| 1 | (Supply Part) - 400 KVA 11/0.4KV Sub-Station |
| 2 | Distribution Transformer (O/D), 11/0.4 kV, 400KVA |
| 3 | Steel Tubular Poles (9 m, Working Load > 200 kgf/m²) |
| 4 | Muffs with concerete filling |
| 5 | X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for incomer line |
| 6 | MS Angle Iron (50X50x6 mm), Length: (2800 mm) x1 Nos for LA's |
| 7 | X-Arm: [Channel Iron (75x40x6 mm), Length : (2800 mm X 4 Nos] for supporting DO fuse unit & GO switch |
| 8 | Transformer LT Distribution Box and GO Switch fixing Assembly MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 9 | MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos |
| 10 | GO Switch Handle Supporting: [Channel Iron (100x50x5 mm), Length : 460 mm |
| 11 | GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type |
| 12 | D.O Fuse Unit |
| 13 | Surge Arrester, 9 kV Station Class (Porcelain Type) |
| 14 | Discs insulator sets (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) |
| 15 | Stay set complete in all respect including Stay Clamp |
| 16 | Stay Wire (7/3.15 mm) (7.0 kg Per Stay Set) |
| 17 | Pipe Earthing Set with G.I. Strips |
| 18 | 6 SWG GI WIRE FOR Earthing |
| 19 | LT Distribution Panel Box (MS Sheet of 1.6mm (1100*800*275mm) cubide box complete with stand etc and copper bus bar 40*6 mm powder coated with primer coating) Fitted With Bakelite sheet 500amp Copper Thimble MCCB 630 amp 3P 50kA-1No. & MCCB 250Amp 63kA-3Nos) make L&T, Schinder ABB , and SFU 9100A 6No, Rewireable) |
| 20 | Half Clamp (M.S. Flat 50X6 mm) |
| 21 | Full Clamps (M.S. Flat 50X6 mm) |
| 22 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 23 | Aluminium Thimble 300 Sq. MM |
| 24 | Thimble (copper) 200Amp |
| 25 | Danger Plate |
| 26 | Barbed Wire |
| 27 | LT Cable (3.5 Core) 300mm² * 2 incomer |
| 28 | LT Cable (3.5 Core) 240mm² *6 Outgoing |
| 29 | 3-Phase 4 wire C.T. Operated Satic Trvector meter (CT 1000/5 Amp) |
| 30 | Aluminium Paint. |
| 31 | Red Oxide |
| 32 | Capacitor Bank 135 KVAR for 400KVA (rate per kVAR) |
| 33 | Fiber Glass Ladder |
| 34 | Prov. Insulation Resistance Tester (Make : HTC 6250 5000V ,200G ohm 3 Ph. Battery Powered) |
| 35 | Providing Dell/HP AIO Desktop with: Intel Core i5-14500T-14th Gen Processor, 8GB DDR4 RAM expandable upto 16GB 512GB SSD, 23\\" LED Color display with FHD (1920×1080) Integrated HD Graphic & webcam, 2xUSB 3.0, 2xUSB 2.0, Audio jack/ VGA/ HDMI/ DP port, 10/100/1000m IPV6 compliant LAN, USB Keyboard & Mouse, internal speaker, 1x802.11b/g/n/ac, PL-Windows10 Pro 64bit O.S |
| 36 | Prov. HP Monochrome Multi Function Laser Printer HP Laser MFP 1188A Printer – A4 Size Paper, Printing Speed 20PPM, Resolution 1200Dpi, Memory 128MB, Copy Speed (Mono) 20CPM, Scan speed Black and Color 6PPM & 3PPM, USB 2.0, Paper Tray Capacity 150 pages. |
| 37 | Transportation Charges |
| 38 | (Supply Part) of 11 KV H.T. Line |
| 39 | 11KV XLPE Cable 3*120 mm2 Double i/c one Spare |
| 40 | Steel Tubular Poles 9 Mtrs Long |
| 41 | Steel Tubular Poles 10 Mtrs Long |
| 42 | Muffs with concerete filling |
| 43 | Cross Arm: [Channel Iron (100x50x6 mm), Length: 2800 mm i/c tolerance of 100 mm either side) x 3 struture |
| 44 | X-Arm (Horizontal) - MS Channel Iron C type 100*50*6 ] Length 1000mm |
| 45 | MS Channel Iron: 75x40x6, Length : 2800 mm for supporting GO Switch and DO Fuse Unit |
| 46 | 11 kV Pin Insulators (Porcelain, 12 kV, 10 KN): 3 No per pole structure |
| 47 | Stay set complete in all respect i/c Stay clamp (1No. / Single Pole , 4 No. / Double Pole Structures) |
| 48 | Stay Wire (7/3.15 mm) (10.0 kg Per Stay Set) |
| 49 | HT Earthing set complete (REC Constr. Stand. J-1) |
| 50 | Messanger Wire/Stay Wire (7/3.15 mm) for holding XLPE Cable |
| 51 | GI Cable Clamps for Holding XLPE Cable With Messanger Wire |
| 52 | Anchoring Assembly for HT |
| 53 | Suspension Assembly For HT |
| 54 | Facede Hooks For HT |
| 55 | Cable Termination Kit 120mm2 |
| 56 | 11 KV G.O. AB Switch Unit (11 KV, 400A, 25 KA) on tapping point |
| 57 | GO Switch Handle Supporting: [Channel Iron (75x40x6 mm), Length : 460 mm |
| 58 | D.O Fuse Unit |
| 59 | Half clamps: [On Double Pole Dead End structure: 4 No; On Run Thro' structure: 2 No ] |
| 60 | Full clamps: [On Double Pole Dead End structure: 4 No, Single Pole Run Thro' structure: 2 No] |
| 61 | Danger Plate (250X200X1.6 mm) |
| 62 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 63 | Barbed Wire |
| 64 | Red Oxide |
| 65 | Aluminium Paint |
| 66 | Transportation Charges |
| 67 | (Supply Part) of L T . Line |
| 68 | ACSR/6/1/3.35 (50mm2) { Includes 3 conductor Lengths for 3 Phsase and additional 1@% ( Sag, Jumpering and Wastage} |
| 69 | LT Cable XLPE UN-ARMOURED 3.5* 70 mm2 (Out going) |
| 70 | LT Cable XLPE UN-ARMOURED 3.5* 240 mm2 (Out going) |
| 71 | Steel Tubular Poles 9 Mtrs Long |
| 72 | Steel Tubular Poles 10 Mtrs Long |
| 73 | Muffs with concerete filling |
| 74 | Angle Iron (75x75x6) [Length- 1.50 Mtr |
| 75 | Shackle Insulator (16 kN) |
| 76 | D-Iron (U- Clamps) with nut bolts |
| 77 | Earth Knob |
| 78 | LT Stay Set (i/c Stay clamp |
| 79 | Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set) |
| 80 | Full Clamps [ 2 No for A.I + 1 No for Stay Set] |
| 81 | Half Clamp for X-Arm |
| 82 | Earthing Set complete |
| 83 | Earth wire (GI, 8 SWG) {Additional 1% (Sag and wastage)} @ 0.102 kg/m |
| 84 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 85 | Aluminium Paint |
| 86 | Red Oxide |
| 87 | Barbed Wire |
| 88 | Spiral PVC Spacer 3Phase |
| 89 | Transportation Charges |
| 90 | (Erection Part ) - 400KVA 11/0.4KV Sub-Station |
| 91 | Erection of 400 Kva,11/0.4KV Transformer, LT Box, MCCB Switch, Cable , service Cableand Energy Meter completed in all respect. |
| 92 | Un-loading and placing of 4oo KVA DTR on DTR Bed with Hydra complete in all respect |
| 93 | (Erection Part) ) of 11 KV H.T. Line |
| 94 | Erection Charges of Double pole Str |
| 95 | Erection Charges of Single pole Str |
| 96 | Erection Charges of GO Switch & DO Fuse Unit |
| 97 | Erection Charges of HT Stay set complete in all Respect |
| 98 | Erection Charges of HT Earthing set complete in all Respect |
| 99 | Erection Charges of XLPE Cable complete in all Respect |
| 100 | (Erection Part) ) of L TLine |
| 101 | Erection Charges of LT Steel tubular Pole |
| 102 | Erection Charges of LT Stay set complete in all Respect |
| 103 | Erection Charges of LT Earthing set complete in all Respect |
| 104 | Erection Charges of Conductor 6/1/.35 (50mm2) |
| 105 | Erection Charges of GI Wire |
| 106 | CIVIL PART (DTR foundation & chain link fencing of 400 KVA distribution transformer Bed) |
| 107 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 108 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:3:6 (1 Cement : 3 coarse sand): 6 graded stone aggregate 20 mm nominal size) |
| 109 | Centering and shuttering including strutting, propping etc. and removal of form for: Foundations, footings, bases of columns, etc. for mass concrete. |
| 110 | Centering and shuttering including strutting, propping etc. and removal of form for: Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 111 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:1.5:3 (1 cement : 1.5 coarse sand): 3 graded stone aggregate 20 mm nominal size) |
| 112 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 113 | C/o Chain Link Fencing for 250 KVA 22/0.4KV Sub-Station:- Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 114 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand) : 6 graded stone aggregate 20 mm nominal size) |
| 115 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement: 2 coarse sand) : 3 graded stone aggregate 20 mm nominal size) |
| 116 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 117 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm |
| 118 | Providing and fixing ISI marked M.S. pressed butt hinges bright finished with necessary screws etc. complete :125x65x2.12 mm |
| 119 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm |
| 120 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/ 10 sqm over an under coat of primer applied @ 0.80 ltr/ 10 sqm of approved brand and manufacture |
| 121 | Supplying, filling, spreading & leveling gravels of approved size in required thickness, for all leads & lifts, all complete as per direction of Engineer-incharge. |
| 122 | Centering and shuttering including strutting, propping etc. and removal of form for:Retaining walls, return walls, walls (anythickness) including attached pilasters,buttresses, plinth and string courses fillets, kerbs and steps etc. |
| 123 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 75 mm diameter Please Enable Macros to View BoQ information |