| 1 | Disconnecting the existing LT UG cable of any size and taking out the damaged electric UG cable from trenches all as specified and directed by Engr-in-chargeNote : earth work shall be maesure and paid seperatly |
| 2 | Supply, lay and testing XLPE, insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 sqmm, 3.5 core cross sectional area laid in trenches/ poles/ ducts/ pipes or through sleeves etc., including connecting/ jointing with lugs complete all as specified and directed by Engr-in-Charge. |
| 3 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out for laying of pipe cables etc,. and getting out complete all as specified and directed |
| 4 | Returing filling in, including spreading levelling, watering and well ramming in layers not exceeding 25cm thick with earth obtained from excavation complete all as specified and as directed. |
| 5 | Removal of surplus excavated soil to a distance n. exc. 50 m and depositing where directed at a level n. exc. 1.5 m above starting point complete, all as specified and directed by engg in charge. |
| 6 | Material and labour for dry river washed and screened dry sand for filling in trenches/ ground 8cm thick before laying of cable and 15 cm thock after laying of cable, stretching and testing the cable Note:- Punned thickness shall only be measured and paid. |
| 7 | Supplying and laying un-reinforced precast concrete cable cover, class LV , type 1 , size 250mm x 150mm x 40mm complete , all as specified and directed by engr-in-charge. |
| 8 | Supply and fix light grade galvanised iron tube 80 mm bore with all fittings and fixed to walls / ceiling or laid in floor, pole or laid in trenches or road crossings all as specified and as directed. |
| 9 | Supply and fixing street light fitting of LED street light 60 watt, complete with single piece die cast aluminum allow housing IP65/IP66 complete with faceted anodised aluminium reflector heat resistant toughened glass cover and LED lamps and fixed on street light poles/swan neck poles by making suitable fixing arrangement complete all as directed. Make: Philips / Crompton / Havells / Orient |
| 10 | Supply and fixing LED flood light 210 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. Make: Philips / Havells / Crompton |
| 11 | M&L for fixing of handhole cover for street light rectangle pole as per sample |
| 12 | M&L for fixing of street light pole terminal plate and other connected items all as specified and directed |
| 13 | M&L for fixing of PVC insulated flexible copper conductor 3 core, 2.5 sqmm cable for street light pole from pole terminal to street light with and including all necessary fitting accessories all as specified and directed Make of cable : Gloster/Finolex/Polycab/Plaza/Havells |
| 14 | Material & labour in rep for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 metre deep below ground level) vertically, with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanized iron earth strip of size 32 x 6mm by means of nuts, bolts, washers of GI steel all as shown on electrical plate No 3 of MES schedule part I-2009 connected to earthing test point & to main switch board and testing on completion with and including necessary excavation and earth work in any type soil, earth lead connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, internal surface of concrete shall be given 10mm thick plaster in CM 1:4, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover, reinforced with 8mm dia deformed or TMT bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh and 40mm dia GI light grade earth lead protection pipe etc complete all as specified and directed. NOTE: - (i) Earth strip and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item (ii) Any joints in earth strip from earth electrode to test point shall not be allowed / permitted. |
| 15 | M&L for painting external surface of poles complete with cross arm/bracket etc with two coats of white and blue synhtetic enamel paint in alternate strip up to 1.50 Mtr from top of base/ coping (each strip of 30 cm) and remaining portion shall be painted with two coats of aluminium paint of LT pole including preparation of surface and marking pole No complete all as specified and directed. |
| 16 | S & F infrared sensor based NATURE SWITCH three phase 8 kw consisting of power contactor, AC conforming to IEC - 60947 - 4 - 1/ IS - 13947 - 4 - 1 for load switching and terminal blocks. The enclosure is made of UV stabilized, FR grade special moulding compound to provide a rust proof, electric shock proof, termite proof, outdoor mountable electrically insulating body capable of enduring solar radiation in the outdoor & suitable for mounting. The enclosure is provided with mounting brackets, cable glands, openable door with lock and key. Selectable options for duration based switching OFF as well as override facility for maintenance shall be available complete all as specified and directed |
| 17 | S&F bracket made of 32 mm bore GI pipe light grade ISI marked 1.20 mtr long bent to shape with 2 Nos MS clamp made of 25x3mm FI with nuts, bolts and washers suitable for off size HT/LT poles duly painted with two coats of aluminium paint over one coat of red oxide primer including dismantling of existing bracket and refixing old/new fitting complete all as specified and directed. |
| 18 | M&L in replacement for clamp made out of FI 25x3 mm suitable to be fixed on pole for holding street light braket of any size eith and including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and incluing two coats of synthetic enamel paint over a coat red oxide primer after preparation of surfaces complete all as specified and directed . |
| 19 | Supply, installation, testing and commissioning of outdoor weatherproof junction box of size 28 cm × 21 cm × 11 cm made of UV-stabilized Fiber Reinforced Plastic (FRP), white colour, with minimum IP65 protection conforming to Bureau of Indian Standards, complete with hinged gasketed door, suitable wall mounting arrangement, weatherproof cable glands, and one no. 6 Amp SP MCB (6 kA breaking capacity) with internal FRLS copper wiring, earthing provision and all necessary accessories. |
| 20 | Supply, installation, testing and commissioning of 12.8 V, 150 Ah Lithium Iron Phosphate (LiFePO₄) solar battery with inbuilt BMS (protection against overcharge, deep discharge, short circuit and temperature), conforming to IS 16046 of Bureau of Indian Standards, complete with rugged weatherproof enclosure, suitable mounting arrangement, interconnections and all required accessories. |
| 21 | Supply, fabrication and erection of battery stand for pole mounting including all welding works using suitable MS sections, complete with cutting, grinding, proper alignment, drilling, bolting/clamping arrangement for pole fixing, application of anti-rust primer and two coats of synthetic enamel paint, and all necessary materials, labour, tools and accessories for a complete installation. |
| 22 | Total contract sum shall be calculated after deduction of schedule of credit amount of Rs. 31,510.00 Please Enable Macros to View BoQ information |