| 1 | Clear water Boosting P/Plant -W.T.P Campus at Basmatta |
| 2 | Supplying, installation, commissioning & testing of open well submersible pump set confirming to IS 8034 and motor confirming to IS 9283. Pump shall be suitable for various delivery head discharge with stainless steel pump shaft and bronze impeller. Motor suitable for working on 415±10%, 3 phase, 50 Hz A.C. supply with cable guard, thrust carbon bearing to with stand entire hydraulic thrust, water proof winding shall be provided. The pump set shall be suitable for direct coupling, pump shall have suitable outlet as per manufactures design. Anti-thrust stream lined non return valve shall be provided with pump. 3 mtr submersible copper conductor cables in single/ double run shall be provided with each pump. Submersible pump set with bronze impeller. Head range- As per required (mtr), Discharge- as per required (m³/Hr), rpm 2905, No. of stage- Minimum, duty point head (nominal) -29 meter, discharge (nom.) -16.67 LPS, overall efficiency->70%, Pump Make- KSB/Kirloskar/Aqua/Crompton/ |
| 3 | Cost towards replacement of old panel by supplying, installation & commissioning of new wall mounting type industrial panel board comprising 100 amp copper bus bar 04 nos. in M.S. steel (14SWG) housing with following accessories-• 100 amp T.P.N. MCCB make L&K/C&S/Siemens -01 No. as incomer feeder.• 63 amp T.P.N MCCB make L&K/C&S/Siemens - 2 nos. as outgoing feeder. • 63 Amp Spare MCCB make L&K/C&S/ Siemens -01 No.• Multi protection device (MPD)- phase preventer, Over-Under voltage preventer, overcurrent preventer etc.-02 nos. for both starters make-L&K/ Minilac / C&S/ Siemens / Schneider/Any reputed make.• Ammeter- digital ammeter-02 Nos. with selector switch L&K/C&S make.• Voltmeter- Digital voltmeter-02 Nos. in 3 phase R-Y-B• Indicating lamp LED- in Red, Yellow and Blue color-1 set.(Phase indicator)• 32 amp. DP MCB for light load and other loads of L&K/Havel’s/C&S make -2 nos.• DOL submersible Pump controller-02 Nos. Make-L&K/C&S/Schneider suitable for above submersible pump set.Panel should be dully painted with two coats super enameled paint of approved color one coat of red oxide primer and internally wired with suitable size of copper wire etc. all complete. |
| 4 | S/F of 90/100 watt LED Flood lighting luminaire with pressure die cast housing and toughened glass cover , operating voltage range 100V-270V AC with structure, stand, clamp, tee, wires and switches etc. all complete at c/w water p/plant. |
| 5 | Cost supplying and laying of 25 sq. mm x 3.5 core XLPE aluminum armored 1.1 KV grade cable from Transformer to main switch in the WTP campus. (Confirms to IS:1554, PART-1) |
| 6 | Raw water P/Plant –Intake Well at Jhajhapara. |
| 7 | Supplying, installation, commissioning & testing of submersible pump set confirming to IS 8034 and motor confirming to IS 9283. Pump shall be suitable for various delivery head discharge with stainless steel pump shaft and bronze impeller. Motor suitable for working on 415±10%, 3 phase, 50 Hz A.C. supply with cable guard, thrust carbon bearing to with stand entire hydraulic thrust, water proof winding shall be provided. The pump set shall be suitable for direct coupling, pump shall have suitable outlet as per manufactures design. Anti-thrust stream lined non return valve shall be provided with pump. 3 mtr submersible copper conductor cables in single/ double run shall be provided with each pump. Submersible pump set 150 mm dia. (with bronze impeller). Head range- 72-105.8 meter, Discharge- 110 - 40 m³/Hr, rpm 2905, No. of stage- 6, head (nominal) 96 meter, discharge (nom.) 22.2 L/S, overall efficiency- > 65%, Pump Make- KSB/CRI/Crompton/Wilo/ Aqua |
| 8 | Cost towards supplying and fitting of 125mm dia. 3 mtrs. long MS black column pipe of wall thickness 6 mm with flange at each end total -04 Nos., & 1.5 mtrs. long-01 no. flange at each end, reducer short piece with flange 150mmx125mm-01 no., 125 mm dia. 2.5 ft long MS adopter-01 No. with nut-bolts-, rubber insertion, all labour tools and tackles and transportation charges etc. all complete. |
| 9 | Providing all labours, tools, tackels and technician for disconnection and taking out 50 HP old submersible pumps set with column pipe from intake well all complete (for Pump set No.-01). |
| 10 | Cost towards supplying all labour tools and tackles for complete opening, dismantling, of 50 HP, 440 Volt, 50c/s, star delta, 3 phase Submersible motor and complete rewinding of the motor with supply of PVC insulated submersible copper winding wire, tapping, repairing of motor with repairing of stator and rotor, & reassembling and then testing on full load and, with including the deduction of scraps, transportation charges etc. all complete. Wt. of pvc copper winding wire -34 kg (approx.) With changing of following bearing:- (i) SS/Carbon Thrust bearing as per sample and at raw water p/plant Jhajhapara. |
| 11 | Providing all labours, tools, tackels and technician for lowering after repairing of 50 HP submersible P/Set with column pipe into intake well all complete (for Pump set No.-02). |
| 12 | Cost towards repairing of 100 KVA Oil cooled Servo Voltage Stabilizer working on three phase input Voltage-240 to 400 V and Output-400±1%V. Make-Power Line with following works-i. Cost towards disconnection and cleaning & drying of stabilizer with all labour tools and tackles.ii. Cost towards S/F of servo motor as per sample-10 kg -01 No.iii. Cost towards s/f of Panel Sensing/control PCB Card as per sample-01 No.iv. R.C kit-01 No.v. Wiring of stabilizer with 4 sq. mm wire Control transformervi. Replacing of analog meter to 3-phase Digital Voltmeter (Output) as per sample-03 Nos.vii. Cost towards supplying and filling of transformer oil.-250 Ltrs.Cost towards complete servicing and repairing cost of stabilizer with all labour, tools and tackles and electrician charges etc. all complete job and testing on full load. Intake well Jhajhapara, Masanjore. |
| 13 | Cost towards special repairing of motor control panel with FASD starter – 2 nos. and 200 Amp, 415Volts MCCB incomer-01 No. 100 Amp outgoing MCCB-02 Nos. with changing following accessories i. L&K MNX contactor as Main contactor (MNX-70) - 01 No.ii. Star contactor (MNX-50) and delta contactor (MNX-70) - 01 No. eachiii. Front & Side Add on Auxiliary contacts- (2NO+2NC) - 01 no. each. iv. Thermal overload Relay-01 No.v. Timer (0-60 sec)-01 No.vi. ON-OFF push buttons-02 Nos.vii. 3 phase Digital Voltmeter-01 No. C&S/ L&K/ Schneider make.viii. 3-phase Digital Ampermeter-01 No.ix. Multi protection Device-02 nos. C&S/MPD/ L&K/Minilac/Schneider make.x. 3 way selector switch-03 Nos.xi. CT 200/5A-03 Nos. and changing of damaged wires as per required and copper lugs., LED Phase indicating bulb-06 Nos., 16 mm2 single Core power cable grip to panel board-10 Mtrs., and 2.5 sq. single core copper cable-20 mtrs. Etc. with all fitting charges at Raw Water p/plant- Jhajhapara. |
| 14 | Cost towards supplying and fitting of 25 mm2 x 3 core PVC insulated, PVC sheathed copper conductor flat submersible cable as per IS:7098. |
| 15 | Cost towards denting and painting of Electro-mechanical components as Panel board, NR Valve, column pipe of submersible motor with primer and two coat of Metal Oil paint as required at Raw water p/plant. |
| 16 | Add 18% GST |
| 17 | Add 1% Labour Cess Please Enable Macros to View BoQ information |