| 1 | Taking out Old U/S MCCB DB with MCCBs and Supply and fixing of MCCB DB VTPN 6 way as per IEC 61439-3 Suitable for Flush /Surface mounting with 250 A Copper Busbar for each phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management fully insulated busbar & shrouded Neutral bars improved Pan assembly for ease of installation prefitted masking sheet reversible metalic door for IP 43 & IP 54 DB's with provision for 100/125/160 Amp 4pole MCCB as incomer and SP/TP MCB's as outgoing complele all as specified and directed. |
| 2 | Taking out Old U/S MCCB DB with MCCBs and Supply and fixing of MCCB DB VTPN 4 way as per IEC 61439-3 Suitable for Flush /Surface mounting with 250 A Copper Busbar for each phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management fully insulated busbar & shrouded Neutral bars improved Pan assembly for ease of installation prefitted masking sheet reversible metalic door for IP 43 & IP 54 DB's with provision for 100/125/160 Amp 4pole MCCB as incomer and SP/TP MCB's as outgoing complele all as specified and directed. |
| 3 | Supply and fixing of MCCB 100A, 25kA, 4P, Thermal magnetic release , Ics=100% Icu . |
| 4 | Supply and fixing of MCCB 125A, 25kA, 4P, Thermal magnetic release , Ics=100% Icu . |
| 5 | Supply and fixing of MCCB 160A, 25kA, 4P, Thermal magnetic release , Ics=100% Icu . |
| 6 | Supply and fixing of MCCB 200A, 25kA, 4P, Thermal magnetic release , Ics=100% Icu . |
| 7 | Supply and fixing of MCCB 250A, 25kA, 4P, Thermal magnetic release , Ics=100% Icu . |
| 8 | Supply and fixing of MCCB 320A, 36kA, 4P, Thermal magnetic release , Ics=100% Icu . |
| 9 | Supply and fixing of MCCB 400A, 36kA, 4P, Thermal magnetic release , Ics=100% Icu . NOTE :- Taking down of MCCB is included against item No 1 & 2 above. |
| 10 | Taking out Old U/S MCB DB including MCBs of any type and any way. |
| 11 | Supply and fixing of MCB TPN DB 8 way double door as per IEC 61439-3 Suitable for Flush /Surface mounting with 100 A Copper Busbar for phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management fully insulated busbar & shrouded Neutral bars improved Pan assembly for ease of installation prefitted masking sheet reversible metalic door for IP 43 DB's for provision for MCB TPN upto 100A as incomer and SP/TP MCB's as outgoing complele all as specified and directed. |
| 12 | Supply and fixing of MCB TPN DB 6 way double door as per IEC 61439-3 Suitable for Flush /Surface mounting with 100 A Copper Busbar for phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management fully insulated busbar & shrouded Neutral bars improved Pan assembly for ease of installation prefitted masking sheet reversible metalic door for IP 43 DB's for provision for MCB TPN upto 100A as incomer and SP/TP MCB's as outgoing complele all as specified and directed. |
| 13 | Supply and fixing of MCB TPN DB 4 way as per IEC 61439-3 Suitable for Flush /Surface mounting with 100 A Copper Busbar for phase with 2 Neutral bar, 2 Earthbar and Cable ties for Cable management fully insulated busbar & shrouded Neutral bars improved Pan assembly for ease of installation prefitted masking sheet reversible metalic door for IP 43 DB's for provision for MCB TPN upto 100A as incomer and SP/TP MCB's as outgoing complele all as specified and directed. |
| 14 | Supply and fix MCB TP upto 63A, 10kA, 415V. NOTE :- Taking down of MCB is included against item No 10 above. |
| 15 | Supply and fix MCB TPN upto 100A, 10kA, 415V. NOTE :- Taking down of MCB is included against item No 10 above. |
| 16 | S&F ISI marked 30mA, 230V, FP RCBO 40/63 Amps for AC applications, conforming to IS:12640 (Part2)-2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP20 protected lower terminals and sliding shutters, all complete as specified and directed. |
| 17 | Taking down old unserviceable and Supply and fix On load change over switch in sheet metal enclousers 4 pole of capacity 63 Amp, 415 V, 50Hz including terminal shrouds, source separator and phase barriers conforms to IEC 60947-3 suitable for horizontal as well as vertical mounting on wall surface complete all as dierected. |
| 18 | Taking down old unserviceable and Supply and fix Plug and socket distribution box of CRCA sheet steel powder coated conforming to IS 8623-1 & 3, IEC 61439-1 & 3 for three phase and nuetral of capacity 40 Amp, 415 V, 4 pole controlled by housed MCB TPN 40 Amp, mounded/flushed on wall surfaces complete all as dierected.Note : MCBs shall be measured and paid separately under respective items. |
| 19 | M&L and replacement for submain wiring with PVC insulated, PVC sheathed, armoured, FRLS 1100 V grade, 3 core 10 sqmm stranded copper conductor fixed on wall roof/duct complete and connecting from TPN DB to SPN DBs with glands including taking out existing damaged cables complete all as specified and directed. |
| 20 | S & F in repairs digital time switch 3 phase of current capacity 16 Amps incl any type of accessories with suitable capacity of contactor after taking out unserviceable one. |
| 21 | Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame LED type (with total lumen output not less than 40000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 400 watt, with ingress protection IP 65 and surge protection device of 10 KV capacity etc incl necessary, angle iron supports , clamps etc complete and testing on completion all as specified and as directed. |
| 22 | S&F Integral decorative LED 20 Watts Post Top with opal acrylic with IP65 Protection mounted on 1.5 Mtr GI pole complete ( minimum medium grade 40 mm bore) with necessary PCC foundation and PCC block of 60cm height above ground including taking out old, U/S complete all as directed. |
| 23 | M&L for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, 3.5 core, cross-sectional area 120 sq. mm laying in treanches/wall/pipe complete all as specified and directed. Note : excavation/pipe shall be measured and paid seperately. |
| 24 | All as per Item No-23.00 here in before but of sizes, 95 sqmm, 3.5 core. |
| 25 | All as per Item No-23.00 here in before but of sizes, 70 sqmm, 3.5 core. |
| 26 | All as per Item No-23.00 here in before but of sizes, 50 sqmm, 3.5 core. |
| 27 | All as per Item No-23.00 here in before but of sizes, 35 sqmm, 3.5 core. |
| 28 | All as per Item No-23.00 here in before but of sizes, 25 sqmm, 4 core. |
| 29 | All as per Item No-23.00 here in before but of sizes, 16 sqmm, 4 core. |
| 30 | All as per Item No-23.00 here in before but of sizes, 10 sqmm, 4 core. |
| 31 | Excavation in trenches not exc 1.5 mtr wide and not exc1.5 mtr in depth for laying of cables etc. in soft/ loose soil and getting out all as specified and directed by Engineer-in-Charge. |
| 32 | Removing of paver blocks carefully and stack properly for refixing after laying of cables |
| 33 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils. |
| 34 | Removing excavated material n exc. 50m from the site of work and transporting out of the station/site of work suitable to the contractor all as specified. |
| 35 | Cutting existing road surface or hard standing, bituminous topping 15 cm but n exc 30cm girth for laying of pipes/ cables complete. |
| 36 | M&L for making good of road cutting upto 450 mm wide, clean the cutting surfaces and filling hard cor and match the existing bitumen surface of road with premix bitumenus material ready to use complete all sa specified and directed by Engr-in-charge. |
| 37 | M&L for in replacement of High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe, 40mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed. |
| 38 | M&L for in replacement of High density poly-ethylene pipes (HDPE) of pressure 4 kgf/cm2 pipe, 75mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed. |
| 39 | M&L for in replacement of High density poly-ethylene pipes (HDPE) of pressure 4 kgf/cm2 pipe, 100/110mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed. |
| 40 | Taking out Old U/S GI pipe of any type and any size. |
| 41 | M&L for GI pipe ,light grade 50mm dia for road crossing of cable for cable protection or above ground surface all as specified and directed. |
| 42 | M&L for GI pipe ,light grade 80mm dia for road crossing of cable for cable protection or above ground surface all as specified and directed. |
| 43 | M&L for GI pipe, light grade 100mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed. |
| 44 | M & L for earthing complete with Galvanised steel earth plate eletrode 60cmx60cmx6mm thick buried directly in ground vertically to (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised Iron Strip of size 32x6mm size with 40 mm bore light grade GI pipe as earth strip protection upto 7.5m, by means of Bolts, Nuts, Check Nuts and washer made of GI or Steel Earth connecting with test point, provision of Charcal and salt in alternate layers, watering pipe 20mm dia medium grade MS funnel with jali, PCC M-15 Type B-1 in pit with XPM not elss than 4Kg per Sqm and Earthpit with cover returning, filling, removing excavated material all as specified in electrical plate No 3 of SSR Part-I making good excavated surfaces such as hard standing refixing machine pressed precast concrete interlocking paver blocks removed during excavation on earthpit to mach existing surfaces after taking out old/unserviceable one complete and testing on completion all as specified and directed by Engr-in-Charge |
| 45 | M & L for Galvanised iron strip 32 x 6 mm burried in ground or fixed on walls/floor with suitable saddles and screws beyond 7.5mtr of earth lead connecting with test point complete all as specified and directed by Engineer-in-Charge. |
| 46 | Taking out Old U/S GI strip of any size |
| 47 | Taking down old unserviceable and Supply, install, testing and commissioning of LT panel mounted on angle iron frame 40 x 40 x 5 mm grouted on floor/PCC foundation,cubical outdoor type for 415V, 3 phase, 4 wire made out of CRCA sheet not less than 3 mm thick , vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 300 Amps rated copper bus bar, top and bottom cable entry with proper size glands as directed. LT panel shall be comprising of the following :-(a) MCCB 4 pole, 160 Amps, 25 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -01 No (Incoming)(b) MCCB 3 pole, 63 Amps, 16 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -06 Nos (Outgoing) (c) MCB SPN 40A, 10KA - 06 Nos.(d) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V,A,F,PF,KW,kVAR,kWH etc. (e) Phase indicator lamp R,Y & B - (01 Set oet three).(f) Power contactor 4 pole 40 Amp, 415 V - 02 No. (g) Analog time switch 3 module - 02 No. (h) Copper Bus bar, 300 Amps Rated - R,Y,B & N - (01Set of four) (i) Intetrnal panel wiring with copper conductor of suitable size. (j) Making good the disturbed surface of meter cabin room if any damages occures during fixing/shifting of panel. Note :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |