| 1 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 45watt complete with minimum 120lum/watt, input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3 core through copper connectors from junction box to security lights, complete all as specified and directed. |
| 2 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP-65 power consumption 70/72watt with minimum 120lum/watt, complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3 core through copper connectors from junction box to security lights, complete all as specified and directed. |
| 3 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 90watt minimum 120 lum / watt, complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3 core through copper connectors from junction box to security lights, complete all as specified and directed. |
| 4 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 120watt with minimum 120lum/watt complete, input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x3 core through copper connectors from junction box to security lights, complete all as specified and directed. |
| 5 | Excavation in trenches not exceeding 1.5m wide and not exceeding 10 Sq.m on plan area and not exceeding 1.5m deep in any type of soil, for laying of cable/pipes etc., including taking out old bricks and separating serviceable & unserviceable bricks, cleaning & stacking serviceable bricks for re-use, complete all as specified. |
| 6 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick of excavated soil, as in any type of soil, complete all as specified. Note: A deduction of 10% shall be made from total computed volume of filling to cater in bulk irrespective of machinery used for ramming. |
| 7 | Removal of excavated material [Soil] to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point, complete all as specified. |
| 8 | S&F IN REPAIR Un-reinforced Precast Cement Concrete Cable Covers, Class LV, Type - 1 flat, size 250mm X 150mm X 40mm in trenches for cable protection, embossed with \\"ELECTRIC\\" on the top surface, complete all as specified and as directed. |
| 9 | M&L for Dry & clean sand cushioning in two layers, first layers of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable, levelled and punned down to a depth of 100mm above the top of the upper-most cable, for cable protection in trenches, complete all as specified and as directed. Note: The punned down thickness shall be measured for payment. |
| 10 | M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete for poles all as specified and directed by Engr-in-Charge. |
| 11 | M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge. |
| 12 | M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge. |
| 13 | S&F IN REPAIR GI pipe light grade pipe 25mm dia for cable protection, laid in trenches /pole / walls / road etc., complete all as specified. |
| 14 | S&F IN REPAIR GI pipe light grade pipe 50mm dia for cable protection, laid in trenches /pole / walls / road etc., complete all as specified. |
| 15 | S&F IN REPAIR GI pipe light grade pipe 80mm dia for cable protection, laid in trenches /pole / walls / road etc., complete all as specified. |
| 16 | S&F IN REPAIR GI pipe light grade pipe 100mm dia for cable protection, laid in trenches /pole / walls / road etc., complete all as specified. |
| 17 | M&L for Cutting of road up to 0.75m deep suitable for laying underground cables /GI tubes of any size / dia including GI pipe of 50mm dia & making good the disturbed area with 200mm thick PCC 1:2:4 type B1 to match with the existing level, with and including removing the surplus soil to a distance upto 50m, complete all as specified and directed. |
| 18 | Supply, laying, testing and commissioning of LT XLPE insulated, screened with extruded PVC inner sheathed, PVC bedded, galvanised steel strip armoured electric power cable [heavy duty] of size 3.5core x 95.0Sqmm, with stranded aluminium conductor, 1100 volts grade, suitable for earthed system with and including cable glands, ferrules and connected accessories, laid in trenches or ducts or through the pipe etc., including taking down old u/s cable, complete all as specified. Note: Necessary excavation & earth work, brick protection & sand cushioning shall be measured and paid separately under respective items. |
| 19 | All as per Serial Item No. 18 here-in-before but for cable of size 3.5core x 150.00Sqmm. |
| 20 | All as per Serial Item No. 18 here-in-before but for cable of size 3.5core x 70.00Sqmm. |
| 21 | All as per Serial Item No. 18 here-in-before but for cable of size 3.5core x 50.00Sqmm. |
| 22 | All as per Serial Item No. 18 here-in-before but for cable of size 4.0core x 35.00Sqmm. |
| 23 | All as per Serial Item No. 18 here-in-before but for cable of size 4.0core x 16.00Sqmm. |
| 24 | All as per Serial Item No. 18 here-in-before but for cable of size 4.0core x 10.00Sqmm. |
| 25 | Supply and laying in repair DWC HDPE Pipe 40mm dia, with ISI marked (IS 14930 Part-1&2), laid in trenches / floors & fixed on wall/ pole with and including necessary fittings such as bends, sockets & other connected accessories etc for laying of electric cables / road crossings etc., complete all as specified. |
| 26 | Supply and laying in repair DWC HDPE Pipe 60mm dia, with ISI marked (IS 14930 Part-1&2), laid in trenches / floors & fixed on wall/ pole with and including necessary fittings such as bends, sockets & other connected accessories etc for laying of electric cables / road crossings etc., complete all as specified. |
| 27 | Supply & Lay reinforced concrete pipe of 120 mm dia, 2 nos half round for bottom and top and before laying, excavated area shall be levelled all as directed by Engr-In- Charge. Note: One half round Top and One half round bottom together will be considered as one running meter. |
| 28 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP-66 power consumption 100watt with minimum 120lum/watt, complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3core through copper connectors as requirement at site, complete all as specified and directed. |
| 29 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 150watt with minimum 120 lum / watt complete, input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3core through copper connectors as requirement at site, complete all as specified and directed. |
| 30 | S&F IN REPAIR new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 200watt with 120 lum / watt complete, input voltage of 150-240 Volt (nominal rated voltage 240 Volt) including pvc coated twisted copper cable 1.5 sqmm x 3 core through copper connectors as requirement at site, complete all as specified and directed. |
| 31 | M&L for Steel tubular swaged pole complete with MS base plate, finial taper plug, bolts, nuts and screws all as specified type 410 SP-31 (9m long) as per IS-2713 (Part-III) of 1980 and applying three coats of black bituminous paint through out internally and two coats externally on the portion embedded in concrete and applying two coats of aluminium paint over a coat of zinc chrome primer to the exposed surfaces and numbering poles with synthetic enamel paint as directed, including dismantling existing u/s street light pole of any type after disconnecting electrical connections and making good the disturbed surface, complete all as specified and as directed. Note: Necessary Earth work & Excavation and concrete shall be measured and paid separately under respective items. |
| 32 | S&F IN REPAIR Factory Fabricated Street light GI pipe bracket made out of 32/40mm boer dia light grade GI pipe of minimum 1.5m in length, bent to required shape, fixed with 2 sets of MS clamps made out of FI 40x4mm with nuts & bolts and washers etc., applying two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified. |
| 33 | S&F IN REPAIR Loop in Loop Junction box of size 300x 200x125mm, made out of SMC / FRP with IP 65 protection of thermoplastic circuit breaker boxe suitable for with metric knock outs for cable entry and exit, comb climate Cable Glands of IP66/IP67 for cable entry and Grommets IP 65 for conduit for cable exit with 01 No of MCB, 230Volt, 06Amp, 10KA, 'C' Curve overload and short Circuit protection, with 4 way connector, terminals as bus terminals for cable, for controlling the street light complete clamped to the pole with and including MS clamp made out of flat iron of size 25mm x 3 mm thick fixed with MS nut, bolts and washers including providing the electrical connection for incoming / outgoing cable through proper lugs/thimbles complete all as specified and as directed.all as specified and directed. |
| 34 | M&L for IN REPAIR Earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 4mm GI wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-I, including excavation / earth work in any strata, adequate quantity of charcoal and common salt, PCC chamber with RCC 1:2:4 type B1 40mm thick cover slab with 8mm dia TMT bars @150mm c/c in bothways, suitable handle and angle iron frame of suitable size to fix the cover, with 20mm bore GI pipe light grade for watering with funnel, wire mesh and 15mm bore GI pipe medium grade for GI wire protection and 4mm GI earth wire, including testing after completion, complete all as specified and directed. Note : Earth wire will be measured after 7.5mtr from the earth strip or earth testing terminal block whichever is lesser under relevant item. |
| 35 | Supply, install and testing for maintenance free chemical earthing of dual pipe technology of 3mtr long with outer pipe dia 88mm and inner pipe dia 48mm, the pipes are properly galvanised for 80-120 micron and wall thickness of inner pipe 3 mm and 2 mm of outer pipe with copper coating on outer surface, terminal for connection of 75mm x 6mm with 2 holes of 14 mm dia, fast electrode filled with highly conductive material with sealing at boath ends with lead terminal of 75mm x 6mm at top along with 2 bags of 25Kgs each of earth enhancing compound of PH value 7-8 duly tested and certified by any international accredited NABL / BIS accredited laborartory with reffering to protocol IS 1350 and IEC 62321/111/54/CDV. The content of mercury and hexa chromium should be below detection level. The electrode should be tested for salt spray test as per BIS 117-09 for corrosion for minimum 500 Hrs. The electrode should be duly tested and certified by CPRI for a min short circuit current of 42k amps for 1 Sec with initial pick of 8.2K amp, connected to copper strip 20mm x 3.15mm thick earth strip by means of bolts, nuts, check nuts and washers of copper with 40mm dia medium grade Gl pipe as a protection up to 7.5m long and RCC pit with cover and connected to earthing test point, including testing on completion, complete all as specified and as directed. |
| 36 | S&F & testing commissioning of outdoor type bus bar panel pedestal type weather proof CPRI approved CRCA cubical panel board of size 110cm x 80cm x 40cm, 4 Nos of bus bar of 300Amp capacity & MCCB 200Amp capacity 4 pole (Ics = Icu = 100%) 25kA, made with CRCA sheet thickness 3.15mm with and including applying one coat of red oxide primer and two coat of enamel paint powder coated paint, mounted on suitable mild steel channels and PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator, complete all as specified and as directed. |
| 37 | S&F & testing commissioning of outdoor type bus bar panel pedestal type weather proof CPRI approved CRCA cubical panel board of size 110cm x 80cm x 40cm, 4 Nos of bus bar of 300Amp capacity & MCCB 160Amp capacity 4 pole (Ics = Icu = 100%) 25kA, made with CRCA sheet thickness 3.15mm with and including applying one coat of red oxide primer and two coat of enamel paint powder coated paint, mounted on suitable mild steel channels and PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator, complete all as specified and as directed. |
| 38 | Taking out under ground, LT cables, different sizes, by excavation and earth work in any type of soil, removing bricks or PCC tiles of any size, re-laying in the same trenches or re-routing after rectification of fault as required complete all as specified and directedNOTE:- (i) Joints & Jointing materials, new cable, additional bricks/PCC Covers, sand shall be measured & paid for separetely.(ii) Retrieved serviceable bricks or PCC cable cover and sand shall be re-laid on the cable & the cost for the same is deemed to be included in the unit rate. |
| 39 | S&F IN REPAIR MCCB, 04 Pole, capacity 40 Amps with ultimate breaking capacity 16kA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site, complete all specified and directed. |
| 40 | Description all as per item No 39 here in above but of capacity 63 Amps with ultimate breaking capacity 16 KA . |
| 41 | Description all as per item No 39 here in above but of capacity 100 Amps with ultimate breaking capacity 25 KA . |
| 42 | Description all as per item No 39 here in above but of capacity 160 Amps with ultimate breaking capacity 25 KA. |
| 43 | Description all as per item No 39 here in above but of capacity 200 Amps with ultimate breaking capacity 25 KA . |
| 44 | Description all as per item No 39 here in above but of capacity 250 Amps with ultimate breaking capacity 35 KA. |
| 45 | Description all as per item No 39 here in above but of capacity 315 Amps with ultimate breaking capacity 35 KA . |
| 46 | Description all as per item No 39 here in above but of capacity 400 Amps with ultimate breaking capacity 35 KA |
| 47 | M&L for Painting of steel tubular 11/9 mtr poles any type complete incl flat iron clamps, D clamps, Stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint including preparation old painted surface initially & applying one coat of red oxide, applying two coat of aluminium paint over the red oxide, marking with alternate BLACK and YELLOW strips of width 15cm each and height 60cm from base, 4 Nos strips with two coat of synthetic enamel paint and also including numbering of poles with circular shape black paint and white colour letters / numbers are located on different locations complete all as specified and directed by Engr-in-Charge. |
| 48 | M & L for Painting of steel cross arm, bracing supports of 11/9 mtr PCC poles any type incl flat iron clamps, D clamps, stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint incl prepration old painted surface and applying cemente based paint over cemented portion of PCC poles, marking with alternator white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint, numbering of poles complete all as specified and directed. |
| 49 | M & L for Painting of PCC Coping of steel/ RCC street light pole with white color after removal of fungus complete all as specified and directed. |
| 50 | S&F IN REPAIR LED Post Top outdoor type fitting 15Watt, 230 volts, >100lum/W, with decorative post top for beam angle of ǿ 360°, AC outdoor type with high Pressure Die Cast aluminum Housing and heat resistant toughened glass with frame complete with LED bulb /lamp 15Watt, driver with impact and corrosion resistant complete with IP 65/66 protection, complete all as specified and as directed. Make: Cat Part No. RUBYMINIPT15W LED757 PSYMTOPC of Havells or Equivalent make as specified here-in-after. |
| 51 | S&F IN REPAIR LED drivers of LED street light /flood light of any make , of capacity 30 watts to 60 watts including replacement of burnt drivers WITH BIS certified, RoHS complied suitable to mount in street light housing, complete all as specified and as directed |
| 52 | Description all as per item no. 51 above but 70 watts to 90 watts and ditto- |
| 53 | Description all as per item no. 51 above but 100 watts to 150 watts and ditto- |
| 54 | Cutting / trimming of tree branches of any girth all around the street light over head lines upto two mtr from all around the over head lines complete and removing the cut branches from site to a distance not exc 50 mtr, complete all as specified. |
| 55 | S&F IN REPAIR MCB TPN 63Amp, 10kA, 230Volt, C curve with necessary connecting up in MCB DB, testing and commissioning, complete all as specified and as directed. |
| 56 | S&F IN REPAIR 1100 Volts grade heavy duty ISI marked cable PVC insulated stranded aluminium conductor one twin core cable flat or circular of size 06 sqmm served with inner sheathing of PVC tape & overall PVC sheathed in service connections etc complete all as specified and direcetd. |
| 57 | S&F IN REPAIR 1100 Volts grade heavy duty ISI marked cable PVC insulated stranded aluminium conductor one twin core cable flat or circular of size 04 sqmm served with inner sheathing of PVC tape & overall PVC sheathed in service connections etc complete all as specified and direcetd. |
| 58 | S&F IN REPAIR FRLSH PVC insulated sheathed, multi standard, copper conductor cable of size 3.0 core x 1.5Sqmm, 1100 volts grade and including cable glands, ferrules and connected accessories, multi stranded 1100 Volt grade confirming to IS 694: 1977, for electric connection from pole / junction box to street light, complete all as specified and as directed. |
| 59 | S&F IN REPAIR LT Panel as per IEC 61439, Outdoor type, floor mounted free standing dust and vermin proof panel / DB with IP-55 protection, CPRI approved OEM, frame fabricated out of 40mmx40mm x 4mm MS angle iron, made with 3.15mm thick CRCA sheet for entire outer panel and 1.6mm thick CRCA sheet 40mmx4mm MS flat Iron for inner compartments with separate cubicle chamber with cable alley with minimum 300mm width for installation/connecting switchgears with the main bus bar using aluminium bus link or copper conductor flexible wires suitable for switch rating and connecting outgoing terminals of the switchgear with terminal blocks of appropriate current rating using flexible copper wires duly terminated by cable lugs and thimbles, MS surfaces epoxy based powder coated, shade as approved over 2 coats of red oxide primer, surfaces pre-treated in seven tank process for de-greasing, de-rusting & Phosphated, panel having front and rear opening and provision for installation of separate cable alleys, all MCCBs must be have thermal magnetic relrase, busbar chamber and switchgear compartments, provision in cable alleys for bottom cable entry for incoming & outgoing cables, fixing danger notice plate, with and including erection, testing and commissioning, complete all as specified and directed including the following fixtures and fitments:- |
| 60 | (a) Aluminium bus bar four strips 400 Amps, 415 volts, fixed on epoxy insulated with panel fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set. (b) Incoming:- MCCB 04 Pole, 200 Amps with ultimate breaking capacity Icu- 35 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 No (Ics=Icu=100%) (c) Outgoing:-MCCB 04 Pole, 100 Amps with ultimate breaking capacity Icu- 25 KA at 415 volts , adjustable type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 No (Ics=Icu=100%) (g) Analoge type volt meter 0-500 volt - 1Set., Indication lamps R,Y,B LED type with 3 Nos – 1 set, Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's. Note :- Panel drawings & make of MCCB/SDFU will be submitted by contractor for approval of GE before ordering the panel. |
| 61 | all as per item no 59 butBusbars:-TPN-Not less than 660 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set.Incoming:- (i) MCCB 400 A, 4 Pole, 50KA with adjustable electronic release (with release range 300-400A) - 01 No., (ii) DG incomer 400 amp 50 ka (with adjustable electronic release)-01 (iii) change over switch on load 4 pole 400 amp -1(ii) CT's 400/5 -03 No., (iii) Ampere Meter 0 - 400 A digital type with selector switch -01 No. (iv) Ammeter-01 No., (v) Voltmeter with selector switch -01 No.(vi) Phase Indicating lamps -03(vii) Control fuses / MCB -03 No. |
| 62 | Outgoing:-(i) MCCB, 4 pole 160 A, 16 KA, thermal magnetic release 160-200 Amp = 02 No (ii) MCCB, 4 pole 200 A, 16 KA, thermal magnetic release 160-200 Amp = 02 No(ii) MCCB 4 POLE 100 AMP 16 KA-3 no. (iii)MCCB 4 POLE 63 AMP -3 no . Make of MCCB: L&T / Seimens / Schneider /indoasian |
| 63 | All asper item no 59 butBusbars:-TPN-400 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set.Incoming:- (i) MCCB 160 A, 4 Pole, 50KA with adjustable electronic release (with release range 300-400A) - 01No. (ii) CT's 200/5 -03 No., (iii) Ampere Meter 0 - 200 A digital type with selector switch -01 No. (iv) Ammeter-01 No., (v) Voltmeter with selector switch -01 No.(vi) Phase Indicating lamps -03(vii) Control fuses / MCB -03 No. Please Enable Macros to View BoQ information |
| 64 | All asper item no 59 butBusbars:-TPN-400 A, Aluminium bus bars E91 grade, 1100 volts grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets and covered all around by insulating/CRCA sheet having no exposed portion. Bus bar chamber to be selected so that it provides gap between Bus bar and heat dissipation conforming to IS standard -1 set.Incoming:- (i) MCCB 160 A, 4 Pole, 50KA with adjustable electronic release (with release range 300-400A) - 01No. (ii) CT's 200/5 -03 No., (iii) Ampere Meter 0 - 200 A digital type with selector switch -01 No. (iv) Ammeter-01 No., (v) Voltmeter with selector switch -01 No.(vi) Phase Indicating lamps -03(vii) Control fuses / MCB -03 No. Please Enable Macros to View BoQ information |