Defence Statutory Bodies & Commissions/Committees Closing in 24 days TDR #55855107

Tender For Provision Of Otm Accn For Inf Bn (Ph-Ii) At Kalimpong Mil Station Under Ge 867 Ews

Issued by Statutory Bodies & Commissions/Committees · Kalimpong, West Bengal
Tender Value
20.75 Crore
Estimated cost
Bid Submission
03 Aug 2026
24 days left
EMD
13.62 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kalimpong → West Bengal
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender For Provision Of Otm Accn For Inf Bn (Ph-Ii) At Kalimpong Mil Station Under Ge 867 Ews

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 19-Jun-2026 Tender presentation cum pre-bid conference Other 10-Jul-2026
2 30-Jun-2026 Date_Corrigendum_1 Date 20-Jul-2026
3 09-Jul-2026 Date_Corrigendum2 Date 03-Aug-2026

BOQ

Name of Work:- PROVN OF OTM ACCN FOR INF BN (PH-II) AT KALIMPONG MIL STATION UNDER GE 867 EWS
Sl. No. Item Description
1BUILDINGS & STRUCTURE (Sch 'A' PART-I)
2Lump sum price worked out by the Contractor for “BUILDINGS & STRUCTURE” as listed in Schedule ‘A’ Part-I. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 11,37,15,013.26 inserted by the MES in Schedule ‘A’ Part-I.
3EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT (Sch 'A' PART-II)
4Lump sum price worked out by the Contractor for “EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT” as listed in Schedule ‘A’ Part-II. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,18,77,708.05 inserted by the MES in Schedule ‘A’ Part-II.
5INTERNAL WATER SUPPLY (Sch 'A' PART-III)
6Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-III. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 1,00,052.16 inserted by the MES in Schedule ‘A’ Part-III.
7INTERNAL ELECTRIFICATION (Sch 'A' PART-IV)
8Lump sum price worked out by the Contractor for “(INTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-IV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 22,82,312.35 inserted by the MES in Schedule ‘A’ Part-IV.
9ROAD, PATH & CULVERT (Sch 'A' PART-V)
10Lump sum price worked out by the Contractor for “(ROAD, PATH & CULVERT )” as listed in Schedule ‘A’ Part-V. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 79,45,964.39 inserted by the MES in Schedule ‘A’ Part-V.
11SEWAGE DISPOSAL (Sch 'A' PART-VI)
12Lump sum price worked out by the Contractor for “(SEWAGE DISPOSAL)” as listed in Schedule ‘A’ Part-VI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 4,80,988.30 inserted by the MES in Schedule ‘A’ Part-VI.
13AREA DRAINAGE (Sch 'A' Part-VII)
14Lump sum price worked out by the Contractor for “(AREA DRAINAGE)” as listed in Schedule ‘A’ Part-VII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 8,09,150.20 inserted by the MES in Schedule ‘A’ Part-VII.
15PERIMETER FENCING (Sch 'A' Part-VIII)
16Lump sum price worked out by the Contractor for “(PERIMETER FENCING)” as listed in Schedule ‘A’ Part-VIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 26,96,916.00 inserted by the MES in Schedule ‘A’ Part-VIII.
17STEEL GATE (Sch 'A' Part-IX)
18Lump sum price worked out by the Contractor for “(STEEL GATE)” as listed in Schedule ‘A’ Part-IX. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 13,62,753.52 inserted by the MES in Schedule ‘A’ Part-IX.
19PROTECTIVE WORK (Sch 'A' Part-X)
20Lump sum price worked out by the Contractor for “(PROTECTIVE WORK)” as listed in Schedule ‘A’ Part-X. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 2,05,42,322.82 inserted by the MES in Schedule ‘A’ Part-X.
21EXTERNAL WATER SUPPLY (Sch 'A' Part-XI)
22Lump sum price worked out by the Contractor for “(EXTERNAL WATER SUPPLY)” as listed in Schedule ‘A’ Part-XI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 5,34,433.23 inserted by the MES in Schedule ‘A’ Part-XI.
23EXTERNAL ELECTRIFICATION (Sch 'A' PART-XII)
24Lump sum price worked out by the Contractor for “(EXTERNAL ELECTRIFICATION)” as listed in Schedule ‘A’ Part-XII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs.21,29,795.27 inserted by the MES in Schedule ‘A’ Part-XII.
25MECHANICAL CRANE (Sch 'A' Part-XIII)
26Lump sum price worked out by the Contractor for “(MECHANICAL CRANE)” as listed in Schedule ‘A’ Part-XIII. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 19,761.80 inserted by the MES in Schedule ‘A’ Part-XIII.
27DG SET (Sch 'A' Part-XIV)
28Lump sum price worked out by the Contractor for “(DG SET)” as listed in Schedule ‘A’ Part-XIV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 45,437.40 inserted by the MES in Schedule ‘A’ Part-XIV.
29FIRE FIGHTING (Sch 'A' Part-XV)
30Lump sum price worked out by the Contractor for “(FIRE FIGHTING)” as listed in Schedule ‘A’ Part-XV. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 7,20,166.70 inserted by the MES in Schedule ‘A’ Part-XV.
31DEMOLITION & DISMANTLING (Sch 'A' Part-XVI)
32Lump sum price worked out by the Contractor for “(DEMOLITION & DISMANTLING) ” as listed in Schedule ‘A’ Part-XVI. Representing ** ___ % ______ percent *Above / Below the lump sum price of Rs. 3,87,338.73 inserted by the MES in Schedule ‘A’ Part-XVI.
33MISCELLANEOUS ITEMS REQUIRED FOR B/R & E/M SERVICES (Sch 'A' Part-XVII)
34ROAD, PATH & CULVERTSupplying and fixing road delineator post conforming to MoRTH Specifications (Clause 804) and IRC:79, made of high impact resistant ABS round body, fitted with 2 Nos. 65 mm diameter high intensity prismatic reflectors of PMMA (micro prismatic type).The delineator shall be mounted on 45/50 mm dia mild steel pipe post of 600 mm height, duly powder coated for corrosion resistance, provided with thermoplastic elastomer reflective bands in green, red and yellow with 25 mm wide reflective tape strips for enhanced night visibility.The system shall include anti-theft steel mesh/net protection for reflectors, durable fixing arrangement, and shall be embedded in PCC 1:2:4 (Type B1) block of size 150 mm × 150 mm × 300 mm, including excavation, foundation preparation, proper alignment, curing and finishing complete all as specified and directed.
35INTERNAL ELECTRIFICATIONS & F modular type 3 pin 20 A socket with Metal Clad S/B, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed. (AC & GYSER POINT)
36S & F modular type 1 module RJ-11 telephone scoket with shutter complete all as specified and directed.
37S & F modular type 1 module co-axial type TV socket all as specified and directed by the engineer in charge
38S & F modular type 1 module Regulator all as specified and directed.
39S&F engagement light (LED type) of Red & green outside the office location as directed controlled by one way switch for main control and two way switch for red/green light complete all as specified and directed.
40S & F single pole & neutral, modular type, double door, 6 way metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for DP RCCB / RCBO / Isolator / MCB as incomer and SP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed for the items mentioned below:-NOTE:[i] DP RCCB / RCBO / Isolator / MCB & SP MCBs shall be measured and paid separately.
41S & F 16 A, 230 V, 50 Hz, 2P MCB conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed.
42S & F 20 A, 230 V, 50 Hz, 2P MCB conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed.
43S & F 63A, 4P, 16KA, 50HZ, moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 5- 10 X Ir), inbuilt encapsulated double break roto active type instantaneous protection, earth fault leakage protection, etc. having Ics = 100% = Icu = 16 & 25 kA as per IEC 60947-2 and suitable for 3-Phase, 415 V, 50 Hz electric supply complete all as specified and directed.
44S&F load line distribution board TPN vertical, double door type, 4-way, fixed on wall semi flush with incoming MCCB 4 poles and, busbars , neutral link, blanking plates complete with all accessories all as specified and as directed
45M & L of 1.1 kV grade, conductor, 3 Core, 1.5 sqmm A2XFY XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded Aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, complete all as specified and directed.
46M & L of 1.1 kV grade, conductor, 3 Core, 1.2 sqmm A2XFY XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded Aluminium compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, complete all as specified and directed.
47Supply and fixing 36 watt LED Recessed panel light (600mm x 600mm), suitable for operation on 220-240 Volts AC, 50 Hz supply, having minimum efficacy of 120 lumens/Watt, CRI > 80, PF > 0.95, complete with LED driver, housing, diffuser, mounting frame, suspension arrangement wherever required, terminal block, connectors, internal wiring, fixing accessories and all connected fittings and accessories required for proper installation, testing and commissioning, complete all as specified and directed.
48Supply and fixing 24 watt LED Recessed panel light (300mm x 300mm), suitable for operation on 220-240 Volts AC, 50 Hz supply, having minimum efficacy of 120 lumens/Watt, CRI > 80, PF > 0.95, complete with LED driver, housing, diffuser, mounting frame, suspension arrangement wherever required, terminal block, connectors, internal wiring, fixing accessories and all connected fittings and accessories required for proper installation, testing and commissioning, complete all as specified and directed.
49Supply and fixing 12 watt LED Recessed down light, suitable for operation on 220-240 Volts AC, 50 Hz supply, having minimum efficacy of 100 lumens/Watt, CRI > 80, PF > 0.95, complete with LED driver, housing, diffuser, mounting frame, suspension arrangement wherever required, terminal block, connectors, internal wiring, fixing accessories and all connected fittings and accessories required for proper installation, testing and commissioning, complete all as specified and directed.
50Supply and Fixing 05 Watt LED Lamp (B22 Cap) Suitable for operation on 220-240 Volts AC, 50 Hz supply, complete with all connected fittings and accessories, testing and commissioning, complete all as specified and directed.
51S & F LED Bulb Holder having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed.
52S & F 80 Watt LED High Bay Luminaire, IP-65 protected, suitable for operation on 220-240Volts AC, 50 Hz Supply, having minimum efficacy of 140 lumens/Watt, complete with LED driver, mounting bracket, suspension arrangement, terminal block, connectors, internal wiring, cable glands, fixing accessories, earthing terminal and all connected fittings and accessories required for proper installation, testing and commissioning, complete all as specified and directed.
53S & F 20 Watt Flameproof/Weatherproof LED Tubelight capable of delivering 100 lumen per watt, Input Voltage - 220-240V AC, input frequency 50- 60 Hz, Surge voltage protection - 4KVA, CCT- 5500 TO 6500K,CRI > 70%, Glass type - Borosilicate, Gasket O' Ring endless neoprene rubber Gasket, Wire Guard Mild Steel Cable entries M20 – 2 NOS Material of construction - Al Die Cast, hazardious classification Area of classification Zone-1,Zone-2, Gas Group IIA,IIB,IIC, Ingress Protection IP66, Temperature class T6, Certification CIMFR & PESO including electrical connection with flexible steel conduit including providing of suitable SS gland to the fixture complete all as specified and directed.
54S & F 10 Watt Flameproof/Weatherproof LED Tubelight capable of delivering 100 lumen per watt, Input Voltage - 220-240V AC, input frequency 50- 60 Hz, Surge voltage protection - 4KVA, CCT- 5500 TO 6500K,CRI > 70%, Glass type - Borosilicate, Gasket O' Ring endless neoprene rubber Gasket, Wire Guard Mild Steel Cable entries M20 – 2 NOS Material of construction - Al Die Cast, hazardious classification Area of classification Zone-1,Zone-2, Gas Group IIA,IIB,IIC, Ingress Protection IP66, Temperature class T6, Certification CIMFR & PESO including electrical connection with flexible steel conduit including providing of suitable SS gland to the fixture complete all as specified and directed.
55S & F 9W LED Study light having Luminous efficacy of > 100, input voltage range 140-270 V, input frequency 50-60 Hz complete all as specified and directed.
56S&F 24\\" heavy duty wall mounted fan complete with blades, down rods, electronic regulator and accessories, 230 V, 600 mm sweep, RPM 1440 complete all as specified and directed.
57Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type BUILDING PANEL (TTA) of suitable size for short circuit, temperature rise, protective earth short circuit test and dielectric tests of required ratings, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed. Item Continued as 17.25 to 17.26
58The BUILDING PANEL shall comprise of the following:[A] BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 100A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection[B] INCOMING[i]100A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 01 Nos.[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.[iii] LED phase indicators (Red, Yellow, Blue)- 01 Set[C] OUTGOING[i]63A, 415 V, Ics = 100% Icu = 16 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 2 Nos
59[ii]32A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 03 Nos[iii]20A, 230 V, Ics = 100% Icu = 10 kA, 50 Hz 2P MCB, conforming to IEC 60947-2, having trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)- 02 Nos[iv] LED phase indicators (Red, Yellow, Blue)- 7 Set
60S & F switch flame proof rotary type with termination box in LM6, 5A, single pole 250V complete all as specified and directed.
61S & F Flame Proof distribution board 4 way with connected accessories prewired complete all as specified and directed.
62SEWAGE DISPOSALSupply, installation, testing and commissioning of factory made, prefabricated LLDPE septic tank of conventional design suitable for 25 users, conforming to relevant CPHEEO Manual on Sewerage and Sewage Treatment and applicable IS codes, manufactured from linear low-density polyethylene (LLDPE), UV stabilized, corrosion resistant, monolithic and leak proof construction, suitable for underground installation.The septic tank shall be complete with inlet and outlet chambers, internal baffle arrangement, partition wall, inspection/manhole openings with tight fitting covers, vent shaft arrangement with mosquito proof cowl, and adequate sludge storage capacity, designed for anaerobic sewage treatment and effluent discharge.The system shall be designed to withstand all imposed loads including earth pressure, hydrostatic pressure, and superimposed surface loads, and shall be factory tested for water tightness and structural integrity prior to installation.The work includes excavation in any type of soil to required dimensions and depth, disposal of surplus excavated material to a distance not exceeding 50 m or as directed, and providing PCC 1:4:8 (Type D-2) bedding below foundation for uniform support. Installation shall include proper positioning, alignment, and levelling of septic tank, ensuring correct gradient for inlet and outlet pipelines.The work further includes providing and fixing inlet, outlet and vent pipes of suitable PVC/HDPE material, jointing with approved solvent cement or rubber ring joints, sealing of all connections, and testing for leakage and satisfactory hydraulic performance of the complete system.Backfilling shall be carried out in layers with selected excavated material, properly compacted to prevent settlement, and restoration of surrounding area to original condition.All materials, workmanship, installation, testing and commissioning shall be in compliance with statutory environmental norms, CPHEEO guidelines, relevant IS codes and manufacturer’s specifications, and shall be complete all as specified and directed.
63M&L for provision of RCC septic tank with screen chamber of conventional design for 100 users complete, including excavation in any type of soil, PCC M-10 below foundation, RCC M-30 (design mix) for base slab, walls, baffle wall, roof slab, columns, beams etc., including reinforcement steel, formwork and centering, vent shaft, manhole opening with CI cover and frame, inlet/outlet connections, screen chamber complete, curing, testing and commissioning, backfilling and disposal of surplus soil, all as per approved drawing and as directed.Note: Work shall be executed as per TD of Chief Engineer, Siliguri Zone, Drawing No. CESZ/2020/TD/ST-07.
64M&L for construction of soakage wells in any type of soil, including excavation, PCC 1:3:6 in foundation, honey-combed brick masonry walls in cement mortar, providing RCC M-25 top ring, intercepting chamber and screen chamber in brick masonry in CM, RCC cover slab in M-25 with CI/RCC cover as required, providing interconnecting RCC pipes, filling of soak pit with brick bats, complete all as specified including all necessary formwork, curing, backfilling and disposal of surplus soil, of size 1.80 m x 3.00 m effective depth, complete all as directed.NOTE :Work shall be executed as per TD of Chief Engineer, Siliguri Zone, Drawing No. SZ/TD-14 Sheet 1/1.
65M&L for construction of soakage wells in any type of soil, including excavation, PCC 1:3:6 in foundation, honey-combed brick masonry walls in cement mortar, providing RCC M-25 top ring, intercepting chamber and screen chamber in brick masonry in CM, RCC cover slab in M-25 with cover as required, providing interconnecting RCC pipes, filling of soak pit with brick bats, complete all as specified including all necessary formwork, curing, backfilling and disposal of surplus soil, of size 2.4 m dia x 4.50 m effective depth, complete all as directed.NOTE : Work shall be executed as per TD of Chief Engineer, Siliguri Zone, Drawing No. SZ/TD-14 Sheet 1/1.
66EXTERNAL WATER SUPPLYMaterial and labour for construction of brick masonry valve pit of internal size 900 mm × 900 mm × 900 mm as per Technical Drawing (TD), using old size sub-class ‘B’ burnt clay bricks conforming to IS standards, laid in cement mortar 1:6, including raking of joints, curing and finishing complete.The work shall include 75 mm thick PCC 1:3:6 (Type C-2) in foundation, and PCC 1:2:4 (Type B-2) benching as shown in TD drawing, including proper shaping, slope and finish for drainage/valve seating Internal and external surfaces shall be finished with 10 mm thick cement plaster 1:4, smooth finished, properly cured and rendered watertight.Providing and fixing 2 mm thick MS sheet cover as per TD drawing, mounted on MS angle iron frame 50 mm × 50 mm × 6 mm thick, embedded in PCC 1:2:4 (Type B-1) coping, complete with hinges, locking arrangement and handle as shown in drawing.MS components shall be cleaned and painted with one coat of red oxide zinc chrome primer and two coats of black bituminous paint.The work includes excavation in soft/loose soil, dewatering if required, returning filling in layers with compaction, disposal of surplus soil to a distance not exceeding 50 m, and all incidental works complete.All work shall be executed strictly as per TD drawing, specifications and as directed.
67EXTERNAL ELECTRIC SUPPLYDesign, Supply, Installation, Testing and Commissioning (DSITC) including making all necessary electrical connections of LT outdoor type, factory-made, CPRI type-tested (Type Tested Assembly – TTA) and IEC 61439 compliant feeder pillar box ,totally enclosed with outer shell shall be made out of 3.15 mm thick sheet & MS angle section of suitable size for frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.0 mm thick sheet with individual switchgear /MCCB encased in separate cubical ,detachable side hinge front coverwith screwed knobs ,bending of edges of front cover with providing suitable rubber/neoprene gaskets at edges, protection class IP 65 as per IS 8623 double door,weather ,dust and vermin prof having overall hinged opening arrangenment in both front & back sided and frame of angle iron 50x50x6 mm duly welded including cable entry & exit through glands at bottom including two coats of powder coated paint over a coat of red oxide primer on both outer and inner surface of panel, internal connection from bus bar to switchgear/MCCB with suitable size of copper stranded PVC insulated wire with suitable copper lugs with extended legs to suitable height embedded in and including PCC 1:3: 6 foundation of suitable size all as specified and directed including following items: Item Continued as 17.35 to 17.37
68Aluminium bus bar 4 strips (covered with colour coded insulated PVC sleeves) of rating 1.5 times current carrying capacity of incoming switch gear or not less than 200 Amps whichever higher suitable length including connection etc complete – 01 Set INCOMING:-(i) MCCB 4P of capacity 200 Amps, 415 Volts, 50 Hz, breaking capacity 25 kA ,Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01 No.(ii) Digital type 3Ph AC ammeter with inbuilt selector switch,flush mounting 96X96mm accuracy class- Cl1 (iii)Digital type 3Ph AC voltmeter with inbuilt selector switch,flush mounting 96X96mm accuracy class- Cl1 (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set
69OUTGOING :- (i) MCCB 4P of capacity 63 Amps, 415 Volts, 50 Hz, breaking capacity 16 KA Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01No.(ii) MCCB 4P of capacity 40 Amps, 415 Volts, 50 Hz, breaking capacity 16 KA Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 03No. (01 Spare)(iii) MCCB 4P of capacity 25 Amps, 415 Volts, 50 Hz, breaking capacity 16 KA Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 03No. (01 Spare)
70(iv) MCCB 4P of capacity 16 Amps, 415 Volts, 50 Hz, breaking capacity 16 KA Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01 No. (iv) MCB 4P of capacity 6 Amps, 415 Volts, 50 Hz, breaking capacity 10 KA - 02 Nos ( 01 Spare). (iv) MCB DP of capacity 16 Amps, 415 Volts, 50 Hz, breaking capacity 10 KA - 02 Nos ( 01 Spare). (v) Danger notice plate of size 25 X 20 cm of 1.6mm thick mild steel sheet, vitreous enameled white,with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamp and bolt and nuts of approved size of LT conformingh to IS:2551 complete- 02 Nos
71Design, Supply, Installation, Testing and Commissioning (DSITC) including making all necessary electrical connections of LT outdoor type, factory-made, CPRI type-tested (Type Tested Assembly – TTA) and IEC 61439 compliant feeder pillar box ,totally enclosed with outer shell shall be made out of 3.15 mm thick sheet & MS angle section of suitable size for frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.0 mm thick sheet with individual switchgear /MCCB encased in separate cubical ,detachable side hinge front coverwith screwed knobs ,bending of edges of front cover with providing suitable rubber/neoprene gaskets at edges, protection class IP 65 as per IS 8623 double door,weather ,dust and vermin prof having overall hinged opening arrangenment in both front & back sided and frame of angle iron 50x50x6 mm duly welded including cable entry & exit through glands at bottom including two coats of powder coated paint over a coat of red oxide primer on both outer and inner surface of panel, internal connection from bus bar to switchgear/MCCB with suitable size of copper stranded PVC insulated wire with suitable copper lugs with extended legs to suitable height embedded in and including PCC 1:3: 6 foundation of suitable size all as specified and directed including following items: Item Continued as 17.39 to 17.40
72Aluminium bus bar 4 strips (covered with colour coded insulated PVC sleeves) of rating 1.5 times current carrying capacity of incoming switch gear or not less than 200 Amps whichever higher suitable length including connection etc complete – 01 Set INCOMING:-(i) MCCB 4P of capacity 25 Amps, 415 Volts, 50 Hz, breaking capacity 16 kA ,Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01 No.(ii) Digital type 3Ph AC ammeter with inbuilt selector switch,flush mounting 96X96mm accuracy class- Cl1 (iii)Digital type 3Ph AC voltmeter with inbuilt selector switch,flush mounting 96X96mm accuracy class- Cl1 (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set
73OUTGOING :- (i) MCCB 4P of capacity 25 Amps, 415 Volts, 50 Hz, breaking capacity 16 KA Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01No.(ii) Danger notice plate of size 25 X 20 cm of 1.6mm thick mild steel sheet, vitreous enameled white,with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamp and bolt and nuts of approved size of LT conformingh to IS:2551 complete- 02 Nos. The panel shall be as per OEM recommendation and approved specifications, and shall be supported with valid CPRI type test certificates (TTA) and routine test reports.Item also includes , RCC pedestal, grouting, cable connections, and all incidental civil and electrical works required for proper installation and operation, complete all as specified and as directed.
74Design, Supply, Installation, Testing and Commissioning (DSITC) including making all necessary electrical connections of LT outdoor type, factory-made, CPRI type-tested (Type Tested Assembly – TTA) and IEC 61439 compliant feeder pillar box,totally enclosed with outer shell shall be made out of 3.15 mm thick sheet & MS angle section of suitable size for frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.0 mm thick sheet with individual switchgear /MCCB encased in separate cubical ,detachable side hinge front coverwith screwed knobs ,bending of edges of front cover with providing suitable rubber/neoprene gaskets at edges, protection class IP 65 as per IS 8623 double door,weather ,dust and vermin prof having overall hinged opening arrangenment in both front & back sided and frame of angle iron 50x50x6 mm duly welded including cable entry & exit through glands at bottom including two coats of powder coated paint over a coat of red oxide primer on both outer and inner surface of panel, internal connection from bus bar to switchgear/MCCB with suitable size of copper stranded PVC insulated wire with suitable copper lugs with extended legs to suitable height embedded in and including PCC 1:3: 6 foundation of suitable size all as specified and directed including following items: Item Continued as 17.42 to 17.43
75Aluminium bus bar 4 strips (covered with colour coded insulated PVC sleeves) of rating 1.5 times current carrying capacity of incoming switch gear or not less than 200 Amps whichever higher suitable length including connection etc complete – 01 Set INCOMING:-(i) MCCB 4P of capacity 16 Amps, 415 Volts, 50 Hz, breaking capacity 16 kA ,Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01 No.(ii) Digital type 3Ph AC ammeter with inbuilt selector switch,flush mounting 96X96mm accuracy class- Cl1 (iii)Digital type 3Ph AC voltmeter with inbuilt selector switch,flush mounting 96X96mm accuracy class- Cl1 (iv) Modular indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set
76OUTGOING :- (i) MCCB 4P of capacity 16 Amps, 415 Volts, 50 Hz, breaking capacity 16 KA Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts,Spreaders, Phase barrier etc - 01No.(ii) MCB DP of capacity 6 Amps braking capacity 10 kA, 230 Volt , 50 Hz- 02 Nos (01 Spare)(iii) Danger notice plate of size 25 X 20 cm of 1.6mm thick mild steel sheet, vitreous enameled white,with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamp and bolt and nuts of approved size of LT conformingh to IS:2551 complete- 02 Nos.The panel shall be as per OEM recommendation and approved specifications, and shall be supported with valid CPRI type test certificates (TTA) and routine test reports.Item also includes , RCC pedestal, grouting, cable connections, and all incidental civil and electrical works required for proper installation and operation, complete all as specified and as directed.
77Supply, fabrication and fixing of street light bracket made out of GI light grade pipe conforming to IS 1239 (Part 1), up to 32 mm nominal bore, of length 1.5 m, bent to an angle of 120 degrees, suitable for fixing street light fittings.The bracket shall be provided with 02 Nos MS clamps of size 40 mm × 6 mm, along with 04 sets of nuts, bolts and washers for proper fixing to pole/wall with and including MS clamps shall conform to relevant IS 2062 (structural steel) and shall be properly cleaned, prepared and painted with one coat of red oxide zinc chromate primer and two coats of aluminium paint. The work includes fixing at required height and position, alignment, tightening, drilling, all labour, tools, accessories and incidental works complete all as specified and directed by the Engineer-in-Charge. complete all as specified and as directed.
78S&F factory made Junction Box , IP-66 (weather proof) , outdoor installation for street light of size 205 mm x 255 mm x 112 mm made of high quality polycarbonate (shock proof, rust free, corrosion free acid and chemical resistant, fire retardant having high impact (IK 08) totally insulated made of halogen and silica free recyclable material, UV resistant having high grade gasket made of polyurethane with copper terminal including MCB SP 2 Amps rating 10 KA with locking arrangement and suitable size cable glands and fixing to the street light pole with 02 Nos, 25 x 3 mm thick MS clapms, nuts & bolt, etc.complete all as specified and directed.
79Taking out existing serviceable HT UG cable upto 95 Sqmm 3 core with all protection GI Pipe etc after disconnecting and relaying with necessary excavation, earth work, sand cushioning, cable cover etc and connections complete all as specified and as directed.NOTE :Earthwork, sand cushioning and cable cover will will be measured and paid under relevent items.
80Taking out existing serviceable LT UG cable upto 120 Sqmm 3.5 core with all protection GI Pipe etc after disconnecting and relaying with necessary excavation, earth work, sand cushioning, brick etc and connections carefully complete all as specified and as directed.NOTE :Earthwork, sand cushioning and cable cover will will be measured and paid under relevent items.
81HOT WATER APPLIANCESSupplying, installing, testing & commissioning, storage water heater (geyser), 50 litres capacity, standing loss less than 0.562 Kwh per day for 45⁰C difference of temperature as per IS 2082 (five-star rated as per BEE), reheating time less than 60 minutes, mixing factor less than 20%, shock proof high density PUF insulation body material, glass lined inner tank material having warranty 7 years on tank material, 4 years on heating element and 2 years on other spares parts comprising following fittings :_(a) glass coated incoloy element (b) capillary type thermostat (c) digital display unit (d) thermal cutout (e) multifunction valve (f) earth leakage circuit breaker (g) magnesium anode rod cathodic protection (h) flexible cable of suitable length with 3-pin plug of 16A capacity (j) drain plug (k) fusible plug fitted on the crown of water heater with operating temperature between 100⁰C to 110⁰C (l) 2 nos stainless steel braided flexible connection pipe for hot and cold water supply for geyser, 15 mm bore, 450 mm length, 12 bar working pressure including fixing by grouting and fastener complete all as specified and as directed.
82MECHANICAL CRANEDesign, Supply, Installation, Testing and Commissioning of electrically operated,overhead traveling (EOT) cranes of capacity not less than 05 Ton, conforming to IS : 3177 (latest revision), with span not less than 21.8 mtrs (approx), height of lift 5 mtrs (not less than ), travel length 25 mtrs (not less than ), suitable for operation on 415 Volts, 3 Phase, 4 wires, 50 HZ supply, double girder box type, with necessary steel supporting structures with Hoist speed 3mtrs / min and creep/micro speed 0.3mtr/min, cross travel speed 15 mtrs / min and creep/micro speed 1.5 mtr/min, long travel speed 20 mtrs/min and creep/micro speed 2 mtr/min with micro drive through clutch and geared motor of suitable capacities with control panel, power and controlling cables, confirming to relevant IS, controlled by pendent push button station and radio remote control switch of operation, with and including dia of steel rope of suitable size ,DSL system of shrouded busbar type with following specification. Item Continued as 17.50 to 17.57
83(A). COMMON FEATURES/TECH SPECIFICATION :- Here in as mentioned below :- (i) Gantry Girders and Bridge girder double box type/Rail of suitable size has to be provided by the bidder as per approved design. (ii) Hoisting Mechanism, with specially designed crab unit for double girder, engineered for smooth jerk free, and soft start, lifting of loads. Hoist drive with micro drive through clutch and geared motor selected according to the class of duty, driving the rope drum, through helical gear box. The rope drum shall be made out of seamless pipes fabricated from plates tested as per ASTM/IS standards.(iii) Gear Boxes with helical gears, oil lubricated, manufactured using the modern gear cutting machines, duly heat treated to withstand the stringent load conditions and selected according to class of duty commensurate with type of application. (iv) End carriages with standard wheel bases fabricated using the modern welding and machining techniques to ensure jerk free and smooth travel motion. The wheels shall be double flanged, supported on self aligning anti-friction bearings, Buffers shall be provided at the ends of the carriage as per IS Standards. (v) Brakes for all drives shall be Electro-magnetic shoe brakes according to the application. Please Enable Macros to View BoQ information
84(A). COMMON FEATURES/TECH SPECIFICATION :- Here in as mentioned below :- (i) Gantry Girders and Bridge girder double box type/Rail of suitable size has to be provided by the bidder as per approved design. (ii) Hoisting Mechanism, with specially designed crab unit for double girder, engineered for smooth jerk free, and soft start, lifting of loads. Hoist drive with micro drive through clutch and geared motor selected according to the class of duty, driving the rope drum, through helical gear box. The rope drum shall be made out of seamless pipes fabricated from plates tested as per ASTM/IS standards.(iii) Gear Boxes with helical gears, oil lubricated, manufactured using the modern gear cutting machines, duly heat treated to withstand the stringent load conditions and selected according to class of duty commensurate with type of application. (iv) End carriages with standard wheel bases fabricated using the modern welding and machining techniques to ensure jerk free and smooth travel motion. The wheels shall be double flanged, supported on self aligning anti-friction bearings, Buffers shall be provided at the ends of the carriage as per IS Standards. (v) Brakes for all drives shall be Electro-magnetic shoe brakes according to the application. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 55855107
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 20.75 Crore
LAST DATE 03-08-2026
Authority
Authority Name Military Engineer Services
Work Description Tender For Provision Of Otm Accn For Inf Bn (Ph-Ii) At Kalimpong Mil Station Under Ge 867 Ews
Basic Detail
Tender No 98822/KGP/SZ/E8
Bidding Type Tender
Location
City Kalimpong
State West Bengal
Key Dates
Publish Date 09 Jul 2026
Submission Date 03 Aug 2026
Open Date 10 Aug 2026
Finance
Tender Value 20.75 Crore
Tender Fee 3000
EMD 13.62 Lakhs
Exemption Available
Document List
Complete_Tender_Except_BOQ.pdf
STR_DRG_1.rar
STR_DRG_2.rar
STR_DRG_3.rar
TD_STRL.rar
Tendernotice_1.pdf
1e437ed4-fab1-45bd-9739-9741a72428a0.html
ARCH_DRG_1.rar
ARCH_DRG_2.rar
BOQ_862380.xls

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 09, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 10, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Today
Jul 20, 2026
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 10 days
Aug 03, 2026
18:00 IST

Corrigendum-3 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 24 days
Aug 03, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 24 days
Aug 10, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 31 days

Tender Documents

Download All (ZIP) ↓
pdf

Complete_Tender_Except_BOQ.pdf

rar

STR_DRG_1.rar

rar

STR_DRG_2.rar

rar

STR_DRG_3.rar

rar

TD_STRL.rar

pdf

Tendernotice_1.pdf

html

1e437ed4-fab1-45bd-9739-9741a72428a0.html

rar

ARCH_DRG_1.rar

rar

ARCH_DRG_2.rar

xls

BOQ_862380.xls

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders