| 1 | CRE - SUPPLY, INSTALLATION , TESTING , COMMISSIONING & VALIDATION |
| 2 | CEILING SUSPENDED LAMINAR AIR FLOW UNIT (CLAF) - S. I.T.C & V |
| 3 | Supply,installation, testing, commissioning and validation of Ceiling Suspended Laminar Air Flow Unit (CLAF) conforming to ISO 14644-1 Class 5 (Grade A) . The unit shall be of the recirculating, vertical unidirectional airflow type, designed for ceiling suspension with a heavy-duty SS 304 Grade (minimum 1.2 mm) structural hanging framework with mirror-polished finish as per site requirement.The scope of work and per-unit costing shall include the SITC of the accessories listed below; quantities of accessories per unit shall be determined in accordance with standard design requirement: Double-width double-inlet (DIDW) forward-curved centrifugal blower. The pre-filtration stage shall consist of a 5-micron EU5-grade pre-filter. The terminal HEPA filter shall be H14 Grade as per EN 1822. LED lamp shall be provided with minimum ≥500 LUX at work surface, The control panel enclosure shall be fabricated from SS 304 Grade, minimum 1.5 mm thick sheet, 240 grit electropolished finish with a satin matt surface, IP54 rated or better, with all edges and corners radiused for cleanability. The panel shall house and integrate the following functional elements: The unit shall be fitted with magnehelic differential pressure gauges for HEPA filter range 0–500 Pa—with high and low pressure alarm indication and visual/audio alert for filter choke, all inclusive of pnenumatic tubing. A Feather-touch ON/OFF switch panel with HMI-type controls for blower, . A Poly Alpha Olefin (PAO) upstream test port shall be provided for HEPA filter integrity testing. Atmospheric pressure port shall also be provided. Air velocity sensing device shall be provided with display on control panel, Speed controller for blower motor shall be of solid-state type. Blower failure visual and audio alarm indication shall be provided. An emergency stop switch (mushroom-head, lockable, IP55) shall be incorporated. The interconnecting pipe between CLAF and control panel shall be of SS304, Electrical supply shall be 230V, 1 Phase, 50 Hz with MCB protection. Hanging arrangement shall be designed for safe working load with minimum 4 suspension points and shall be approved structurally. All works shall include mechanical fixing, electrical connections to existing DB, pneumatic tube connections for gauges, levelling and alignment. Testing and commissioning shall include installed HEPA filter integrity test, non-viable particle count, airflow velocity uniformity and pattern test, pressure drop verification across each filter stage, lux level measurement, sound level measurement. Validation documentation (DQ, IQ, OQ) shall be submitted as per HBL approved format. |
| 4 | BCG Block |
| 5 | Size (Overall) in mm: 2260 x 3065 x 650 - SITC |
| 6 | Size (Overall) in mm: 2260 x 965 x 650 - SITC |
| 7 | Size (Overall) in mm: 1100 x 1400 x 650 - SITC |
| 8 | VVF Block |
| 9 | Size (Overall) in mm: 2590 x 1250 x 650 - SITC |
| 10 | Size (Overall) in mm: 2590 x 1350 x 650 - SITC |
| 11 | CRE - INSTALLATION , TESTING , COMMISSIONING & VALIDATION |
| 12 | CEILING SUSPENDED LAMINAR AIR FLOW UNIT (CLAF) - I.T.C & V |
| 13 | Installation, testing, commissioning and validation of Ceiling Suspended Laminar Air Flow Unit (CLAF) conforming to ISO 14644-1 Class 5 (Grade A) . The unit shall be of the recirculating, vertical unidirectional airflow type, designed for ceiling suspension with a heavy-duty SS 304 Grade structural hanging framework with mirror-polished finish as per site requirement. The unit shall incorporate a double-width double-inlet (DIDW) forward-curved centrifugal blower. The pre-filtration stage shall consist of a 5-micron EU5-grade pre-filter. The terminal HEPA filter shall be H14 Grade as per EN 1822. The unit shall be fitted with magnehelic differential pressure gauges for HEPA filter range 0–500 Pa—with high and low pressure alarm indication and visual/audio alert for filter choke. Feather-touch ON/OFF switch panel with HMI-type controls for blower, LED lamp shall be provided. LED lighting, providing ≥500 LUX at work surface, shall be incorporated. A Poly Alpha Olefin (PAO) upstream test port shall be provided for HEPA filter integrity testing. Atmospheric pressure port shall also be provided. Air velocity sensing device shall be provided with display on control panel, Speed controller for blower motor shall be of solid-state type. Blower failure visual and audio alarm indication shall be provided. An emergency stop switch (mushroom-head, lockable, IP55) shall be incorporated. Electrical supply shall be 230V, 1 Phase, 50 Hz with MCB protection. Hanging arrangement shall be designed for safe working load with minimum 4 suspension points and shall be approved structurally. For the CLAF in the filling area(Qty-01no.), a wiring interlock feature should be incorporated to ensure that the filling machine can be powered ON only when the CLAF is in operation. All works shall include mechanical fixing, electrical connections to existing DB, pneumatic tube connections for gauges, levelling and alignment. Testing and commissioning shall include installed HEPA filter integrity test, non-viable particle count, airflow velocity uniformity and pattern test, pressure drop verification across each filter stage, lux level measurement, sound level measurement. Validation documentation (DQ, IQ, OQ) shall be submitted as per HBL approved format. |
| 14 | BCG Block |
| 15 | Size (Overall) in mm: 3510 x 3984 x 650 - ITC & V |
| 16 | VVF Block |
| 17 | Size (Overall) in mm: 1340 x 1188 x 650 - ITC & V |
| 18 | Size (Overall) in mm: 2113 x 1503 x 650 - ITC & V |
| 19 | Size (Overall) in mm: 2113 x 1503 x 650 - ITC & V |
| 20 | VERTICAL LAMINAR AIR FLOW UNIT (VLAF) - I.T.C & V |
| 21 | Installation, testing, commissioning and validation of a Vertical Laminar Air Flow Unit (VLAF), self-stand providing ISO 14644-1 Class 5 (Grade A) unidirectional vertical down airflow. The unit shall be mounted on SS 304 nylon levelling jacks for mobility. DIDW centrifugal blowers shall be provided. Pre-filters (EU5 grade), HEPA filters (H14) shall be provided. Magnehelic gauges—0–500 Pa for HEPA and 0–250 Pa for pre-filter—shall be mounted on the SS 304 main control panel with high/low pressure alarm indication. LED lighting system shall provide minimum 500 LUX inside the workspace; UV lamp with hour-meter shall be incorporated with sash-position interlock (when front sash is closed, UV lamp ON and LED lamp OFF; when sash is open, UV lamp OFF and LED lamp ON). HMI-type feather-touch ON/OFF switches for blower, LED and UV light with LED indication, speed regulator, blower trip indication (2 Nos.), PAO upstream test port, LED display for motor operation, high and low pressure alarm, front sash SS 304 frame with toughened glass and sash-lifting system, power sockets (5/15A), MCBs for motor protection and blower trip indication shall be incorporated. Emergency stop switch (IP55) shall be provided. Relay for door/sash integration (2 changeover, 12V DC) shall enable the interlocking system. Air velocity sensing device shall be provided with display on control panel. Electrical supply 230V, 1 Phase, 50Hz, power with earthing. Installation scope includes mechanical assembly, levelling verification, electrical connections to existing DB, and commissioning checks. Testing and commissioning shall include PAO/DOP HEPA integrity test, non-viable particle count test, airflow velocity and pattern test, pressure drop measurement, sash interlock functional test, alarm and trip tests, lux and sound level measurements. Validation documentation (IQ, OQ) shall be prepared and submitted in HBL approved format |
| 22 | BCG Block |
| 23 | Size (Overall) in mm: 1650 x 820 x 2025 - ITC & V |
| 24 | Size (Overall) in mm: 1650 x 820 x 2025 - ITC & V |
| 25 | CRE - TESTING , COMMISSIONING & VALIDATION |
| 26 | CEILING SUSPENDED LAMINAR AIR FLOW UNIT (CLAF) - T.C & V |
| 27 | Testing, commissioning and validation of Ceiling Suspended Laminar Air Flow Unit(s) (CLAF) already installed at site. Prior to testing, the contractor shall conduct a thorough visual inspection of the installed units for structural integrity, fastener tightness, suspension arrangement safety, filter housing seal condition, electrical wiring integrity, earthing continuity, blower condition, general cleanliness and the unit to be serviced where required. The units shall be powered up and checked for correct direction of rotation and absence of abnormal noise or vibration. Testing shall be carried out as per ISO 14644-3 and WHO GMP guidelines. The testing programme shall include: (a) HEPA filter integrity (b) Non-viable particle count at the working zone (c) Air velocity measurement at defined grid points on the HEPA face (d) Airflow pattern visualisation by smoke test (e) Pressure drop measurement across HEPA and pre-filter using magnehelic gauges; (f) Recovery test (if applicable) to Grade A at rest; (g) Lux level measurement at the working plane (minimum 500 LUX); (h) UV light intensity measurement ; (i) Functional test of all alarms (high/low pressure, blower failure), interlocks, emergency stop, and feather-touch switches. Any deficiencies or non-conformances identified during testing shall be reported and rectified before validation acceptance. For the CLAF in the filling area(Qty-01no.), a wiring interlock feature should be incorporated to ensure that the filling machine can be powered ON only when the CLAF is in operation.Validation documentation (IQ review/as-found and OQ as applicable) shall be prepared and submitted as per HBL format. |
| 28 | BCG Block |
| 29 | Size (Overall) in mm: 2595 x 1320 x 650 - TC & V |
| 30 | Size (Overall) in mm: 1630 x 1730 x 650 - TC & V |
| 31 | VVF Block |
| 32 | Size (Overall) in mm: 3058 x 1950 x 650 - TC & V |
| 33 | Size (Overall) in mm: 1807 x 883 x 650 - TC & V |
| 34 | Size (Overall) in mm: 1824 x 750 x 650 - TC & V |
| 35 | Size (Overall) in mm: 1990 x 1675 x 650 -TC & V |
| 36 | Size (Overall) in mm: 3510 x 4026 x 650 - TC & V |
| 37 | MOBILE LAMINAR AIR FLOW UNIT (MLAF) - T.C & V |
| 38 | Testing, commissioning and validation of Mobile Laminar Air Flow Unit(s) (MLAF) already installed or positioned at site. Prior to testing, the contractor shall perform a pre-commissioning inspection covering structural condition of the mobile cabinet, castor wheel and locking brake functionality, door seal and interlock condition, filter housing seal condition, blower motor wiring, inverter/UPS and battery connection integrity, magnehelic gauge zero verification and earthing continuity, general cleanliness and the unit to be serviced where required. Testing programme shall include: (a) HEPA filter integrity test (b) Non-viable particle count (c) Air velocity measurement at HEPA face grid points (d) Airflow pattern test (e) Pressure drop measurement across HEPA (f) Lux level measurement (≥500 LUX) (g) UV intensity measurement and hour-meter function verification (h) Door interlock functional test confirming UV lamp switches OFF and CFL lamp switches ON upon door opening (i) Battery backup/inverter test confirming minimum 1 hour runtime at rated load (j) Functional test of alarms (blower failure, pressure alarms), emergency stop and ON/OFF switches. Any non-conformances shall be documented and rectified prior to validation sign-off. Validation documentation (IQ as-found review and OQ) shall be prepared and submitted as per HBL approved format. |
| 39 | BCG Block |
| 40 | Size (Overall) in mm: 1730 x 700 x 1900 - TC & V |
| 41 | VVF Block |
| 42 | Size (Overall) in mm: 1430 x 700 x 1900 - TC & V |
| 43 | Size (Overall) in mm: 1730 x 700 x 1900 - TC & V |
| 44 | VERTICAL LAMINAR AIR FLOW UNIT (VLAF) - T.C & V |
| 45 | Testing, commissioning and validation of Vertical Laminar Air Flow Unit(s) (VLAF) already installed or assembled at site. The contractor shall first carry out a pre-commissioning inspection of the VLAF covering: overall structural assembly integrity; levelling jack verification; front sash condition, alignment and lifting mechanism; toughened glass side panel seating; work table (SS 316L perforated) condition; SS pipe support integrity; blower motor connections; control panel wiring verification; magnehelic gauge mounting and tube connections; earthing continuity and MCB rating verification, general cleanliness and the unit to be serviced where required. Testing programme shall include: (a) HEPA filter integrity test (b) Non-viable particle count (c) Air velocity measurement (d) Airflow pattern visualisation (e) Pressure drop measurement across HEPA and pre-filter (f) Recovery test to Grade A at rest conditions (g) Lux level measurement (minimum 500 LUX at work surface per design requirement) (h) Vibration measurement (i) Sash interlock functional test — when sash closed: UV ON, LED light OFF; when sash open: UV OFF, LED light/blower ON (j) Air velocity sensor display verification against calibrated reference anemometer (l) Alarm and trip tests: blower failure alarm, HP/LP alarms across HEPA, emergency stop (k) Speed regulator function verification. Any non-conformances shall be documented, rectified and re-tested. Validation documentation (IQ as-found and OQ as applicable) shall be prepared and submitted as per HBL approved format. |
| 46 | VVF Block |
| 47 | Size (Overall) in mm: 1650 x 820 x 2025 - TC & V |
| 48 | Size (Overall) in mm: 1980 x 820 x 2025 - TC & V |
| 49 | DYNAMIC GARMENT CUBICLE (DGC) - T.C & V |
| 50 | Testing, commissioning and validation of Dynamic Garment Cubicle(s) (DGC) already installed at site. A pre-commissioning inspection shall first be conducted covering: structural assembly and joint integrity; door alignment, seal condition and latch functionality; perforated shelf condition and seating; levelling jack condition and height; filter housing seal condition; blower motor wiring; magnehelic gauge connections; UV lamp condition; hour-meter functionality; interlock wiring and relay condition; earthing continuity, general cleanliness and the unit to be serviced where required. Testing programme shall include: (a) HEPA filter integrity test (b) Non-viable particle count test (c) Air velocity at HEPA face (d) Airflow pattern test (e) Pressure drop measurement across HEPA and pre-filter (f) Lux level measurement at shelf level (minimum 500 LUX) (g) UV intensity measurement and hour-meter verification (h) Door interlock functional test — UV OFF and LED Light ON when door is opened (i) Blower failure alarm functional test (j) Emergency stop functional test. Non-conformances shall be documented, rectified and re-tested. Validation documentation (IQ review and OQ as applicable) shall be prepared and submitted as per HBL approved format. |
| 51 | BCG Block |
| 52 | Size (Overall) in mm: 720 x 865 x 2300 - TC & V |
| 53 | VVF Block |
| 54 | Size (Overall) in mm: 720 x 865 x 2300 - TC & V |
| 55 | FILTERS & ACCESSORIES - SITC |
| 56 | HEPA FILTER - H14 |
| 57 | Supply, Installation, Testing and Commissioning (SITC) of HEPA Filters of grade H14 conforming to EN 1822, having minimum efficiency of ≥99.995% at MPPS, constructed with mini-pleat moisture-resistant, fire-retardant glass fiber media, housed in rigid extruded anodized aluminium frame, with thermoplastic separators and fire-retardant polyurethane sealant, complete with one-piece foamed polyurethane / neoprene gasket suitable for leak-proof sealing, provided with epoxy coated protective face guards on both air entering and leaving sides, suitable for operation at rated face velocity of 0.45 m/s, with initial pressure drop not exceeding 125 Pa, including individual filter leak test certificate and commissioning. |
| 58 | BCG Block |
| 59 | 430 x 940 x 69 (mm) |
| 60 | 458 x 610 x 69 (mm) |
| 61 | 458 x 762 x 69 (mm) |
| 62 | 500 x 980 x 69 (mm) |
| 63 | 580 x 660 x 69 (mm) |
| 64 | 580 x 720 x 69 (mm) |
| 65 | 610 x 610 x 69 (mm) |
| 66 | 610 x 763 x 69 (mm) |
| 67 | 610 x 940 x 69 (mm) |
| 68 | 610 x 1015 x 69 (mm) |
| 69 | 610 x 1178 x 69 (mm) |
| 70 | 650 x 1015 x 69 (mm) |
| 71 | 658 x 1015 x 69 (mm) |
| 72 | 680 x 1050 x 69 (mm) |
| 73 | 686 x 1015 x 69 (mm) |
| 74 | 720 x 1015 x 69 (mm) |
| 75 | 730 x 730 x 69 (mm) |
| 76 | 730 x 870 x 69 (mm) |
| 77 | 744 x 1178 x 69 (mm) |
| 78 | VVF Block |
| 79 | 458 x 610 x 69 (mm) |
| 80 | 580 x 1390 x 69 (mm) |
| 81 | 610 x 610 x 69 (mm) |
| 82 | 610 x 763 x 69 (mm) |
| 83 | 610 x 915 x 69 (mm) |
| 84 | 610 x 1068 x 69 (mm) |
| 85 | 730 x 975 x 69 (mm) |
| 86 | 762 x 915 x 69 (mm) |
| 87 | BLOWER |
| 88 | Supply, installation, testing and commissioning of forward-curved Double Inlet Double Width (DIDW) centrifugal blower suitable for cleanroom Laminar Air Flow applications, with 4-pole single phase motor rated for 230V AC ±10%, 50Hz, 150W, operating speed 1300–1400 RPM, capable of delivering static pressure up to 450 Pa, with impeller size approximately 7” x 7”, direct-driven construction with statically and dynamically balanced impeller ensuring low vibration and noise level not exceeding 60 dB(A) at 1 m, motor with Class F/B insulation, minimum IP20/IP21 protection and inbuilt thermal overload protection, blower housing made of galvanized steel with corrosion-resistant finish, complete with anti-vibration mounts, terminal box for electrical connections, and compatibility for integration with cleanroom equipment control panel, including installation, wiring, earthing as per IS standards, and performance testing. |
| 89 | (DIDW) centrifugal blower @ BCG Block |
| 90 | (DIDW) centrifugal blower @ VVF Block |
| 91 | MAGENEHELIC GUAGE |
| 92 | Supply, installation, testing and commissioning of magnehelic differential pressure gauge of range 0–500 Pa, suitable for monitoring pressure drop across HEPA filters in cleanroom equipment, with accuracy ±2% of full scale, 100 mm dial with clear readable scale and pointer, die-cast aluminium housing with corrosion-resistant finish, capable of withstanding static pressure up to 100 kPa, provided with dual pressure ports compatible with 6 mm pneumatic tubing, suitable for flush panel mounting on SS control panel, with adjustable set-point indicators for filter monitoring and provision for alarm integration, complete with installation, tubing connections and zero setting, |
| 93 | Magnehelic differential pressure gauge of range 0–500 Pa @ BCG Block |
| 94 | Magnehelic differential pressure gauge of range 0–500 Pa @ VVF Block |
| 95 | CONTROL PANEL FOR CLAF |
| 96 | Supply, installation, testing and commissioning of a dedicated control panel for the Ceiling Suspended Laminar Air Flow (CLAF) unit suitable for flush or surface mounting. The control panel enclosure shall be fabricated from SS 304 Grade, minimum 1.5 mm thick sheet, 240 grit electropolished finish with a satin matt surface, IP54 rated or better, with all edges and corners radiused for cleanability. The panel shall house and integrate the following functional elements: (a) Feather-touch capacitive ON/OFF switches for blower and LED light, with embedded LED status indication for each function; (b) Magnehelic differential pressure gauge display section (with provision for 0–500 Pa) with dedicated labelled bezels; (c) Velocity sensor display unit for the air velocity sensor output (d) High and low pressure alarm indicator lamps with audible buzzer; (e) Emergency stop mushroom-head push button (lockable, IP55, red head); (f) F1–F4 selector/function switches (g) ATM (atmospheric pressure port reference) valve push button; (h) HEPA pressure drop indicator label; (i) Blower-fluorescent lamp ON/OFF sub-panel. All including Panel wiring, MCBs, RCCB, earthing etc. Installation includes wall/ceiling mounting (as per site requirement), conduit or flexible cable tray routing of cables to CLAF unit, earth bonding, and commissioning verification of all functions. |
| 97 | Control panel @ BCG Block |
| 98 | Control panel @ VVF Block |
| 99 | S.S. PIPE FOR CONTROL PANEL |
| 100 | Supply, installation, testing and commissioning of stainless steel conduit/pipe (OD-40mm dia) for routing of electrical cables and pneumatic tubing between control panel and cleanroom equipment, fabricated from SS 304 with smooth electropolished finish suitable for GMP environment, complete with matching SS fittings, bends and supports with vibration-isolated clamps, sized to maintain maximum 40% fill ratio, with IP54-rated SS glands at entry points, installed with proper cutting, bending and fixing on SS supports at suitable spacing, ensuring separation of power and control cables, earthing including testing and inspection |
| 101 | S.S.pipe @ BCG Block |
| 102 | S.S.pipe @ VVF Block |
| 103 | FEATHER TOUCH ON/OFF SWITCH BOARD |
| 104 | Supply, installation, testing and commissioning of feather-touch capacitive ON/OFF switch board for control of blower, lighting and UV systems in cleanroom equipment, comprising multi-channel capacitive touch interface with minimum three outputs for blower (unidirectional flow), LED light and UV light, with LED status indication for each channel and blower trip indication, housed in GMP-compliant SS 304 with smooth, crevice-free finish and minimum IP54 protection, suitable for flush or surface mounting, operating on 230V AC supply with internal relay/solid-state outputs, complete with internal copper wiring, terminal connections, compatibility with control panel, installation, wiring, earthing, and functional testing of all controls and indications. |
| 105 | Feather touch on/off switch @ BCG Block |
| 106 | Supply, installation, testing and commissioning of feather-touch capacitive ON/OFF switch board for control of blower and lighting systems in cleanroom equipment, comprising multi-channel capacitive touch interface with minimum two outputs for blower (unidirectional flow) and LED light, with LED status indication for each channel and blower trip indication, housed in GMP-compliant SS 304 with smooth, crevice-free finish and minimum IP54 protection, suitable for flush or surface mounting, operating on 230V AC supply with internal relay/solid-state outputs, complete with internal copper wiring, terminal connections, compatibility with control panel, installation, wiring, earthing, and functional testing of all controls and indications. |
| 107 | Feather touch on/off switch for CLAF @ BCG Block |
| 108 | Feather touch on/off switch for CLAF @ VVF Block |
| 109 | ATMOSPHERIC PORT |
| 110 | Supply, installation, testing and commissioning of atmospheric reference port (ATM port) for cleanroom equipment, suitable for zero-referencing of differential pressure gauges, fabricated in SS 304 with threaded mounting, compatible with 6 mm PU pneumatic tubing, provided with smooth internal flow path and EPDM/Viton sealing, complete with protective cap to prevent contamination, panel-mounted including installation, tubing connection, and functional verification for accurate zero setting. |
| 111 | ATM port @ BCG Block |
| 112 | ATM port @ VVF Block |
| 113 | POLY ALPHA OLEFIN (PAO) PORT |
| 114 | Supply, installation, testing and commissioning of PAO (Poly Alpha Olefin) upstream challenge port for HEPA filter integrity testing in cleanroom equipment, fabricated in SS 304/316L, provided with threaded or push-to-connect fitting compatible with aerosol generator probes with PTFE/Viton seals and protective cap, installed on upstream plenum with proper sealing/welding, labelled for identification, and complete with leak testing |
| 115 | PAO port @ BCG Block |
| 116 | PAO port @ VVF Block |
| 117 | LED LIGHTS |
| 118 | Supply, installation, testing and commissioning of 2-ft (600 mm) LED light fixture for cleanroom LAF units, rated approximately 9–14W, 230V AC, 50Hz, with IP54-rated housing, providing minimum 500 LUX at working plane complete with electronic driver suitable for flush/surface mounting, wired to control panel with interlock operation, including installation, wiring, earthing and lux level verification. |
| 119 | LED light - 2foot @ BCG Block |
| 120 | LED light - 2foot @ VVF Block |
| 121 | Supply, installation, testing and commissioning of 4-ft (1200 mm) LED light fixture for cleanroom LAF units, rated approximately 18–28W, 230V AC, 50Hz, with IP54-rated housing, providing minimum 500 LUX at working plane complete with electronic driver suitable for flush/surface mounting, wired to control panel with interlock operation, including installation, wiring, earthing and lux level verification. |
| 122 | LED light - 4foot @ BCG Block |
| 123 | LED light - 4foot @ VVF Block |
| 124 | UV LIGHT & HOUR METER |
| 125 | Supply, installation, testing and commissioning of germicidal UV-C lamp assembly with hour meter for cleanroom equipment, comprising low-pressure mercury vapour UV lamp emitting at 254 nm wavelength, providing adequate irradiance for surface decontamination, IP54 protection. complete with UV interlock system ensuring lamp switches OFF when door/sash is open (fail-safe operation), and integrated non-resettable hour meter for monitoring lamp life, including wiring, mounting, safety shielding to prevent UV exposure, and functional testing of interlock and UV intensity. |
| 126 | UV Light - 15W / 1.5 ft. @ BCG Block |
| 127 | UV Light - 30 W / 3 ft. @ BCG Block |
| 128 | UV Light - 15W / 1.5 ft. @ VVF Block |
| 129 | UV Light - 30 W / 3 ft. @ VVF Block |
| 130 | Hour Meter @ BCG Block |
| 131 | Hour Meter @ VVF Block |
| 132 | AIR VELOCITY SENSOR |
| 133 | Supply, installation, testing, and commissioning of air velocity sensor for cleanroom LAF units, garment cubicles, and general applications, thermal thin-film anemometer principle, adjustable range 0–15 m/s, accuracy ±(0.2 m/s + 3% reading) at 20°C/45% RH, 24V AC/DC , 4–20 mA or 0–10 V output for panel display/BMS/PLC/alarm integration. Robust polycarbonate sensor probe (IP20 head/IP42 transducer), duct-mounted with adjustable immersion stem, leak-tight flange fitting downstream of HEPA or representative locations. Complete with shielded cabling , 3-digit LED indicator (4–20 mA input), wiring/termination to SS control panel, earthing and commissioning verification of signal linearity, display accuracy, alarms |
| 134 | Air velocity sensor @ BCG Block |
| 135 | Air velocity sensor @ VVF Block |
| 136 | LEVELLING JACK |
| 137 | Supply, installation, testing and commissioning of levelling jacks for cleanroom equipment, screw-type adjustable design with minimum 40 mm diameter base and 75 mm height adjustment, comprising SS 304 threaded stem with locknut and SS mounting flange, fitted with non-marking, anti-vibration nylon/polyamide base pad suitable for epoxy/PU flooring, with minimum load capacity of 200 kg per jack, providing stable and level support, complete with installation, bolting to equipment frame, height adjustment, locking arrangement, and verification of proper levelling and stability. |
| 138 | Levelling Jack @ BCG Block |
| 139 | Levelling Jack @ VVF Block |
| 140 | PU CASTER WHEEL |
| 141 | Supply, installation, testing and commissioning of polyurethane (PU) caster wheels for cleanroom equipment, 100 mm diameter with PU tyre on nylon core, non-marking, anti-static and resistant to common disinfectants, with minimum load capacity of 100 kg per wheel, provided with SS 304 swivel bracket, double bearing arrangement and total-lock brake mechanism for simultaneous wheel and swivel locking, complete with SS mounting plate compatible with equipment frame, installation using SS fasteners, and verification of smooth movement, locking function and stability, suitable for GMP cleanroom applications. |
| 142 | PU Caster Wheel @ BCG Block |
| 143 | PU Caster Wheel @ VVF Block |
| 144 | INVERTER |
| 145 | Supply, installation, testing and commissioning of pure sine wave inverter/UPS system for cleanroom equipment, rated approximately 800 VA / 700 W with 230V AC output at 50 Hz and input from 12V DC battery, providing minimum 1-hour backup for LAF blower and lighting load, with output voltage regulation within ±5% and THD <3%, incorporating automatic changeover (ATS) with transfer time <10 ms, overload, short-circuit, over-temperature and deep discharge protection, along with inbuilt battery charging system, suitable for integration within equipment service panel, complete with mounting, wiring, battery connection, earthing, and testing for backup duration and functional performance. |
| 146 | Inverter - 800 VA @ BCG Block |
| 147 | Inverter - 800 VA @ VVF Block |
| 148 | DRY BATTERY |
| 149 | Supply, installation, testing and commissioning of 12V, 130AH sealed maintenance-free VRLA battery for inverter backup in cleanroom equipment, low internal resistance and self-discharge, suitable for minimum 1-hour backup operation, housed in non-spillable, acid-resistant ABS casing, with M6 terminal connections, designed for operation in 0°C to 45°C range, installed in ventilated compartment with secure mounting, complete with DC cabling, fuse protection, polarity check, and testing for backup performance and discharge characteristics, along with submission of technical datasheet. |
| 150 | Dry Battery - 12V / 130AH @ BCG Block |
| 151 | Dry Battery - 12V / 130AH @ VVF Block |
| 152 | GARMENTS TRAY |
| 153 | Supply, installation and commissioning of perforated garment storage tray for Dynamic Garment Cubicle, fabricated in SS 304 with minimum 1.2 mm thickness and 240 grit smooth finish, having perforated base to allow adequate airflow through garments, with folded edges and smooth welds ensuring no sharp edges, designed as removable tray compatible with SS runners, with minimum load capacity of 15 kg, suitable for GMP cleanroom use, complete with installation, proper fitment, easy removal and cleaning |
| 154 | Tray 500 x 700 x (mm) @ BCG Block |
| 155 | LIMIT SWITCH |
| 156 | Supply, installation, testing and commissioning of 12V DC limit switch for door/sash position detection in cleanroom equipment, electro-mechanical micro-switch type with SPDT (NO/NC) contacts rated for minimum 0.5A at 12V DC, suitable for UV and blower interlock system, housed in compact IP54-rated enclosure with durable ABS/phenolic body, capable of high mechanical life, with lever/roller or plunger actuator as per application, mounted on SS 304 bracket with adjustable positioning, complete with wiring, termination to control panel, and functional testing to ensure proper interlock operation (UV OFF on door opening and ON when closed). |
| 157 | Limit Switch @ BCG Block |
| 158 | Limit Switch @ VVF Block |
| 159 | BUZZER |
| 160 | Supply, installation, testing and commissioning of electronic buzzer for alarm indication in cleanroom equipment control panels, operating on 12V DC with minimum sound level 85 dB(A) at close range, housed in compact ABS enclosure with two-wire connection, complete with wiring, mounting, and functional testing to ensure audible alarm activation |
| 161 | Buzzer @ BCG Block |
| 162 | Buzzer @ VVF Block |
| 163 | DOOR CLOSER MAGNET (PASSIVE) |
| 164 | Supply, installation, testing and commissioning of passive door closer magnet (1.5\\"x1\\") for cleanroom equipment doors, complete with matching armature plate, mounted on door frame and leaf with proper alignment |
| 165 | Door Closer Magnet @ BCG Block |
| 166 | Door Closer Magnet @ VVF Block |
| 167 | EMERGENCY PUSH SWITCH |
| 168 | Supply, installation, testing and commissioning of emergency stop push switch for cleanroom equipment, mushroom-head type (40 mm dia, red with yellow base), push-to-actuate and twist/key-to-release latching mechanism with direct-opening action, rated for minimum 10A at 230V AC/12V DC, IP55 protection, provided with NC contacts for fail-safe interruption of blower, UV lamp and associated circuits, panel-mounted in accessible location with proper labelling, complete with wiring, interlock to prevent automatic restart, and functional testing to ensure immediate shutdown and manual reset operation. |
| 169 | Emergency Push Switch @ VVF Block |
| 170 | PU PNEUMATIC TUBE |
| 171 | Supply, installation, testing and commissioning of polyurethane (PU) pneumatic tubing for cleanroom equipment, size 6 mm ID x 8 mm OD, made of food-grade, phthalate-free, hydrolysis-resistant PU suitable for GMP environment, compatible with gauge ports and fittings, installed with push-fit/compression connectors |
| 172 | PU Pneumatic Tube @ BCG Block |
| 173 | PU Pneumatic Tube @ VVF Block |
| 174 | PVC SLIT CURTAINS |
| 175 | Supply Installation Testing and Commissioning of PVC strip curtains to cover the equipment/ openings as required, fabricated from virgin, clear transparent flexible PVC conforming to relevant IS standards, non-toxic, smooth finish, minimum 85% transparency, flame-retardant and self-extinguishing, suitable for pharma/ vaccine cleanroom applications. Strips shall be 200 mm wide × 2.0–2.0 mm thick with minimum 50% overlap (60% in controlled areas). |
| 176 | Supply Installation Testing and Commissioning of SS 304 strips of 32mm width and 1.0mm thickness. The strip shall be fixed to the Laminar Air Flow hood along with PVC curtains as per site requirements. Please Enable Macros to View BoQ information |