| 1 | Providing Services of the qualified and experienced staff for day to day maintenance of electrical installation & fans , fittings and control/ main panel board, DB, SPMCB etc & operation of pump sets i/c minor repair for all days excluding Sundays & holidays in general shift daily etc as required at fish seed farm, seelampur, Delhi in General shift in 9:00 AM to 5:00 PM by providing staff as per terms and condition of the agreement complete as required at site.(1). Wireman cum operator-1 No. (In General Shift)(2). Khallasi-1 No. (In General Shift) |
| 2 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 3 | 3 x 1.5 sq. mm |
| 4 | 3 x 4 sq. mm |
| 5 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 6 | 5/6 amps switch |
| 7 | 15/16 amp switch |
| 8 | 3 pin 5/6 amp socket outlet |
| 9 | 6 pin 15/16 amp socket outlet |
| 10 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 11 | 100 Amp, 30KA, FPMCCB |
| 12 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 13 | Single pole |
| 14 | Double pole |
| 15 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 16 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 17 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 18 | 18- 22 Watt (Powder Coated CRCA Sheet Body (Thickness >0.50 mm) |
| 19 | Supplying & Laying of one Number Following size. XLPE insulated PVC outer sheathed armoured with galvanized round steel wire or strip cables with standard aluminium conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with amendment No. 1 in following manners. |
| 20 | 4 x 16 sq.mm (Open Duct/existing trench) |
| 21 | 3.5 x 50 sq.mm (Open Duct/existing trench) |
| 22 | Supplying & laying of one Number Following size. XLPE insulated PVC outer sheathed armoured with galvanized round steel wire or strip cables with standard aluminium conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with amendment No. 1 in following manners. |
| 23 | 4 x 16 sq.mm (In the existing RCC/ HUME/ METAL/DWC pipe as required.) |
| 24 | 3.5 x 50 sq.mm (In the existing RCC/ HUME/ METAL/DWC pipe as required.) |
| 25 | Supplying & laying of one Number Following size. XLPE insulated PVC outer sheathed armoured with galvanized round steel wire or strip cables with standard aluminium conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with amendment No. 1 in following manners. |
| 26 | 4 x 16 sq.mm (direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering.) |
| 27 | 3.5 x 50 sq.mm (direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering.) |
| 28 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 29 | 4 x 16 sq.mm (28 mm) |
| 30 | 3.5 x 50 sq.mm (35 mm) |
| 31 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 best report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 32 | 150 watt (LED Street light fixture, powder coated pressuredie cast aluminium body (System lumen efficacy≥120 <135 lm/Watt) |
| 33 | Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under oltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for bea angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR,PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 34 | 70 watt (LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt) |
| 35 | 200 watt (LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt) |
| 36 | Credit for Old Dismantle materials |
| 37 | Assorted Fan |
| 38 | Assorted LED Fitting |
| 39 | Assorted Switch & Socket |
| 40 | Assorted Batten Fitting |
| 41 | Assorted MCCB |
| 42 | Assorted MCB Please Enable Macros to View BoQ information |