Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Schedule-A |
| 2 | Comprehensive maintenance for single phase AMR meter software hosting, GPRS Charges, meter calibration testing with multimeter, RF network monitoring and trouble shooting and repair/replacement of meter parts with manufactruing defect complete all as specified and as directed by Engr-in-charge (AMC for 440 Meter/ per month for 09 Months). |
| 3 | Comprehensive maintenance for for three phase AMR meter software hosting, ,GPRS Charges, meter calibration testing with multimeter, RF network monitoring and troubleshooting and repair/replacement of meter with manufactruing defect complete all as specified and as directed by Engr-in-charge.(AMC for 80 Meter/ per month for 09 Months). |
| 4 | Comprehensive monthly maintence of auto fire alarm system installed in 13 BRD/16 BRD AF Stn Palam. The detail scope of work consists of the following :-(i) Cleaning inspecting, checking and repairing if required all the equipments of fire detection system.(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.(iii) The contractor shall submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge on monthly basis.(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.(v) Emergency visit shall be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.(vi) Material required for replacement shall be measured and paid separately under respective items of this schedule as 'Supply and fixing' and labour component for the same is not included in comprehensive maintanance contractor shall quote the rate accordingly. (vii) Testing of entire fire alarm system and rectification of fault complete to the entire satisfaction of engr-in-charge all as specified and directed . |
| 5 | Supply and installation in replacement of response indicator lamp complete all as specified and as directed. |
| 6 | S&F in replacement of addressable duct detector with multiple sensitivity level, programmable for timed automatic sensitivity and with base UL listed complete all asspecified and directed. |
| 7 | S&F in replacement of Analogue addressable control modules complete all as specified and directed. |
| 8 | S&F in replacement of Analogue addressable fault isolator module capable of monitoring shorted loop circuit and automatically restore communication when shorted conditions are re corrected complete all as specified and directed. |
| 9 | S&F in replacement of Addressable Dual tone electronic sounder / hooter enclosed in MS box with LED indication hooter complete all as specified and directed. |
| 10 | M&L 2x1.5sqmm+1x1sqmm PVC insulated unsheathed, FRL Smultistr and edcopper conductor cable,1100V grade asper IS1554 Part Idrawn through and including ERW steel conduitnot less than 20 mm dia duly painted complete all asspecified and directed. |
| 11 | M&L 2x4.0 sq mm +1x2.5 sq mm PVC insulated unsheathed, FRLS multistrand and copper conductor cable, 1100V grade as per IS1554 Part I drawn through and including ERW steel conduit not less than 20mm dia duly painted complete all asspecified and directed. |
| 12 | S&F in replacement of 9 volts DC battery for wireless smoke detector complete all as specified and as directed. |
| 13 | S&F in replacement of hooter radio meter operating voltage 15 volts DC, indication alarm 85 db, complete all as specified and directed. |
| 14 | S&F in replacement of MCP remote key of black colour including testing with battery complete all as specified and directed. |
| 15 | M&L in replacement of wire less smoke detector having 9 volt DC battery, smoke sencor temp range (10-70 ) degree centigrade, humidity range 20 % to 95 %, including testing complete all as specified and directed. |
| 16 | Supply and fixing in replacement of response indicator as per existing make and model complete all as specified and directed. |
| 17 | Supply and installation in replacement of 12 volt 7 AH battery complete all as specified and directed. |
| 18 | Taking down of old unserviceable optical type smoke detector and supply and testing of detectors complying with and type certified to EN-45 adjustable type smoke detector Photo electric / Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed . |
| 19 | Supply and fixing in replacement of mother board suitable for Fire alarm system complete all as specified and directed. |
| 20 | Supply and fixing in replacement of Power Supply card suitable for Fire alarm system complete all as specified and directed. |
| 21 | Supply and fixing in replacement of manual call point resettable type complete as directed. |
| 22 | Supply and fixing in replacement of electronic sounder cum strobe complete all as directed. |
| 23 | Supply and fixing in replacement of Repeater Panel 08 Zone complete all as specified and directed. |
| 24 | Supply and fixing in replacement of 1.5 sqmm three core PVC insulated sheathed ISI marked FRLS copper conductor multi stranded 1100 volt grade cable drawn through existing conduit connecting and testing all as specified and directed. |
| 25 | Supply and fixing in replacement of Heat Detector with Base complete all as specified and directed. |
| 26 | Supply, installing, connecting and testing in replacement of Three phase automatic change over switch of capacity TPN 63 Amps complete all as specified and directed. |
| 27 | M&L in replacement of 4.0 sq mm 3 core PVC insulated unsheathed, FRLS multistranded copper conductor cable, 1100V grade as per IS1554 Part I drawn through and including ERW steel conduit not less than 20 mm dia duly painted complete all asspecified and directed. |
| 28 | Comprehensive monthly maintence of 1 X 30 KVA UPS and 1X 105 KVA system installed in 13 BRD AF Stn Palam. The detail scope of work consists of the following :-(i) Execute diagnostics and physical checks.(ii) Examine, clean, test, all equipment as required and repair parts as and when required.(iii) Measurement of UPS parameters like input/output voltage, frequency, current, frequency, room temperature etc.(iv) Battery Parameters like voltage, current and other relevant parameters.(v) Ensure dust free and controlled temperature conditions.(vi) The corrective maintenance may require multiple visits to site (vii) Check all Equipment LED LCD display board if any fault found to be rectified in the same cost.(viii) Checking of servicibility of MCB/MCCB if found unserviceagle to be replace without any extra cost. (ix) Checking of UPS fuse. if found us to be replace.(x) Keeping of servicibility of UPS is the responsibility of the contractor for the entire contract period.Note : Response time should be not more than 24 hours from the time of receipt of complaint on any working day between 9 AM to 6 PM. |
| 29 | Disconnect the unserviceable battery lead connections from 65 AH/100 SMF battery of 30 KVA/105 KVA UPS and transport the us battery to work shop for reconditioning work by using dedicated battery regenerator. Sulfation on plates should be removed by using high powered pulses, replace the us battery terminals , replace the electrolyte and recharge the battery upto 24 to 36 hours to gain more than 12 volts. After completion of reconditioning work the battery will be refix at the same position including necessary testings complete all as specified and directed. |
| 30 | Disconnect the cable connection from unserviceable electric siren from site and refixing the same after completion of necessary repair work complete all as specified and as directed |
| 31 | Supply and installation in replacement of 12 volt 65 AH battery for 30 kVA UPS complete all as specified and directed. |
| 32 | Supply and installation in replacement of 12 volt 100 AH battery for 105 kVA UPS complete all as specified and directed. |
| 33 | M&L for opening of electric siren motor and , cutting the burnt winding from motor and rewinding the motor with super enamelled copper wire as per existing size and gauge with and including provision of insulating material varnishing with good quality varnish including replacement of all unserviceable parts such as safety pin, fan blade,bearings and three core copper wire etc complete all as specified and as directed by Engr-in-charge. |
| 34 | Repair/Servicing of Siren,horizontal double mounting, single phase,audible range 3.25 KM at 220/250 volt, 6000 rpm, 50 Hz, AC complete all as specified and directed. |
| 35 | M&L in replacement of 3 core copper conductor of size 2.5 sqmm cable 1100V grade complete all as specified and as directed by Engineer- in Charge. |
| 36 | Disconnect the cable connection from unserviceable single phase AMR meter from existing meter panel box and deposit to MES office complete all as specified and as directed |
| 37 | Disconnect the cable connection from unserviceable three phase AMR meter from existing meter panel box and deposit to MES office complete all as specified and as directed |
| 38 | S&F in replacement of unserviceable Single Phase AMR Meter with the following specifications:• AC Single Phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt Low Power Radio Frequency (LPRF) communication facility in Cyanconnode or equivalent Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry.• Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy, cumulative apparent energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand• Meter should have connect / disconnect functionality operable from billing software |
| 39 | S&F in replacement of unserviceable Three Phase AMR Meter with the following specifications:• AC Three Phase Four Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt Low Power Radio Frequency (LPRF) communication facility in Cyanconnode or equivalent Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry.• Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy, cumulative apparent energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand• Meter should have connect / disconnect functionality operable from billing software |
| 40 | M&L for repair of single phase AMR meter two wire LCD dispaly/ dial type any make 5-30 Amps complete all as specified and as directed by Engineer- in Charge. |
| 41 | M&L for repair of three phase AMR meter four wire LCD dispaly/ dial type any make complete all as specified and as directed by Engineer- in Charge. |
| 42 | S&F ISI marked electric energy meter single phase two wire LCD dispaly 5-30 Amps complete all as specified and as directed by Engineer- in Charge. |
| 43 | S&F ISI marked electric energy meter three phase four wire LCD dispaly 10-60 Amps complete all as specified and as directed by Engineer- in Charge. |
| 44 | Demolition of cement concrete in ground floors and paving not exceeding 15 cm thickness (below or above ground level) complete all as specified and directed. |
| 45 | M&L for PCC 1 : 3 : 6 type C1( Using 20 mm graded crushed stone aggregate) for foundation / concrete blocks / earthing chamber / chamber cover complete all as directed by Engineer-in-charge at site. |
| 46 | M& L in replacement of test point terminal block made out of gun metal or phosphorous bronze of size 75x75x25 mm drilled & screwed including 3 hole,8mm dia 25mm long hexagonal head with nuts & washers complete as specified and directed. |
| 47 | S &F in replacement air temination, single pointed aluminium rod 12mm dia and 300mm long all as specified and directed. |
| 48 | S &F in replacemen air temination, single pointed copper rod 12mm dia and 300mm long all as specified and directed. |
| 49 | S&F in replacement of 50 mm bore GI tubing, light grade galvanized with all fitting and fixed to walls and ceilings or laid in floors for earthing strip protection complete. |
| 50 | S&F in replacement of 15 mm bore GI tubing, medium grade galvanized with all fitting and laid in trenches complete. |
| 51 | S&F in replacement of 15 mm bore GI tubing, medium grade galvanized with all fitting and fixed to walls and ceilings or laid in floors of complete. |
| 52 | S&F in replacement gun-metal, globe or gate valves, with iron wheel head, screwed both ends to iron pipe and fixed to 15 mm bore pipe complete. |
| 53 | S&F in replacement gun-metal, globe or gate valves, with iron wheel head, screwed both ends to iron pipe and fixed to 20 mm bore pipe complete. |
| 54 | M&L for colour coding of earthing pit cover and indication plate with rod with the following colour:- Red for chemical earth pit. Yellow for conventional earth pit. The numbering/marking of earth pit will be in capital black colour and is to be done as directed by Engineer -in- Charge. |
| 55 | M& L For industrial salt for earthing pit recharging all as directed by Engineer in charge |
| 56 | M& L For technical grade Magnisium Sulphate for earthing pit recharging all as directed by Engineer in charge |
| 57 | M & L for testing of earth resistance value of existing earthing pits once in a month with digital type earth tester at different locations of 13 BRD/16 BRD area up to the entire satisfaction of AF personnel & submitting the earth result all as directed. Note : Testing of all earth pits will be carried out on monthly basis and the same will be measured in presence of Air force staff. |
| 58 | Tightening and fixing in position loose hanging copper/aluminium strip of any size on wall or building roof using new insulators of porceline of approved size and fixing existing Aluminium/copper strip on the same as existing.(Insulators will be measured and paid separately against the item in the schedule) |
| 59 | Supply and fix Copper Strip of size 20 X 3 .15mm in replacement to aluminium strip buried/laid in trenches/fixed on wall/tower etc complete all as specified. |
| 60 | Supply and fix Copper Strip of size 25 X 3 mm in replacement to aluminium strip buried/laid in trenches/fixed on wall/tower etc complete all as specified. |
| 61 | Supply and fix Copper Strip of size 32 X 6 mm in replacement to aluminium/GI strip buried/laid in trenches/fixed on wall/tower etc complete all as specified. |
| 62 | Supply and fix in replacement of flexible Copper Strip of size 20x3 mm thickness complete all as specified. |
| 63 | M & L for copper brazing with copper strip/copper rod complete all as specified. |
| 64 | Supply & Fix in replacement of PVC insulater supporter with nut bolts / screws for fixing of copper / aluminium strips / GI strips on walls/PCC blocks etc . |
| 65 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers , of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including provision of GI strip protected by 40 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation and earth work & connecting the earthing to an earthing test point complete all as specified & directed by Engr-in-Charge. |
| 66 | Supply and fix in replacement of Aluminium Strip of size 25 X 3 .15mm buried/laid in trenches/fixed on wall/tower etc complete all as specified. |
| 67 | Supply and fix in replacement of GI Strip of size 25 X 3 .15mm buried/laid in trenches/fixed on wall/tower etc complete all as specified. |
| 68 | M& L char coal for earthing pit recharging all as directed by Engineer in charge |
| 69 | M & L for earthing of equipments with copper plate earth electrode 60cmx60cmx3.15 mm thick buried directly in ground (earth pit not less than 3.00 mtr below ground level with top edge of plate not less than 2.25m. below ground level) brazed with copper strip 20x3 mm size 7.0 mtr long and connected to copper strip of any size by means of copper bolts, nuts, check nuts and washers complete all as specified and directed.Note:- The rated quoted is deemed to the inclusive of the followings:-(a) The excavation and earth work (filling in, ramming in layers, watering etc as directed) in any type of soil for earth pit (pit size 1.20x 1.20x3.0mtr).(b) Perforated GI tubing (ISI marked) light grade 50mm bore 7.0 mtr long for strip protection and watering.(c) Common salt charcoal dust in alternative layers of 15cm, up to 60cm above the top of copper plate all as directed (Salt - 300Kg, Charcoal dust - 500 Kg).(d) Earth chamber of internal size 600mmx600mmx600mm, built in PCC (1:3:6) type C2 bed 15cm thick at bottom, brick work in CM 1:6 upto 45cm over PCC bed and PCC (1:3:6) type C1 coping 15cm above, embedded with MS angle 50mmx50mmx3mm frame work duly painted with anti corrosive bituminous paint, with and including RCC slab 50mm thick in cement concrete (1:2:4) type B1, reinforced with XPM (weight not less than 4Kg per Sqm) having lifting arrangement duly painted in green and making earth pit as directed.(e) On testing, after completion, if the earth resistance < 2 Ohms is not obtained, earthing will be regenerated at no extra cost till the desired earth resistance is obtained.(f) GI tubing, bib tap etc for provisioning of continuous water supply at earthing pit will be measured and paid seperately under respective schedule of the contract. |
| 70 | M & L for chemical earthing complete with copper plate earth electrode 90cmx60cmx5 mm thick buried directly in ground (earth pit not less than 4.00 mtr below ground level with top edge of plate not less than 3.25 mtr below ground level) brazed with copper strip 50x6 mm size 7.5 mtr long and connected to copper strip of any size by means of copper bolts, nuts, check nuts and washers complete all as specified and directed. Note:- The rated quoted is deemed to the inclusive of the followings:-(a) The excavation and earth work (filling in, ramming in layers, watering etc as directed) in any type of soil for earth pit (pit size 1.20x 1.20x4.0mtr).(b) Perforated GI tubing (ISI marked) light grade 80mm bore 7.0 mtr long for strip protection and watering.(c) Common salt charcoal dust in alternative layers of 15cm, up to 90cm above the top of copper plate and one layers of 15cm Magnesium sulphate (MgSo4) all as directed (Salt - 500Kg, Charcoal dust - 1000 Kg & MgSo4 - 150 Kg).(d) Earth chamber of internal size 600mmx600mmx600mm, built in PCC (1:3:6) type C2 bed 15cm thick at bottom, brick work in CM 1:6 upto 45cm over PCC bed and PCC (1:3:6) type C1 coping 15cm above, embedded with MS angle 50mmx50mmx3mm frame work duly painted with anti corrosive bituminous paint, with and including RCC slab 50mm thick in cement concrete (1:2:4) type B1, reinforced with XPM (weight not less than 4Kg per Sqm) having lifting arrangement duly painted in green and making earth pit as directed.(e) On testing, after completion, if the earth resistance <2 ohms is not obtained, earthing will be regenerated at no extra cost till the desired earth resistance is obtained.(f) GI tubing, bib tap etc for provisioning of continuous water supply at earthing pit will be measured and paid seperately under respective schedule of the contract. |
| 71 | Supply & Fixing of Nut, M6 (Stainless steel) as per matching/ existing complete all as specified and directed by Engr-in-Charge. |
| 72 | Supply & Fixing of Bolt, M6 x 25, Hex Head (Stainless steel) as per matching/ existing complete all as specified and directed by Engr-in-Charge. |
| 73 | Supply & Fixing washers, M6 x 25, Hex Head (Stainless steel) as per matching/ existing complete all as specified and directed by Engr-in-Charge. |
| 74 | M & L in replacement of testing point box of size 100 x 100 x 50 mm depth as per sample complete all as specified. |
| 75 | M & L in replacement of earhing pit GI funnel as per sample complete all as specified. |
| 76 | M & L in replacement of 15 mm PVC bib tap as per sample complete all as specified. |
| 77 | Taking down and up any type of copper/aluminium strip of any size and type on wall or building roof for execution of misc works on roof and the same has been to be fix after completion of civil work. (Insulators,nut bolts with washers and any type of strip will be measured and paid separately against the item in the schedule) |
| 78 | M&L for painting to test point box of size 100 x 100 x 50 mm depth all as specified and directed |
| 79 | Supply, Installation, Testing and Commissioning in replacement of Waterless Maintenance Free Grounding System Based on Conductive Earthing Electrode and having following specification :- Dimensions L*D (MM): 3000*80 with 16mm solid conductor (Pure Copper) Conduction: Non Ionic Movement of Ions, Multi Point Dissipation Contacts, Environment: Ph Neutral Internal Material, Relative Density: 890-990 kg/m3, 3000 times more effective than Bentonite Electrolytic Corrosion Resistance: >86% reduction in corrosion Short Circuit Current (Tested): Peak: 40 KA RMS: 22 Kilo Amps for 1 Sec Mechanical Strength: >Grade 25 Concrete High Fault Current Test Withstand: 1686 V for 500 ms Standards: IEEE 80:2000 & BS 7430 Warranty: 5 Years On testing, after completion, if the earth resistance < 1 ohms is not obtained, earthing will be regenerated at no extra cost till the desired earth resistance is obtained. |
| 80 | Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc. and getting out Hard/dense soil complete. |
| 81 | Returning, filling in including spreading, levelling, watering and well ramming in layer not exceeding 25cm complete. |
| 82 | Removing excavated materials not exceeding 50 mtrs away and depositing where directed at a level not exceeding 1.5 mtr above the starting point. |
| 83 | M&L for common burnt clay bricks Designasion sub class 'B' for stacking for bricks around the earth pits including civil work complete all as specified and directed. |
| 84 | M&L for laying of coarse aggregate(broken stone boulders) 40mm size in continuous bed of thickness 20mm and soft ramming to consolidate the aggregate to form a compact layer of aggregate around Earth pits and carefully demercating the surrounding in length by breadth, to facilitate percolation of rainwater rendering the surface where aggregate are laid, safe for operation during rainly season by naturally facilitating a insulating surface all as specified. |
| 85 | Comprehensive monthly maintence of Fire Hydrant system installed 16 BRD AF Stn Palam. The detail scope of work consists of the following :-(i) Cleaning inspecting, checking and repairing if required all the equipments of fire hydrant system.(ii) Operational test of all the equipment of Fire Hydrant system in presence of rep of users and Engr-in-charge.(iii) The contractor shall submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge on monthly basis.(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.(v) Emergency visit shall be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi)Testing of entire piping network and rectification of leakage as requirement at site complete to the satisfaction of engr-in -charge and all as directed.(viii) Material required for replacement shall be measured and paid separately under respective items of this schedule as 'Supply and fixing' and labour component for the same is not included in comprehensive maintanance contractor shall quote the rate accordingly. (viiI) Checking of fire hyrant system and rectification of fault all as specified and directed by Engineer-In - Charge |
| 86 | Comprehensive monthly maintence of auto fire sprinkler system installed in 16 BRD AF Stn Palam. The detail scope of work consists of the following :-(i) Cleaning inspecting, checking and repairing if required all the equipments of fire sprinkler system.(ii) Operational test of all the equipment of fire sprinkler system in presence of rep of users and Engr-in-charge.(iii) The contractor shall submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge on monthly basis.(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.(v) Emergency visit shall be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi)Testing of entire piping network and rectification of leakage as requirement at site complete to the satisfaction of engr-in -charge and all as directed.(vii) Material required for replacement shall be measured and paid separately under respective items of this schedule as 'Supply and fixing' and labour component for the same is not included in comprehensive maintanance contractor shall quote the rate accordingly. (viii) Checking of sprinkler system and rectification of fault and live testing by generating heat and bursting sprinkler at particular area complete all as specified and directed by Engineer-In - Charge |
| 87 | Supply and fix in repair Earth continuity conductor or main earthing lead fixed to wal on batten or recess or chasses or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation of 25x4 mm galvanised iron strip. |
| 88 | Supply and fixing in replacement of sprinkler Quick / Early response type as per IS 15105 / TAC guide lines, 79 degree temperature rating pendant type complete all as specified and directed. |
| 89 | Supply and fixing in replacement of Pressure switch of existing make and capacity complete all as specified & directed |
| 90 | Supply and fixing in replacement of stainless steel Single headed hydrant valve 63 mm dia, ISI marked of existing make complete all as specified and as directed. |
| 91 | Supply and fixing in replacement of RRL hose pipe ISI marked 15 mtr length, type A complete all as specified and as directed. |
| 92 | Supply and fixing in replacement of stainless steel Male Coupling of complete all as specified and as directed. |
| 93 | Supply and fixing in replacement of stainless steel Female Coupling complete all as specified and as directed.. |
| 94 | Supply and fixing in replacement of Short stainless steel pipe of existing all as specified and as directed. |
| 95 | Supply and fixing in replacement of brass Nozzle for 20 mm pipe of existing make complete all as specified and as directed. |
| 96 | S&F for external hose box (in repair) made of 18 gauge MS Sheet 800X 600X250mm with double door with 4 mm thick glass and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard complete all as specified and directed. |
| 97 | Supply and fixing in replacement of MS ERW pipe C class of 150 mm dia including jointing and testing as per manufacturer's instructions complete all as specified and as directed. |
| 98 | Supply and fixing in replacement of MS ERW pipe C class of 100 mm dia including jointing and testing as per manufacturer's instructions complete all as specified and as directed. |
| 99 | Supply and fixing in replacement of MS ERW pipe C class of 80 mm dia including jointing and testing as per manufacturer's instructions complete all as specified and as directed. |
| 100 | Supply and fixing in replacement of GI pipe C class of 25 mm dia including ISI marked GI fittings and testing complete all as specified and as directed. |
| 101 | Supply and fixing in replacement of GI pipe of 20 mm dia including ISI marked GI fittings and testing complete all as specified and as directed. |
| 102 | Supply and fixing in replacement ISI Marked, 100mm size cast iron non butterfly valve, both ends flanged jointed and tested including taking down old valve complete all as specified and directed. |
| 103 | M&L for 1.5 sqmm 3 core PVC insulated unsheathed, FRLS multistranded copper conductor cable, 1100V grade complete al as specified and directed. |
| 104 | M&L for removing of lubricating oil from chamber and oil filter chamber of the diesel driven pump 44 KW/55 KVA and cleaning of oil chamber & filter chamber thoroughly to remove all types of deposits and supply & filling of new lubricant oil SAE 15 W/40 W-20 liter at required level complete all as specified and as directed. |
| 105 | Supply and fixing in replacement of Element lub oil filter of 44 KW/55 KVA DG complete all as specified and as directed. |
| 106 | Supply and fixing in replacement of Fuel filter of 44 KW/55 KVA DGcomplete all as specified and as directed. |
| 107 | Supply and fixing in replacement of Coolant assy of 44 KW/55 KVA DG complete all as specified and as directed. |
| 108 | Supply and fixing in replacement of Element Air cleaner of 44 KW/55 KVA DG complete all as specified and as directed. |
| 109 | M & L for repair and reconditioning of battery charger alternator kirloskar/ cummins make including taking out the defective alternator from 44KW/55 KVA capacity DG set , complete dismantling and repair and replacing the carbon brushes, rectifier diode set, bearing and bush, regulator control, refixing the same in the DG set and connecting with the circuit including all required items, starting and testing all as specified and directed by Engineer-in-charge |
| 110 | Supply and curring coolant for radiator suitable for DG set 44KW/55 KVA including drained out old one coolent. all as per manufacturers recommendations |
| 111 | M & L for supply , fixing in replacment of fan belt set of 2 nos in 44KW/55 KVA DG set all as specified and directed by Engineer-in-charge |
| 112 | S & Fixing in repairs High water temperature trip safety control make Kirloskar in 55 KVA DG set and connecting with DG set system of 55 KVA all as specifiied and directed by Engineer-in-charge |
| 113 | S & Fixing in repairs Low lub oil pressure safety control make Kirloskar in 55 KVA DG set and connecting with DG set system of 55 KVA all as directed by Engineer-in-Charge |
| 114 | M & L for replacement of battery brass terminal with nuts and bolts for 55 KVA DG set complete all as specified and directed. |
| 115 | M & L for supply, fixing and testing DG set stop solenoid switch in 55 KVA by taking out the defective switch from the DG set, replacing by new and aligning, connecting with circuit, starting and testing all specified and directed by Engineer-in-charge |
| 116 | M & L for supply, fixing in repair coil electrical in STC control valve under in 55 KVA DG set as specified and directed by Engineer-in-charge |
| 117 | M & L for supply , fixing in repairs to Lub oil pressure transducer in 55 KVA DG set and connecting with DG set system all as directed by Engineer-in-Charge |
| 118 | M & L for supply, fixing in repair shutdown valve under in 55 KVA DG set as specified and directed by Engineer-in-charge |
| 119 | M & L for repair and reconditioning the starting motor 12 V DC system including taking out the defective starter from 44 KW/55 KVA capacity DG set , complete dismantling and repair and replacing the carbon brushes with holder, solenoid switch assly, bushes, commutator unit, starting coil, etc refixing the same in the DG set and connecting with the circuit including all required items, starting and testing all as specified and directed by Engineer-in-charge |
| 120 | M & L for supply and fixing of AMF Logic conttroller (Microprocessor based type) by taking out the defective unit from 44KW/55 KVA capacity DG set complete checking the panel and its connection circuit in the panel board, providing prper interlink connection with DG set including all required items, starting and testing all as specified and directed by Engineer-in-charge |
| 121 | M & L for supply, installation and commissioning of AVR in 44KW/55 KVA DG set by taking out the defective AVR from DG set alternator from its control circuit, fixing the new AVR and connecting in the circuit, thorough checking and testing the DG set on load all as directed by Engineer-in-Charge. |
| 122 | S & Fixing in repair and rewinding the excitor stator assembly of 44KW/55 KVA capacity DG Set by takingout complete burnt coils, cleaning and rewinding the same by supper enamel copper wire SWG 18, insulalting the coils with nomex paper, milinex sheet, heating and varnshing by varnish materials and applying one coat of bectol anti rust protection, fixing back in to the alternator, connecting teh cables, starting and testing all as specified and directed by Engineer-in-charge |
| 123 | M & L for supply, installation and connection including taking out U/S battery charger 230 V AC input and output 24 V / 12 V 10 amps charging rating IMPS type with fully auto control in charging and floating with boost system all as specified and directed by Engineer - in charge |
| 124 | Material and labour for replacement of unserviceable battery 12 V, 150 AH with maintenance free battery 12 Volt initially charged. |
| 125 | Taking out induction motor from the system carrired out motor to work shop , Rewinding of Induction AC Motor, 440 volts , 50Hz, 03 phase, brusless of Rating 60 HP, with super enameled copper wire of superior quality as per existing gauge including vanishing, insulating material complete all as directed and greasing, oiling etc and including reassembling fixing in position making connection testing, commissioning & transporting complete. Note :- rewinding shall be done with gurantee during the contract period. Any defects after rewinding shall be rectified by the contractor at his own expanses.with copper enameled wire, refixing and testing the motor complete all as specified and as directed by Engineer-in-Charge. |
| 126 | M&L in replacement of 25 mm Gun Metal gate Valves complete all as specified and as directed by Engineer-in-Charge. |
| 127 | Supply and fixing in replacement of Heavy duty threaded / welded GI Flange with rubber gasket 80 mm including nuts and bolts complete all as specified and as directed. |
| 128 | Supply and fixing in replacement ISI Marked,150mm cast iron Foot valve, with flanged jointed and tested including taking down old valve complete all as specified and directed. |
| 129 | M&L for Cleaning of 50000 Gallon overhead tank with 6 Stage Cleaning Method STAGE 1: Dewatering the water with Mechanical electric Pump STAGE 2 : Clean the sluge from wall and floor of overhead tank STAGE 3: High pressure cleaning with special pump STAGE 4: Suction with Industrial Vaccum Cleaner STAGE 5 : Anti bactrial Spray on wall and Floor of overhead tank ( Test Certificate Of Chemical Must be Provided That chemical is safe for Humans) STAGE 6: UV Radiation for disinfect from the bactrial envoirment (Note: This work done by Specialist Agenceis of water treatment) complete all as specified and as directed. |
| 130 | M&L for Cleaning of 25000 Gallon semi UG Sump with 6 Stage Cleaning Method STAGE 1: Dewatering the water with Mechanical electric Pump STAGE 2 : Clean the sluge from wall and floor of sump STAGE 3: High pressure cleaning with special pump STAGE 4: Suction with Industrial Vaccum Cleaner STAGE 5 : Anti bactrial Spray on wall and Floor of Sump( Test Certificate Of Chemical Must be Provided That chemical is safe for Humans) STAGE 6: UV Radiation for disinfect from the bactrial envoirment (Note: This work done by Specialist Agenceis of water treatment) complete all as specified and as directed. |
| 131 | M&L for Cleaning of 5000 Ltr PVC Tank with 6 Stage Cleaning Method STAGE 1: Dewatering the water with Mechanical electric Pump STAGE 2 : Clean the sluge from wall and floor of PVC Tank STAGE 3: High pressure cleaning with special pump STAGE 4: Suction with Industrial Vaccum Cleaner STAGE 5 : Anti bactrial Spray on wall and Floor of PVC Tank (Test Certificate Of Chemical Must be Provided That chemical is safe for Humans) STAGE 6: UV Radiation for disinfect from the bactrial envoirment (Note: This work done by Specialist Agenceis of water treatment) complete all as specified and as directed. |
| 132 | Material and labour for painting of EOT crans installed above the height of 5.0m from working level, thoroughly cleaned of all dirt, grease, scale and rust by shot blasting or chemical cleaning methods, removing old paint from EOT cranes and attachments parts such as double girders, motors, crane rail, Gearbox cabinet, LT panel board and all moving parts. A single coat of primer shall be given to all parts exposed to the weathering effects and two coats of paint as approved by GE for indoor/outdoor cranes shall be given on all primer painted surface. The bright exposed parts of the crane shall be given one coat of rust inhibitor. Interior of all gear boxes shall be painted with one coat of oil resisting paint. Writing the Technical details of respective crane as per existing data available on each cranes with paint as approved by GE, complete all as directed by Engineer-in-Charge. The capacity of Crans are as under :- |
| 133 | EOT Crane 2.0 Ton |
| 134 | EOT Crane 3.0 Ton |
| 135 | EOT Crane 5.0 Ton |
| 136 | Material and labour for painting of EOT crans installed above the height of 5.0m from working level, thoroughly cleaned of all dirt, grease, scale and rust by shot blasting or chemical cleaning methods, removing old paint from EOT cranes and attachments parts such as double girders, motors, crane rail, Gearbox cabinet, LT panel board and all moving parts. A single coat of primer shall be given to all parts exposed to the weathering effects and two coats of paint as approved by GE for indoor/outdoor cranes shall be given on all primer painted surface. The bright exposed parts of the crane shall be given one coat of rust inhibitor. Interior of all gear boxes shall be painted with one coat of oil resisting paint. Writing the Technical details of respective crane as per existing data available on each cranes with paint as approved by GE, complete all as directed by Engineer-in-Charge. The capacity of Crans are as under :- |
| 137 | Capacity 2 TON |
| 138 | Capacity 3 TON |
| 139 | Capacity 5 TON |
| 140 | Material and Labour for disconnecting the electric motor of capacity 0.5 to8 HP from the cranes transporting to workshop, taking out old winding and rewinding the motorwith super enameled copper wire of superior quality as per existing gauge including vanishing, insulating material complete all as directed and greasing, oiling etc and including reassembling fixing in position making connection testing, commissioning & transporting complete. |
| 141 | Testing of EOT/HOT cranes with full load and 25% over load all as specified in IS No 301 of 1977 and 3177 of 1977 and writing the date of load testing all as directed by the Engineer-in-Charge for the following capacity :-(Note :- Contractor will be responsible for provision of load materials in P&E Lab) |
| 142 | Capacity 2 TON |
| 143 | Capacity 3 TON |
| 144 | Capacity 5 TON |
| 145 | PVC insulated unsheathed , FRLS multistranded copper conductor cable, 1100V grade as per IS 1554 (Part-1) of size 4 Sq mm, 10 Core Copper Conductor. |
| 146 | PVC insulated unsheathed , FRLS multistranded copper conductor cable, 1100V grade as per IS 1554 (Part-1) of size 2.5 Sq mm, 10 Core Copper Conductor. |
| 147 | Variable Speed driver altivar 12 for synchronous motor of capacity 2.2KW/3HP with input voltage 380-500V-3 phase and output voltage-380-500volts-03 phase . |
| 148 | SPARES PARTSSupply only Spares/Components after approval and as directed by Engineer-in-Charge for the following capacity of Cranes/Hoists :-Crane Capacity 2 TON |
| 149 | Carbon Brushes |
| 150 | Over Load Relay 5 to 10 Amps |
| 151 | Brake Lining. |
| 152 | Steel Wire Rope 10mm dia. |
| 153 | Magnetic Coil. |
| 154 | Clutch Plate . |
| 155 | Thrust Bearing. |
| 156 | Gear Wheel. |
| 157 | Limit Switch . |
| 158 | Roller Bearing. |
| 159 | Push Button. |
| 160 | Oil Seal |
| 161 | Crane Capacity 3 TON |
| 162 | Oil Seal. |
| 163 | Gasket. |
| 164 | Steel Wire Rope. |
| 165 | Pedant Push Button . |
| 166 | Carbon Brushes. |
| 167 | Over Load Relay 13 to 21 Amps |
| 168 | Clutch Plate. |
| 169 | Wheel Bearing |
| 170 | Trolley Wheel. |
| 171 | Brake Pad. |
| 172 | Crane Capacity 5 TON |
| 173 | Oil Seal. |
| 174 | Gasket. |
| 175 | Brake Pad. |
| 176 | Brake for LT/CT Coil. |
| 177 | Pedant Push Button . |
| 178 | Clutch plate. |
| 179 | Over Load Relay 13 to 21 Amps. |
| 180 | Brake lining. |
| 181 | Limit Switch |
| 182 | Key Switch |
| 183 | Gear Box Bearing. |
| 184 | Gear Wheel. |
| 185 | Magnetic Coil |
| 186 | S& F FRLS PVC insulated unsheathed multi stranded copper conductor cable of 1100 Volts grade of size 2.5 Sq mm, 4 Core Copper Conductor. |
| 187 | S&F FRLS PVC insulated unsheathed multi stranded copper conductor cable of 1100 Volts grade size 2.5 Sq mm, 3 Core Copper Conductor. |
| 188 | S&F Kit kat fuse assembly complete of 32 amps capacity |
| 189 | S&F TP Contactor 40 Amps, 110 Volts coil voltage ML-3. |
| 190 | S&F TP Contactor 32 Amps, 110 Volts coil voltage ML-2. |
| 191 | S&F PVC Insulated sheathed multistrand Copper conductor cable, 1100 volt grade of size 2.5 Sqmm, 12 core, |
| 192 | S&F No Volt Coil 110 Volts AC suitable for 40 Amps Contactor. |
| 193 | S&F Transformer 440/110 Volts, 30VA. |
| 194 | S&F PVC Insulated sheathed multistrand Copper conductor cable, 1100 volt grade of size 4 Sqmm, 12 core. |
| 195 | M&L for MCCB TPN 63 Amps mechanical adjustable type breaking capacity 16 KA including fixing/connecting arrangement all as directed by Engineer-in-Charge. |
| 196 | All as per Srl item No 150 here-in-before but capacity 32 Amps mechanical adjustable type, breaking capacity 16 KA. |
| 197 | M&L in replacement of Steel rope multistranded, suitable for lifting of load upto 5 ton size of stee reope not less than 12 mm thickness complete all as specified |
| 198 | M&L in replacement of Steel rope multistranded, suitable for lifting of load upto 7 ton size of stee reope not less than 15 mm thickness complete all as specified |
| 199 | Supply and fixing LED street light fitting of capacity 60 watts ,230 volts AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optic and equipped with IP 66 protection, with impact and corrsion resistant complete with drivers and as per national lighting code by using each LED>1W and <3 W, LED Chip efficiency>=135 Lumens/Watt, CRI>70, CCT 5000K to 6500 K with LED Lifespan at 70% of light output>50000 hours. The driver should be 140 V to 270 V universal driver with built in surge protection >5 KV, 50 Hz, +/-3%, pf>0.95, THD<10% with system efficiency must be >85 lumens/Watt and power efficiency >=90% and overall, Driver and luminaire shall comply LM-79/IS: 16106 and all accessories and making all necessary connection including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge. |
| 200 | Supply and fixing LED street light fitting of capacity 90 watts ,230 volts AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optic and equipped with IP 66 protection, with impact and corrsion resistant complete with drivers and as per national lighting code by using each LED>1W and <3 W, LED Chip efficiency>=135 Lumens/Watt, CRI>70, CCT 5000K to 6500 K with LED Lifespan at 70% of light output>50000 hours. The driver should be 140 V to 270 V universal driver with built in surge protection >5 KV, 50 Hz, +/-3%, pf>0.95, THD<10% with system efficiency must be >85 lumens/Watt and power efficiency >=90% and overall, Driver and luminaire shall comply LM-79/IS: 16106 and all accessories and making all necessary connection including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge.. |
| 201 | Supply and fixing 150 watt energy , saving environmental friendly, long life exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural features or retail spaces, and as per national lighting code by using each LED>1W and <3 W, LED Chip efficiency>=135 Lumens/Watt, CRI>70, CCT 5000K to 6500 K with LED Lifespan at 70% of light output>50000 hours. The driver should be 140 V to 270 V universal driver with built in surge protection >5 KV, 50 Hz, +/-3%, pf>0.95, THD<10% with system efficiency must be >85 lumens/Watt and power efficiency >=90% and overall, Driver and luminaire shall comply LM-79/IS: 16106 including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge.. |
| 202 | Supply and fix in repair thermal over Load realy MN2 type MN suitable for MNX contactor for 3 phase 415 volts AC supply of range 24-40 Amps capacity. including necessary electrical connection complete all as specified and directed. |
| 203 | Supply and fix in repair thermal over Load realy MN5 type MN suitable for MNX contactor for 3 phase 415 volts AC supply of range 66-110 Amps capacity. including necessary electrical connection complete all as specified and directed. |
| 204 | Supply and fix in repair front mountin Add-on-aux contact block MNX/MCX front Add-on aux contact bloxk MNX-0-80/MCX01-23, 1 No+1NC suitable for 240 volts AC supply including necessary electrical connection complete all as specified and directed. |
| 205 | Suppy and fix in repair Electronic Timer suitable for 240/360/415 V, 50HZ, for 3-30 Sec time setting including necessary connection complete all as specified and directed. |
| 206 | Supply and fix in repair contactor MNX40 suitable for 3 phase, 415 volts AC supply of capacity 40A of LT Legrand ncluding necessary electrical connection complete all as specified and directed |
| 207 | Supply and fix in repair contactor MNX80 suitable for 3 phase, 415 volts AC supply of capacity 80A of LT , Legrand ncluding necessary electrical connection complete all as specified and directed |
| 208 | Supply and fixing LED post top lantern LED type of capacity 20 watts , 230 volt AC outdoor tye with decorative post top for 360 degree indirect light IP65 protection with impact and corrosion resistant comlete with drivers and lamp and as per national lighting code by using each LED>1W and <3 W, LED Chip efficiency>=135 Lumens/Watt, CRI>70, CCT 5000K to 6500 K with LED Lifespan at 70% of light output>50000 hours. The driver should be 140 V to 270 V universal driver with built in surge protection >5 KV, 50 Hz, +/-3%, pf>0.95, THD<10% with system efficiency must be >85 lumens/Watt and power efficiency >=90% and overall, Driver and luminaire shall comply LM-79/IS: 16106 and all accessories and making all necessary connection including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge. |
| 209 | S&F LED bollard of 9 watt with soft 360° light, IP 65 protection, Resistant to corrosion for better optics and uniform distribution including making foundation (As per manufacturer specification) for bollard light along with bolt integrated with PCC and nut & washer to tightened bollard light and making provision for cable entry and exit through pcc block, complete all as specified and directed.Note: Model/Make/Type of bollard light will be finalised by Engineer-in-charge as per user requirement. |
| 210 | Note :- The amount of Rs 60230.00 against Schedule of Credit on Srl Page 159 to 162 shall be deducted from the total amount quoted against Sch 'A' Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail