| 1 | Supplying, Installation, Testing & Commissioning of ‘Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:(A) Diesel Engine:Tourbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.(B) Engine mounted Instrument Panel fitted with and having digital dis Plate for following:(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubricantion Oil trip indication(ix) Engine Running Hours indication(x) Fuel Level125 KVA DG set (CPCV-IV)Make :- Kirloskar Green |
| 2 | S/F OF of 200 Amp. 4 pole change over switch with Sheet steel enclouser. |
| 3 | Supply, Installation, Testing amd Commissioning of LT Panel vermin proof floor mounting , M.S. channel base with bottom and Fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating.The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit of 50kA for panels having ACB as Incomer & 36kA for panels having MCCB Incomers. Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be completed in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering. INCOMING 200 Amp. MCCB-1 No AND OUT GOING 63 AMP MCCB-3 NOS |
| 4 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. 120 Sq mmx 3,1/2 core |
| 5 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. 35 Sq mmx 3,1/2 core |
| 6 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc.SIZE 10 sq. mm X 2 core |
| 7 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 8 | Providing and fixing 25 mm X 5 mm G.l. strip in 40 mm dia G.l. pipe from earth electrode including connection with G.l. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 9 | Earthing with copper earth plate 6000×600×3mm thick including accessories and providing masonry enclousre with cover plate having locking arrangement and watering pipe of 2.7 Metre long etc.with charcoal/coke and salt as required |
| 10 | providing and fixing 25 ×5 mm copper strip on surface or in recess for connections etc as required |
| 11 | supply and Making suitable Foundation with teen shad cover with angle iron and M.S sheet & M.S Clamp for 125 KVA DG set including all material and fixing charges labour . |
| 12 | Supplying and fixing 4 way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) |
| 13 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | Supplying and fixing following rating, 4 pol ,in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 Amp ,4POL MCB |
| 16 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.SIZE 4 X 16 sq. mm + 2 X 6sq. mm earth wire |
| 17 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.SIZE 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 18 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 ,1/2 X 120 SQ MM |
| 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3,1/2 X 35 SQ MM |
| 20 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2X 10 SQ MM Please Enable Macros to View BoQ information |