| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2X 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor (Polycab Green/Havell Life guard/ Fenolex/ Salzer/RR/Apar/ Grandly make as desired by engineer incharge ) single core cable in surface / recessed medium class PVC conduit,( including the cost of conduit) with modular switch Antibacterial series ( Legrand /ABB / Siemens make.), modular plate,suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Wiring for lighting points/fan points/ exhaust fan points/call bell points with 1.5 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit, with 240V 6A modular switch , modular plate and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable, etc. as required. (Havells/ Polycab/ Anchor/ Finolex/KEI/RR/Apar/Grandly or equivalent make ) incl. cost of conduit. |
| 3 | Supplying and fixing of suitable size GI box with modular plate and modular cover in front on surface or in recess, including providing and fixing of 6 pin 15/16 A modular socket outlet and 15/16A modular switch, connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent) |
| 4 | Supplying and fixing of suitable size GI box with modular plate and modular cover in front on surface or in recess, including providing and fixing of 2 no. 3 pin 5/6 A modular socket outlet and 2 no. 5/6A modular switch, connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or eq.) |
| 5 | Supplying and fixing of modular sockets/ indicators/switches on existing modular plate and switch box , incl. connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent) |
| 6 | i.3 pin 5A - 10A socket. |
| 7 | Indicator |
| 8 | Point wiring for 5A -10A socket out lets (computer points) with 2x2.5 sq mm (P+N)FRLS PVC insulated 660/1100volt grade flexible stranded copper conductor wires in recessed or surface conduiting system and earthing the point with 1 x 2.5 sq. mm single core copper wire (loop earthing),(Maximum two points shall be connected on one circuit).(Havells/ Polycab/ Anchor/ Finolex/KEI/RR or equivalent) incl. cost of conduit |
| 9 | Supply, installation, testing and commissioning of 18 Watt LED recessed/ mounted (round or square) Down lighters having aluminum body, minimum 100lm/w, average life 50000 hours, LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India , Operating temperature -10`C to +45`C. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro).Commercial series. |
| 10 | Supply, installation, testing and commissioning of 50Watt LED Flood lighting luminaries having aluminum body, minimum 100lm/w, the luminary housing should be aluminum and the luminary optics shall have a high efficiency with transmittance, average life 50000 hours, Operating temperature -10`C to +45`C. LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro). |
| 11 | Supply, installation, testing and commissioning of 100Watt LED Flood lighting luminaries having aluminum body, minimum 100lm/w, the luminary housing should be aluminum and the luminary optics shall have a high efficiency with transmittance, average life 50000 hours, Operating temperature -10`C to +45`C. LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro). |
| 12 | Supply, installation, testing and commissioning of 1 star 1200 mm sweep ceiling fans of Havells / Crompton /Bajaj/ Anchor , incl. cost of extension of GI rod (if required) and making of necessary connections. |
| 13 | Supply and fixing of two module stepped electronic fan regulator on the existing modular plate switch box, incl. connections but excluding modular plate etc. as reqd. |
| 14 | Supply, installation, testing and commissioning of 200-250 mm sweep shutter type exhaust fans, incl. cost of ceiling rose and making of space in walls/ windows as per site and necessary connections. (Havells/ Anchor/ Crompton). |
| 15 | Supply, installation, testing and commissioning of 600-650 mm sweep large industrial type exhaust fans, incl. making of space in walls/ windows as per site and necessary connections. |
| 16 | Supplying and fixing of modular blanking plates on existing modular plate and switch box ,excluding modular plate as required. |
| 17 | Wiring for sub mains along with earth wire in FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, incl. cost of conduits(Havells/ Polycab/ Finolex/ Anchor/KEI/RR or equivalent). |
| 18 | 2 x 2.5 sq.mm + 1x 2.5 sq. mm earth wire |
| 19 | 4 x 6 sq.mm + 2x 6 sq. mm earth wire for three phase points |
| 20 | 4 x 10 sq.mm + 2x 6 sq. mm earth wire |
| 21 | Supply and fixing of 8 way (4 + 24) Double door surface/ recess mounting , Vertical/ Horizontal type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, excluding cost of MCBs and Incomer. . |
| 22 | Supply, installation, testing and commissioning of 5-32A single pole rating 240/415V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCB DB complete with necessary connections. |
| 23 | Supply, installation, testing and commissioning of 32 A DP rating 240V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 24 | Supply, installation, testing and commissioning of 63 A DP rating 240V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 25 | Supply, installation, testing and commissioning of 63A TP&N rating 240/ 415V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 26 | Providing of chemical earthing as per IS standards by way of digging 8 feet pit then embedding 2.5 mtr. Long GI earthing electrode, 60 mm dia. Connecting the plate with main control board by 10 SWG Copper wire with 1/2” dia. Full thread brass nut/ bolts and washers, refilling the pit with chemical compound. |
| 27 | Supply, installation , testing and commissioning of 30 KVA, 3-Phase, 415V,LT, Unbalanced AVR of Essentials, KE, ALBA, Chinar, Cosco make, operating from input voltage of L-L=155-460V & L-N=90-265V, thereby producing the output voltage of 415V +_2% Phase to Phase and 230V +_2% Phase to Neutral. The AVR should have inbuilt Over voltage protection, Under voltage protection & Over loading with TDR. The stabilizer shall be servo controlled automatic, ONAN cooled and provided with first filling of fresh filtered transformer oil having required di-electric strength. The stabilizer shall be capable of smooth operation up to 10% un-balanced in the load currents complete with servo bye pass system consisting of 100A four pole manual type change over switch, 100A four pole MCCB 01 no. and required bus bar. The supplier has to give guarantee for any manufacturing defect with three servicing of the equipment for two years reckoned from successful commissioning. The job also includes all applicable taxes, carriages, loading and unloading. |
| 28 | Supply, laying, connecting and commissioning of 150 sq. mm 3.5 core PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade Aluminum LT cable , incl. cost of required al. thimbles duly crimped. ( under ground). |
| 29 | Supplying and laying of DWC HDPE (Double Wall Corrugated High Density Polyethylene) pipe, 200 mm dia.(OD – 200 mm & ID – 175 mm) ISI marked along with all accessories like sockets, bends, couplers, etc. with fitting and cutting, jointing, etc. (under ground), including excavation and refilling the trench after laying the pipes.(complete job) |
| 30 | SITC of wall/free standing floor mounted dust and vermin proof compartmentalized cubical panel for electrical Works, made out of CRCA sheet. Other parameters required as per point (a) Thickness of sheet shall not be less than 1.6 mm up to 600 mm length/width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartment shaving bolted type doors with/without detachable extension type structure. (b) Panel shall be duly treated for derusting in 7 tank process with de phosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/Neoprene rubber gasket of not less than 3mm thickness, required hardware, separate detachable gland plate M.S. base channel (min 75mm), hinged door with locking arrangement for equipment/switchgear c) Interconnection between bus bar and switch gears/cable shall be rigidly supported and made out by flexible copper wires (upto 125 amp) and by solid bus bar (> 125). (d) Only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator, CPRI Test certificates to be submitted) All as per pre approved by Engineer in charge. |
| 31 | Providing and fixing following rating and breaking capacity and pole MCCB with thermo magnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Thermal Magnetic type, Adjustable type) |
| 32 | Normal Incoming |
| 33 | 250 Amp, 50 KA, FP MCCB |
| 34 | Aluminum Bus Bar 500 Amp set of 4 strips |
| 35 | ON Load Change Over Switch FP 200 amp. (Front operated) |
| 36 | Aluminum Bus Bar 400 Amp set of 4 strips |
| 37 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, etc. |
| 38 | Outgoing |
| 39 | 63 Amp, TPN MCB 10KA |
| 40 | 63 Amp, 10 KA, DP MCB |
| 41 | Space for 16 way MCBs |
| 42 | Providing and laying of 4 sq.mm 4 core 2Xwy copper XLPE insulated armored stranded FRLS cable1.1KV from LT panel to machines/ equipments. |
| 43 | Supply , installation, testing and commissioning of industrial socket/plug with 32A top and 32 A TPN MCB with box.(complete job) |
| 44 | Supply , installation, testing and commissioning of industrial socket/plug with 32A top and 16 A TPN MCB with box.(complete job) |
| 45 | Supply and erection of Mild Steel Swaged Tubular Pole confirming to IS: 2713-1980 ( Part I-II) with base plate. The pole shall be made from steel tube and pipe (IS : 1141, Fe 410)including excavation of the pit and filling up the same with cement concrete of M15 Grade (1:2:4 mix)from base plate to 50 cm above ground level, earthing terminal, cable entry with 32mm dia B- class GI cable sleeves. The pole shall be painted with 2 coats of red oxide primer and 2 coats of enamel paint of silver. The job also includes the cost of form work and carriage of all required materials. (9 mtr. 410 SP-28) |
| 46 | Providing and fixing of detachable type round or square bracket (suitable for 6 lights) of 40 mm dia. GI pipe as per requirement. |
| 47 | Supply, installation, testing and commissioning of 120Watt LED Flood/High Mast lighting luminaries having aluminum body, minimum 100lm/w, the luminary housing should be aluminum and the luminary optics shall have a high efficiency with transmittance, average life 50000 hours, Operating temperature -10`C to +45`C. LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro). |
| 48 | Supply, laying, connecting and commissioning of 16 sq. mm 4 core PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade Aluminum LT cable , incl. cost of required al. thimbles duly crimped. ( under ground). |
| 49 | Supplying and drawing FRLS PVC insulated copper conductor single core cable through pole up to light. |
| 50 | 2 x 2.5 sq. mm (P + N) |
| 51 | 1 x 2.5 sq. mm (Loop/ Common earth) |
| 52 | Providing and fixing/ laying of earthing station by way of placing GI electrode rod/ pipe in a pit , connected through GI strip. (complete job) |
| 53 | Providing and fixing of sheet steel enclosure with knock out for cable entry/out incl. fixing with nut bolts of suitable size with 100A connector 3 no. 6/10A MCBs for controlling the High Mast lights. Please Enable Macros to View BoQ information |