| 1 | Taking down carefully aluminium / copper point wiring any type for one light , fan, socket power point controlled by one switch complete including fitting / fixtures such as switches, ceiling roses, holder, socket etc; and making good disturbed surfaces of walls, ceilings etc |
| 2 | Material and labour for point wiring for one light/fan/exhaust fan controlled by one way switch with 1.5 Sqmm PVC insulated unsheathed two single core multi-stranded copper conductor (FRLSH) cable, 1100 Volts grade drawn through and including rigid non metallic PVC concealed conduit (medium grade) of suitable dia along with 1.5 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire, connected to earth dolly and in including modular pressed steel sunken boxes of required size with modular cover plate with frame for mounting modular switches, sockets, fan regulators etc including testing on completion complete including cutting chases for concealed conduit pinning in making good to disturbed surface and pointing in using cement mortar 1:3 all as specified and as directed for the following. |
| 3 | One light/fan point controled by one 5/6 Amp modular type switch |
| 4 | One 3 pin socket outlet 5 Amps on same board. |
| 5 | One 3 pin socket outlet 5 Amps on indpendent board |
| 6 | All as per item No 2 here in before but point wiring with 2.5 sqmm FRLSH multi stranded copper conductor cable for main circuit and 2.5 sqmm cable as earth continuity conductor for one 15 Amp socket out let controlled by one 15/16 Amp switch on independat board, complete all as specified and directed. |
| 7 | Material and labour for point wiring for one light/fan/exhaust fan controlled by one way switch with 1.5 Sqmm PVC insulated unsheathed two single core multi-stranded copper conductor (FRLSH) cable, 1100 Volts grade drawn through and including PVC casing/conduit of suitable size as per site requirement fixed to wall, ceiling including PVC closed recessed boxes ISI marked laminated sheet top cover plate complete for mounting of switches, sockets etc incl 1.50 sqmm (nominal area) PVC insulated and sheathed multistranded copper conductor cable FRLSH 1100 volts grade single core earth continuity conductor connected to common earth dolly all as directed and specified for the followings. |
| 8 | One light /fan point controled by one 5/6 Amp piano type switch |
| 9 | One 3 pin socket outlet 5 Amps on same board. |
| 10 | One 3 pin socket outlet 5 Amps on indpendent board |
| 11 | All as per item No 4 here in before but point wiring with 2.5 sqmm FRLSH multi stranded copper conductor cable for main circuit and 2.5 sqmm cable as earth continuity conductor for one 15 Amp socket out let controlled by one 15/16 Amp switch on independat board, complete all as specified and directed. |
| 12 | S&F in replacement of switch piano (flush button type) single pole, one way, 5 Amps complete all as specified and directed. |
| 13 | S&F in replacement of switch socket combination 2 in one, 3 pin , 5/6 Amps, 240 Volts flush type,complete all as specified and directed. |
| 14 | S&F in replacement of switch socket combination 2 in one , 3 pin, 5/6/16 Amps flush type complete all as specified and directed. |
| 15 | S&F in replacement of socket out let 2 in 1, 3 pin 5 Amps flush type complete all as specified and directed. |
| 16 | S&F in replacement of modular switch single pole one way 6 Amps 1 module complete all as specified and directed. |
| 17 | S&F in replacement of modular socket 6 A-2/3 pin combined 2 module complete all as specified and directed. |
| 18 | S&F in replacement of modular switch single pole one way 16 Amps 1 module complete all as specified and directed. |
| 19 | S&F in replacement of modular socket 6 A/16 amp -2/3 pin combined 2 module complete all as specified and directed. |
| 20 | S&F in replacement of ceiling rose polycarbonate type three terminals complete all as specified and directed. |
| 21 | S&F in replacement of step type electronic fan regulator 120 watt single pole 240 Volts complete all as specified |
| 22 | S&F in replacement of modular fan regulator, electronic step type heavy duty modular 2 module 230 volts, 120 watt complete all as specified and as directed. |
| 23 | Supply and fix in replacement Lamp holder PVC case body of Bakelite with back plate suitable for batten fittings,all as specified. |
| 24 | S&F in replacement LED lamp,6500K,900lm in white colour of 9/10 Wattbase cap B-22 with poly carbonate difusser and aluminium heat sink ,complete all as specified & directed. |
| 25 | S&F in replecement of Ultra slim LED light to new 36W, 6500 K LED (CDL/WW type as per site requirement) recess mounted bakelite panel of size 2 x 2 feet luminaire suitable for surface/grid ceiling for low ceiling applications complete with tube, driver and connecting cable including making electric connection to ceiling rose or connector including taking down old unserviceable luminaire, complete all as specified and as directed. |
| 26 | S&F in replacment of LED tubelight fitting 1x20Watt batten type fitting 4 feet long aluminium extruded housing IP-20 rated rated voltage 230 volts(operating range 140 volt to 270 volts) , 50Hz system wattage 20 Watt +/-10% ,system current not less than 102 mA ,power factor more than 0.95, system lumen efficacy 100 lm /watt ,CCT 6500K complete all accessories prewired and connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor of size 0.75 sqmm 3 core all as specidfierd and directed. |
| 27 | All as per item No 20 here in before but LED tubelight fitting 1x10Watt batten type fitting 2 feet long, complete all as specified and directed. |
| 28 | S & F in replacement of LED light fitting 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size |
| 29 | S&F in replecement of plug top, AC 230 Volts, 5/6 Amps complete all as specified and directed. |
| 30 | S&F in replecement of plug top, AC 230 Volts, 16 Amps complete all as specified and directed. |
| 31 | S&F in replecement of PVC conduit medium grade with fittings, ISI marked, 25 mm size complete all as specified and directed. |
| 32 | S&F in replecement of PVC casing & capping with fittings, ISI marked, 25X16 mm size complete all as specified and directed. |
| 33 | S&F in replecement of PVC switch boards, closed recessed suitable for surfaces, sizes 4 X 4 (Inches) complete all as specified and as directed. |
| 34 | S&F in replecement of PVC switch boards, closed recessed suitable for surfaces, sizes 4 X 7 (Inches) complete all as specified and as directed. |
| 35 | S&F in replecement of PVC switch boards, closed recessed suitable for surfaces, sizes 8 X 6 (Inches) complete all as specified and as directed. |
| 36 | S&F in replecement of sub main wiring with two run of single core PVC insulated FRLSH stranded copper conductor cable of size 6 Sq mm and one run of 6 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductor drawn in and including PVC casing and caping/PVC rigid conduit 20mm dia with necessary accessories complete all as directed. Note : 2 Runs of 6 sqmm cable and one run of 6.00 sqmm earth wire with PVC casing and caping shall be measured as one unit. |
| 37 | S&F in replecement of sub main wiring with two run of single core PVC insulated FRLSH stranded copper conductor cable of size 4 Sq mm and one run of 4 Sq mm PVC insulated FRLSH copper conductor cable as earth continuity conductor drawn in and including PVC casing and caping/PVC rigid conduit 20mm dia with necessary accessories complete all as directed. Note : 2 Runs of 4 sqmm cable and one run of 4.00 sqmm earth wire with PVC rigid conduit shall be measured as one unit. |
| 38 | S&F in replecement of 1100 volts grade heavy duty cable PVC insulated aliminium conductor served with inner sheathing of PVC sheathed with stranded conductor 10 sqmm twin core cable flat or circular, complete all as specified and directed. |
| 39 | S&F in replecement of 1.5 Sqmm dia, flexible single core PVC insulated FRLSH multistranded copper conductor wire, 1100 volts rating conforming to IS:694, complete all as specified & directed. |
| 40 | S&F in replecement of Sheet metal enclosure IP-43 double door for DBs(where MCBs are reqd) SPN 240 V, for 4 ways, complete all as specified. |
| 41 | All as per item No. 35 above but SPN 8 ways 240 volts complete all as specified and directed. |
| 42 | All as per item No.35 above but SPN 12 ways 240 volts complete all as specified and directed. |
| 43 | S&F in replecement of MCB SP 6 to 32 Amp, 240 volts complete all as specified. |
| 44 | S&F in replecement of MCB SPN 32-40 Amp, 240 volts 50Hz AC supply, complete all specified. |
| 45 | S&F in replecement of MCCB 63/100 Amp,4 pole, 16KA 415 volts 50Hz, AC supply, complete all specified. |
| 46 | Supply and fixing in replacement of MCB distribution board double door vertical type made out of CRCA mild steel sheet surface with insulated material like polyester or with epoxy powder coating, TPN 4 way. 415 volts with bus bar rating 200 Amps, dust and vermin proof and IP 43 - IK 09 protection suitable for incorporation of MCCB 63/100/125 Amps 4 pole, including grouting in the wall, cutting & chasing/surface mounting etc. complete all as specified. |
| 47 | Supply and fixing in replacement of LED lights 18 watt, 6500lmn recess mounted square type size 185X185mm including connection with 1.5 sqmm PVC insulated copper wire complete. |
| 48 | Supply and fixing in replacement of LED lights 18 watt surface mounted Round type size 205mm cut out dia including connection with 1.5 sqmm PVC insulated copper wire complete. |
| 49 | M&L in replacement of earthing complete with galvanized steel earth plate electrode of size 60cm x 60 cmX 6.0 mm buried in the ground to a depth not less than 2.25 mtr below ground level connected with GI wire 4 mm by means of GI nut, bolts, washers and check nut and complete as shown in electric plate No 03 of SSR Part-I including 20 mm dia GI pipe medium grade for watering, funnel and RCC cover including earth work for excavation and removal of surplus soil and making earth test point complete all as specified and directed. |
| 50 | Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire |
| 51 | M & L for Servicing of the window AC 1.5/2 ton capacity of any make, including oiling/greasing the blower motor, cleaning the evaporator condenser coils externally to remove the dust, replacement of defective thimbles etc and re-fixing the air conditioner at its original position by the experienced refrigeration mechanic complete all as specified and as directed by Engineer-in-Charge. Note:- (i) Any u/s items need to be replaced/gas charging etc shall be replaced & paid seperately under respective items. (ii) The cost of dismantling, taking out window AC 1.5/2.0 ton from window and shifting to location where directed for proper washing and servicing and refixing the same shall be deemed to be included in item rate quoted. |
| 52 | All as per ser item No. 1.00 here-in-before but for split type AC/Inverter type AC 1.5/2.0/3.0/4.1 Ton |
| 53 | M&L in replacement Fan Motor of AC (Window/ Split Type) 1.5 TR Capacity as per site requirement to suit existing AC including taking out the unservice-able Fan Motor from the AC, complete all as specified and as directed. |
| 54 | All as per Item No. 3 here–in–before, but AC (Window/Split Type). 2.0 TR Capacity |
| 55 | M&L Rewinding Fan Motor of AC 1.5/2.00 TR Capacity, (Window/Split Type) of any Make with Super Enameled Copper Wire of appropriate Gauge and Quantity including taking out burnt Winding, complete all as specified and as directed. |
| 56 | M&L in replacement Air circular Blower Fan Motor of AC (Split Type), 1.5 TR/2.0/3.00TR Capacity including taking out unser-viceable Air circular Blower Fan Motor complete all as specified and as directed. |
| 57 | M&L in replacement Air Filter suitable of AC (Window type) 1.5 TR/2.0 TR Capacity including taking out unserviceable Air Filter from AC complete all as specified and as directed. |
| 58 | M&L in replacement Air Filter suitable of AC (Split type) 1.5 TR/2.0 TR Capacity including taking out unserviceable Air Filter from AC complete all as specified and as directed. |
| 59 | M&L in replacement Capacitor Running 36 mfd – 45 mfd suitable for new/star rated for AC (Window/Split Type) 1.5 TR/2.0 TR Capacity and of any make including taking out unserviceable Capacitor from AC complete all as specified and as directed. |
| 60 | M&L in replacement Capacitor Starting 80 mfd – 120 mfd suitable for old ones AC (Window/Split Type) 1.5 TR/2.0 TR Capacity and of any make including taking out unserviceable Capacitor from AC complete all as specified and as directed. |
| 61 | M&L in replacement Fan Motor Blades AC (Window/Split type) 1.5/2.0 TR capacity including taking out unserviceable Blades of Fan Motor from AC complete all as specified and as directed. |
| 62 | M&L in replacement Fan Motor Capacitor 4 mfd of suitable for new/star rated AC (Window/Split Type) 1.5/2.0TR capacity including taking our unserviceable Fan motor capacitor from AC complete all as specified and as directed. |
| 63 | M&L Fan Motor in replacement Capacitor 6 mfd suitable for old ones AC (Window/Split Type) 1.5/2.0/3.0TR capacity including taking our unserviceable Fan motor capacitor from AC complete all as specified and as directed. |
| 64 | M&L in replacement Single Pole Contactor 25A Capacity, MR 11W type as approved suitable for AC (Split Type) including taking out unserviceable Single Pole Contactor complete all as specified and as directed. |
| 65 | M&L in replacement Starting Relay of AC (Window/Split Type) 1.5 TR/2.0TR Capacity including taking out unser-viceable Starting Relay from AC complete all as specified and as directed. |
| 66 | M&L in replacement Strainer with Capillary Tube of AC Window/ Split Type) 1.5 TR/2.0/3.0 TR Capacity (including taking out unserviceable Strainer with Capillary Tube from AC complete all as specified and as directed. |
| 67 | M&L in replacement Thermostat Switch of AC (Window/Split Type) 1.5 TR/2.0 TR Capacity including taking out unserviceable Thermostat Switch from AC complete all as specified and as directed. |
| 68 | S&F in replacement cooling coil suitable for window type room AC 1.5/2 ton including taking out unserviceable cooling coil of capacity 1.5/2 ton as per sample. |
| 69 | S&F in replacement Condensing coil suitable for window type AC 1.5/2 ton including taking out unserviceable Condensing coil of capacity 1.5/2 ton as per sample. |
| 70 | S&F in replacement Condensing coil suitable for split type AC including taking out unserviceable Condensing coil of capacity upto 2 ton. |
| 71 | S&F in replacement cooling coil suitable for split type AC including taking out unserviceable cooling coil up to capacity 2 ton. |
| 72 | Suuply & Fix in replacement of Hermitacally sealed compressor for split/window type AC capacity 1.5 Ton. |
| 73 | All same as per ser item No. 22 here-in-before but for split/ window type AC capacity 2.0 Ton. |
| 74 | M&L in replacement PCB with remote and sensor for window type AC up to 2 Ton capacity including taking out unserviceable PCB complete all as specified and directed . |
| 75 | M&L in replacement PCB with remote including sensor for Split type AC upto 2.0 ton capacity including taking out unserviceable PCB complete all as specified and directed . |
| 76 | S&F in replacement wiring kit suitable for 1.5 to 2.0 ton capacity AC complete including taking out unserviceable wiring kit all as specified and directed. |
| 77 | S&F in replacement gas charging pin valve complete including taking out unserviceable pin valve all as specified and directed. |
| 78 | Taking out window type AC complete unit from any height/ any floor and shifting to another location in the same or other building in the complex including refixing of the unit complete all as specified and directed. |
| 79 | Taking out split type AC complete indoor and outdoor unit from any height/ any floor including pumping down the gas into the compressor by controlling the suction and discharge valves , disconnecting the suction and dischagre copper piping and shifting to another locatiion in the same or other building in the complex including refixing of the unit complete all as specified and directed. |
| 80 | Supply and charging the gas refrigerant R22 (including refrigerant) of window type AC upto 2 ton capacity including testing after application of nitrogen gas pressure to find out any leakage, brazing and stopping of all leakage detected, re-application of nitorgen pressure to ensure leak proof gas circulator system flushing out the nitrogen gas complete all as specified and directed. |
| 81 | All as per ser item No. 30 here-in-before but R- 410/32 for split type AC up to 2 TR capacity complete. |
| 82 | S&F in replacement Hermatically Sealed compressor for 300 Ltrs capacity Deep freezer including bracing the sunction and discharge lines complete all specified and dircted. |
| 83 | S&F in replacement of casing of window type AC including company fitted condensing & cooling coil suitable for 1.5 TR capacity complete including PCB except compressor complete. |
| 84 | M&L for replacement of split valve ¼” for split AC up to 2.00 ton capacity complete all as specified and directed. |
| 85 | All as per ser item No. 34 here-in-before but 1/2\\"complete all as specified and directed. |
| 86 | S&F in replacement compressor shut off valve 3/8\\" for split AC up to 2.00 ton capacity complete all as specified and directed. |
| 87 | S&F in replacement compressor shut off valve 5/8\\" for split AC up to 2.00 ton capacity complete all as specified and directed. Please Enable Macros to View BoQ information |
| 88 | S&F in replacement compressor shut off valve 5/8\\" for split AC up to 2.00 ton capacity complete all as specified and directed. Please Enable Macros to View BoQ information |