Comprises Followings”. 1. PV Panel 30W Monocrystalline.2. Lithium Cell for back up 15.4AH with inbuilt BMS. 3. High brightness W-LED lamp 16W, CRI>700, CCT6500K. 4. Microcontroller based charge controller cum driver with automatic dimming function, Dusk to Dawn Operation. 5. Working temperature: (-) 10°C to (+) 55°C. System should be supplied with adjustable MS clamp and 40mm dia arm suitable for pole/wall mounting complete with satisfaction of Engineer In Charge. |
| 33 | S& F of decorative colour light of 3 mtr length having pole material GI PU painted pipe and light material as polycarbonate acrylic of lenth as per halonix cat part no HLDC-45-75-TRI-3M with rated voltage and frequency 240v 150 hz system voltage 75 watt +- 10% system current <0.382 mA power factor > 0.90 colour output suffron,white and green (tiranga colour with same sequence) and driver efficiency >=80 % base plate of the pole light shall be of dia 300 mm and thickness 12 mm PCB hole 260mm dia & 25 mm dia light shall be mounted on a half feet pcc plaster properly fixed with plate and foundation bolt complete all as specified and directed. |
| 34 | Supply,installation,commissioning and testing in replacement high intensity type LED based street light of 90 watt rating new generation energy generation and environmental friendly long life versatile pressure die cast aluminium IP-65/66 roadway luminaire with high power LED as light source complete with all fittings,No of lens -02 ,10000 > lumens and prewired complete all as specified and directed. |
| 35 | S&F in replacement gate light of Globe shaped post top lantern in frosted finish made out of polycarbonate including suitable for upto 27w retrofit LED including taking down of old U/S globe complete all as specified and directed. |
| 36 | S & F in replacement Garden light BAMBOO Type fitting LED 9 W including LED lamp and necessary PCC work/FI nuts, bolts for mounting the fitting complete all as specified and directed by Engineer-in-Charge including taking down U/S light any type any size . |
| 37 | Supply and fix in replacement Intelligent, flexible & smart outdoor lighting control unit for automatic switch ON at dusk automatic switching OFF at Dawn with Astronomical Time Switch, high voltage and low voltage protection, 3 Pole / 230V For 12 KW load equally distributed over 3 phases. Minimum IP54 Degre of Protection complete all as specified and directed. |
| 38 | Material and labour in replacement for circuit /sub main wiring from junction box to street light fitting complete with 1.5 sqmm 3 core PVC insulated and PVC round sheathed multistranded copper conductor flexible industrial cable 1100 V grade drawn through PVC conduit in street light poles complete all as specified and directed. NOTE :- Cost of Necessary tools and plants such as ladders, hydra for connection to street light fittings etc should be deemed to be included in the unit rate quoted. |
| 39 | M&L in replacement LT Cable junction box outdoor shall be made out of Polycarbonate with glass fiber reinforced and size should be not less than 225mm x 295mm x 122 mm(upto Cable Size 35/50sq.mm). The Polycarbonate Junction Box shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive. The Junction Box shall be rated for Degree of ingress Protection IP 66/69 in accordance with IEC 60529.Weatherproof, UV-resistant, rainwater-proof, temperature-resistant. The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22 & IEC 60670 - 2 - 5. The Junction Box with Connectors or Terminal Trip or Bus Bar. The manufacturer of Junction Box / Enclosure shall submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested at Glow Wire test for 960 degree Centigrade & Current Carrying Capacity upto 102Amps. The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector and one no. MCB SP 'B' curved 6-32 Amp and chromium plated clamps and nut bolts, Glands complete all as per manufacturer’s instructions.Make : Cat Part :- KF 3500 B of Hensel/Siemens/GE Power/Rittal or equivalent. Please Enable Macros to View BoQ information |