| 1 | Earth work in excavation by Mechanical means ( Hydraulic excavator) manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and remming of bottoms,lift upto 1.5 m,including getting out the excavated soil and disposal of surplus excavated soil as directed, within lead of 50m. (2.8.1-2.36) |
| 2 | Providing and laying sand filling/ watering, ramming consolidation and dressing complete including loading unloading and carriage of material from C&D plant to site complete in all respect as per the directions of Engineer-In-Charge. |
| 3 | Carriage of earth by mechanical transport including loading, unloading Lead of 2 km complete in all respect to the entire satisfaction of the Engineer-In-Charge. |
| 4 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:5:10 (1 cement : 5 coarse sand (zone-III): 10 graded stone aggregate 40 mm nominal size) DSR 4.1.10 |
| 5 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) (DSR 6.1.1) |
| 6 | 15mm cement plaster of mix: 1:4 (1 cement: 4 coarse sand) to the entire satisfaction of Engineer-in-Charge. (DSR 13.5.1) |
| 7 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished ,machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Granite of any colour and shade Area of slab upto 0.50 sqm (DSR 8.2.2.1) |
| 8 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of quired size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) (D.S.R 10.28). |
| 9 | Providing and fixing of fiberglass cartoon figures with sculpture of size upto 6'6”(Height)x5'0\\"(Width)x1'6\\"(Thickness) including painting with good quality paint and gloss coating including fixing on existing platform to the entire satisfaction engineer in charge. Cost includes all type of labour cost, material cost, transportation cost etc. |
| 10 | Providing and fixing of fiberglass figure of size upto 2’6\\"(Height)x1'6\\"(Width)x1'6\\"(Thickness) fixed on stainless steel pipe of length upto 9' and dia upto 1\\" including painting with good quality paint and gloss coating including fixing on existing platform to the entire satisfaction engineer in charge. Cost includes all type of labour cost, material cost, transportation cost etc. |
| 11 | SITC of 12-15W decorative LED Spike Light, 2700-3000k, THD<10%, P.F ≥0.95, CRI >70 having high quality toughened glass in clear finish for uniform light distribution, operating voltage range 140V-270V. The frame should be of pressure die cast aluminium housing, powder coated. The housing provides IP66 protection for high reliability in outdoor application. The conncetor should be IP 67. The job includes fixing the LED light on suitable foundation, fixing IP 66/67 (weather proof) junction box for outdoor installation with knockouts for cable entry & covering the whole assembly with MS wire mesh cover, properly fixed in foundation, for protection of LED fitting.Twinkle. The work shall be executed to the entire satisfaction of Engineer-in-Charge. |
| 12 | SITC of 18-20W projector light uplighter 2700-3000k, THD<10%, P.F ≥0.95, CRI >70 having high quality toughened glass in clear finish for uniform light distribution, operating voltage range 140V-270V & IP 68 water proof connectors. The frame should be of pressure die cast aluminium housing and powder coated. The housing provides IP66 protection for high reliability in outdoor application. The job includes fixing the LED uplighter on the floor and fixing IP 66/67 (weather proof) junction box for outdoor installation with knockouts for cable entry & doing the required electricity connection.Make: Twinkle. The work shall be executed to the entire satisfaction of Engineer-in-Charge. |
| 13 | Supply & laying PVC insulated Aluminum Conductor armoured ISI Marked cable of 2 Core 10 mm sq loose in trench/pipe. Supply & laying of ISI marked 2 core 10 mm sq PVC Insulated Aluminum conductor armoured cable (PVC Sheathed) of make Sunhome/ Finolex/ Cirtina/ Ecko/ Lapp/ Polycab/ KEI conforming IS:1554 (Pt.1) amended. The cable to be laid in trench/ pipe as per DSR Code 7.1.2/2022 MV CB PIP-25 Part-II (External). The cable should be terminated in existing/ new CC Collar with proper thimbling. The job included all Connections, Commissioning and testing of phase supply Material Testing report to be submitted and material to be supplied at site after confirmation from Engineer-in-charge. The specification of the cable as below:- i) Conductor – Aluminumii) Core – 2iii) Working Voltage – 1100 Viv) Nominal Cross Section – 6mm2 v) Minimum No. of Wire – 7/6Maximum d.c. Resistance at 20 Deg. C – 1.91 ohm/kmThe work shall be executed to the entire satisfaction of Engineer-in-Charge. |
| 14 | Supply & Laying of DWC pipe 51/63mm with hand bockey:- DSR 14.15.1 (75 cm below) Supply and Laying of pipe (OD-63 mm & ID-51 mm nominal) Double Wall Corrugated (DWC) With Hand Bockey High Density Polyethylene pipe ISI marked (HDPE Density 240 to 958 KG/Cm3) having corrugation on the outer wall and plain surface inner wall with average wall thickness for outer layer as 1.1+0.1mm and for inside layer 1.2+0.1mm maintenance free, ‘C’ value over 150 with lowest frictional losses, good weathering resistance, with all accessories like socket, bend, couplers etc. conforming to IS 14930/ IS 16205 complete with fitting and cutting, jointing etc.direct in ground (depth as per the direction of Engineer in charge or upto 75 cm below ground/ road level by digging the ground or cutting the road/ paver blocks upto required level & laying of DWC pipe for laying L.T. upto 1.1 KV grade) cables etc. including excavation and refilling the trench but including sand cushioning and protective covering etc., complete as required and PSEN-50086 (P-I & II) of Make Gemini, Rex, Duraline. The entire satisfaction of Engineer-in-Charge of work. |
| 15 | Supply & Laying of DWC pipe 51/63mm without hand bockey:- DSR 14.16.1 (75 cm below) Supply and Laying of pipe (OD-63 mm & ID-51 mm nominal) Double Wall Corrugated (DWC) Without Hand Bockey High Density Polyethylene pipe ISI marked (HDPE Density 240 to 958 KG/Cm3) having corrugation on the outer wall and plain surface inner wall with average wall thickness for outer layer as 1.1+0.1mm and for inside layer 1.2+0.1mm maintenance free, ‘C’ value over 150 with lowest frictional losses, good weathering resistance, with all accessories like socket, bend, couplers etc. conforming to IS 14930/ IS 16205 complete with fitting and cutting, jointing etc. direct in ground (depth as per the direction of Engineer in charge or upto 75 cm below ground/ road level by digging the ground or cutting the road/ paver blocks upto required level & laying of DWC pipe for laying L.T. upto 1.1 KV grade) cables etc. including excavation and refilling of digging including sand cushioning and protective covering etc., complete as required and PSEN-50086 (P-I & II) of Make Gemini, Rex, Duraline. The entire satisfaction of Engineer-in-Charge of work |
| 16 | Supply, Installation, Testing and Commissioning of Polycarbonate Junction box shall be insulated and made out of Polycarbonate with glass fiber reinforced. The size in mm should not be less then 155 x 210 x 92 cat. Part no KF1616. The Polycarbonate JB shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive. The Jb shall be rated for Degree of Ingress Protection IP 66/67 in accordance with IEC 60529. The gasket material shall be Polyurethane and the gasket shall be internally embedded. The JBs shall be comples with requirements of the Standards IEC 60998-1, IEC 60998-2-1, IEC 60670 - 22 & 60670 - 2.5. The manufacturer of Junction Box shall submite a copy of IEC Certificate. For better safety the Polycarbonate encl shall be fire retardant & self-extinguishing in accordance with IEC 60 695-11, DIV VDE 0304 Part 3, UL Subject 94 for Flammability V-2. It should be tested and Glow Wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures i.e. the Degree of Protection against Mechanical load shall be in accordance with EN 50298-98 for IK 08. The connecting terminal cable entry should be fixed in junction box for incoming and outgoing. The box shall be Hensel/ Schneider/ ABB (size suitable for termination of 2 x 10mm2 Armoured aluminium cable). Manufacturer should submit routine test certificate for CJB/PJB. The job includes supply and fixing of MS clamp of required size. The clamps is to be fixed on the backside of the box including welding/ drilling of holes complete in all respect and to be fixed on LT- RCC/ Steel tubular pole/ Wall at as certain height upto the entire satisfaction of Engineer-in-Charge |
| 17 | S/F PVC Conduit: 25 mmSupplying & Fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. The work shall be executed to the entire satisfaction of Engineer in charge. |
| 18 | Supply & Laying of flexible PVC insulated FR PVC sheathed 3 Core 1.5 mm2 Copper Cable conforming to IS - 694:2010 of make KEI/ Havell's/ Cirtina/ Finolex/ Lapp/ Polycab within the already erected 9 mtr Steel Tubular Pole and within bracket fitted on pole with the help of ladder/crane. The job include the cost of dismantling & re-erection fitting, bracket, managing traffic using proper precaution, making the required connection as started above and other petty material required to complete the job to the entire satisfaction of engineer-in-charge precautions of the work. |
| 19 | S&E of Outdoor type both side openable M.S. Cubical Pedestal of size 900mmx 600mm x350mm fabricated from 16 G.M.S. sheet welded on M.S. angle iron frame of size 50mmx 50mm x6mm with 4 Nos. legs of angle iron of same size each of length 600mm with M.S. sheet of size 100mm x 100mm x 6mm thick at the bottom of the legs. The front side of the pedestal should be openable with hiunged door provided with Godrej type handle and L-key locking arrangements (with 2 sets of L-key). A 'U' type support made from M.S. sheet of 16 G having width 75mmx 6mm be welded vertically in the inner side of the door to avoid entry of water. The door of the pedestal should be provided with rubber gasket to avoid entry of other insects etc. The top of the pedestal shall be covered with canopy made out of 16 G M.S. sheet projected outside to avoid entry of water. Four No. supporting members each of size 50mm x 6mm thick according to cubical size shall be welded for mounting switcher gear i.e. ICTPN, BBC, Timer and energy meter etc. The Pedestal shall be painted with two coats of P.O. red paint after applying one coat of red oxide. One No. The legs of the pedestal shall be embedded in the 1:2:4 C.C. mixture by digging 1' deep pit of 1' dia.The letter 'M.C.C.' in 4\\" size shall be written on the front door of the Pedestal. The job also included supply and erection one no. wooden plank/ board of size 1’-6’’ x 1’-6’’ and 25mm thick suitable for fixing energy mater including cost of screw, nuts and bolts in cubical pedestal complete in all respect. The pedestal will be housed on RCC foundation, Snowcem and platform of size 900 mm deep (450 mm underground and 450 mm above ground x 610 mm long x 360 mm wide including sufficient number of DWC pipe size of 51/63mm pieces to facility to entire the main cable and the circuit cable. The work shall be executed to the entire satisfaction of Engineer-in-Charge |
| 20 | S&E of Mouled Case Circuit Breakers (MCCB) of rating 63 Amp with Breaking Cap 16 kA, 415 Volts.Supply & Erection of 3 pole, 16 kA, 63 Amp MCCB with adjustable thermal and magnetic setting having Ics 75% of Icu. The MCCB is to be fixed in the feeder pillar complete in all respects. The MCCB should be make Havells/ ABB/ L&T/ Legrand/ Schneider. The work shall be executed to the entire satisfaction of Engineer-in-Charge. |
| 21 | G.I. Earth pipe electrode without salt/ Charcoal: DSR 5.2/2022 Supply and laying of earth electrode made out of ISI marked 'B' class earthing with G.I. earth pipe 4.5 mtr long, 40mm dia including accessories, G.I. pipe electrode shall be cut tapered at the bottom, and provided with holes of 12mm dia, drilled not less than 7.5 cm from each other upto 2 Mtr. of length from bottom (without charcoal or coke and salt). The earth electrode shall be laid in ground after boring as per CPWD specifications complete in all respect and to the entire satisfaction of the engineer-in-charge. |
| 22 | P/F 6 SWG G.I. earth wire in pipe: DSR 5.12/2022 Providing & laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipe from earth electrode, as required. |
| 23 | S/F’C series, SP MCB DSR 2.10.1Supply and fixing 6 amps to 32 amps rating, 240 volts ‘C’ series, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB Complete with connections testing and commissioning etc as required. Single pole 16 Amps “C” series Make of Anchor, Havells, Legrand, ABB, Siemens, L&T. The work shall be executed to the entire satisfaction of Engineer in charge. |
| 24 | Supplying and fixing DP sheet steel enclosure on surface/recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required complete in all respect. Make of Anchor, Havells, Legrand, ABB, L&T, Siemens. The specifications complete in all respect and to the entire satisfaction of Engineer-in-Charge. DSR 2.16 |
| 25 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way, Double door. Make of Panasonic, Anchor, Havells, Legrand, ABB, L&T. The work shall be executed to the entire satisfaction of Engineer in charge. DSR 2.3.1 Please Enable Macros to View BoQ information |