| 1 | Design, Supply, installation, testing and commissioning of 200 KVA manually operated voltage Stabilizer with following broad band specifications:Type of voltage controller: Manually operated copper strip wound, 3 phase & neutral powersupply. Type of Regulator: Plate type with electrolytic copper contacts.Input Voltage: 90-220V (phase to neutral).Output Voltage: 415±15%V (phase to phase)Frequency: 50hz±5% Mode of operation: Manual Phase imbalance: Imbalanced voltage & frequency characteristics.Winding: Electrolytic grade copper strips of adequate section, vacuum impregnated and oven dried.Voltage regulator: 06 steps with suitable amperage.Insulation: Fiber glass insulation to tested parameter.Efficiency: 98%.Cooling: Natural with convection fins, oil cooled.Mounting: Mounting on uni-directional wheels at four corner.Duty cycle: 100% continuous.Suitability: suitable for all power factorsEnclosure: M.S sheet minimum 04mm thick in pressed CGR sheet, powder coated duly strengthened with stiffeners of M.S flat/angle. It shall also be provided with a filling nozzle at the top & a drain at the bottom dully plugged.Core laminates: High grade low eddy current loss grain oriented silicon steel laminations.Display panel: The container shall be provided with a display on the top housing 2 No. voltmeter (0-500V) digital type for incoming & outgoing feeder.Cooling medium: The container shall be filled with relevant grade T-oil up to the required level.Connection Box: The stabilizer shall be provided with complete input/output connection box to ensure proper input/output power supply of voltage stabilizer.The equipment has to be provided/ installed at site and successfully tested commissioned on full load. |
| 2 | Supply,installation,testing and commissioning of 100 HP, 1440 rpm, 03 phase horizontal induction motor.Make : ABB/Kirloskar/Crompton &GreavesModel : Squirrel cage induction motor.Rating: 100 HPSpeed : 1440 RPMDesigned voltage: 415± 15% VoltsDesigned frequency : 50± 3% Hz.Class of insulation : FType of enclosure : TEFCIP Rating : 55.Duty type : S1Motor efficiency : IE2Mounting type : FootThe Job includes all costs of material and labour invloved for modification if any required for fitment of the motor on existing base frame with providing and fitting of new coupling of suitable size for coupling of new motor with existing 07 cusec horizontal pump at site. The Job also includes head load charges if any required for shifting of motor to site. |
| 3 | Providing and fitting of 400 A, 415 V, 03-pole MCCB with thermal magnetic release from 215 A to 400 A having 36 KA breaking capacity. Make L&T D-sine. |
| 4 | Providing, fitting, testing and commissioning of 150HP manually operated oil immersed double contact star-delta motor starter complete in all respects. The starters shall be provided with T. oil of specific grade upto to requisite level . The job includes all charges on account of successful installation and testing of starters of SKN make. |
| 5 | Providing and fitting of XLPE insulated 150 sq mm 3.5 core 1100 V armoured industrial aluminium cable of reputed make with proper Al thimbles at all terminals conforming to IS 7098.. |
| 6 | Providing and fitting of XLPE insulated 70 sq mm single core 1100 V armoured industrial copper cable of reputed make with proper Cu thimbles at all terminals conforming to IS 7098. |
| 7 | Fabrication, providing and fitting of MS pipe for such as tail pieces, replacement pipes |
| 8 | Providing and welding of MS flanges of nominal pressure rating 1.0 as per IS 6392 of 300 mm dia |
| 9 | Providing and welding of MS flanges of nominal pressure rating 1.0 as per IS 6392 of 250 mm dia |
| 10 | providing and fitting of 300 mm dia rubber gasket for flanged joints |
| 11 | providing and fitting of 250 mm dia rubber gasket for flanged joints |
| 12 | Providing and fitting of MS nuts bolts of assorted sizes |
| 13 | Welding of MS sections etc including cost of consumables etc but excluding cost of transporatation of equipment at site by gas welding |
| 14 | Welding of MS sections etc including cost of consumables etc but excluding cost of transporatation of equipment at site by electric welding |
| 15 | providing and fitting of 03 ton capacity heavy duty chain pulley block with a lift height of 06m as per IS 3832 of Globe/pulllift/indef/elephant/ Kepro make |
| 16 | Providing and fitting of 96*96 flush mounting 03-phase LED Ammeter and voltmeter of class I accuracy of L&T/Risabh/AE Make |
| 17 | Earthing with GI earth plate of size 600×600×6 mm thick including accessories and providing masonary enclosure with cover plate and locking arrangement and 200 mm dia GI medium class watering pipe 2.7m long, funnel etc with charcoal, coke and salt as required. |
| 18 | Illumination of pump house by way of providing and fitting of a.providing installtion and testing of die cast Alumimium flood lights of Havells make LED with IP 65 rating of 30 Watt (08 no).Providing and fitting of 1.5 mm2 Cu wire (90m), Providing and fitting of PVC conduit (30m), Providing and fitting of 03 no. 6-32A DP MCB 240 V 50 Hz control switch for lighting. Providing and fitting of 6A 3 pin socket (02 no.), 240 V 50 HZ of anchor make. The job includes cost on account of charges for skilled electrician and labour. |
| 19 | Complete dismantling of single stage horizontal pump by way of disconnecting all leads from the motor and marking the terminals, uncoupling of motor from the pump. Disassembling, dismantling and segregation of various pump parts such as shaft and sleeves, impeller, gland, fasteners, etc for suction dia of 300mm. |
| 20 | Mechanical transportation, loading, unloading and handling of pump to and fro, carriage of old material scrap from site to divisional store using tata mobile as means of transport through a lead of approximately 30 kilometer. |
| 21 | Fabrication, providing and fitting of GM sleeve as per sample |
| 22 | Providing and fitting of gun metal split gland as per sample |
| 23 | Manufacturing, providing and fitting of GM bronze impeller wearing ring/seal ring |
| 24 | Repairs to the SS shaft less than 50 mm dia by way of rebuilding of shaft using high quality SS electrodes and then turning the shaft on lathe machine to remove excess material deposit and restore the original dimensions and profile of shaft.(03 spots) |
| 25 | Repairs to damaged MS impeller by way of rebuilding of vane profile using electric arc welding and then machining to get desired profile |
| 26 | Providing and fitting palmetto packing |
| 27 | Providing and fitting TC-19 coupling set complete for pumping unit along with flexible rubber tyre . Taking dimensions of prime mover shaft and pump shaft at site and then boring the CI coupling halves as per site requirement on lathe machine at workshop. Complete linear and angular alignment of prime mover and pump shafts for smooth operation including providing and fitting of coupling bolts. Testing pumping unit on full load at site. |
| 28 | Rethreading of bolt hole upto M12 size of pump casing |
| 29 | Providing of AP3 grease all purpose type |
| 30 | Providing of circulating oil for bearing lubrication |
| 31 | Steel work in built up section , including cutting, hoisting , applying steel primer coat for fabrication of door, windows, Modification/fabrication of the base frame as per site requirement |
| 32 | Complete assembling of single stage horizontal pump after cleaning of all parts throughly with petrol, coupling and alignment with motor, connecting of motor leads and testing on full load. |
| 33 | Hiring of excavator 3D with driver and fuel for retrieving of old machinery etc. Please Enable Macros to View BoQ information |