| 1 | Dismantling Wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/slabs/blankets, any thickness, including cover fillets complete all as specified and as directed. |
| 2 | S&F solid PVC Wall Lining consisting of 5mm thick Plain colour PVC sheet inclusive of solvent cement and fixing at site on PVC frame as per specifications and drawing complete all as specified and as directed. |
| 3 | S&F 5mm thick PVC sheet fillet of width 35mm for wall paneling inclusive of fixing on to wall to make PVC Frame as per specification and drawing complete all as specified and as directed. |
| 4 | M&L for 2nd class hard wood, in scantlings, clean sawn timber as in un framed work and including dismaling of old ones,complete all as specified and as directed. |
| 5 | M&L for preparation of new wood or wood based surface of any description exceeding 10 cm width or girth and applying two coats of synthetic enamel paints over a coat of pink primer complete all as specified and as directed. |
| 6 | S&F suspended false ceiling using E-grid 2430, 180 GSM (exposed ceiling suspension system ) of grid size 600mmx600 mm with main runner 38 mm x 24 mm and wall angle 24mm x 24mm using 4mm thick High Pressure stean Crude Everest Non Asbestos Fiber Cement plain Board (E-Board Classic) in & including a grid of GI system duly suspended with 4mm dia GI wire hanger fixed with providing positions for light fixtures,air conditioning diffuser and ducts ,sprinkler ,smoke detectors etc.The main runners to be secured to structural soffits by hanger @ 1220 mm maximum c/c. the last hanger at the end of each main runner should not be placed at more than 450mm from the adjucent wall,Flush fitting 1220 mm cross tee to be interlocked between main runners @ 610mm c/c,so as to form 600mm x 600 mm grid complete all as specified and as directed. |
| 7 | Taking down carefully any type of point wiring (light, fan, bell, socket or power), complete excluding fittings but including switches, ceiling roses, pendants, regulators, sockets, etc. and making good disturbed surfaces of walls, ceiling, floors etc to match with existing surface complete all as specified and as directed. |
| 8 | M&L for point wiring with 1.5 sqmm, single core, PVC insulated and PVC unsheathed FR-LSH cable, 1100 volts grade IS-694 marked, with multistranded copper conductors and earth continuity wire with 1.5 Sqmm copper conductor cable (including connecting to earth dolly) laid/fixed with and including PVC Casing and Caping on walls/ceiling, and with PVC switch board for mounting switches/socket etc for one light/fan/exhaust fan point controlled by one number one way 5 Amp switch complete all as specified and as directed. |
| 9 | All as per item serial No 8 here-in-before but for One 3 pin 5 Amp socket combination on independent board with other switches. |
| 10 | All as per item serial No 8 here-in-before but with 2.5 Sqmm single core multistranded copper conductor cable and earth continuity wire with 2.5 Sqmm cable for 6 pin 15 Amp socket outlet on independent board. |
| 11 | S & F switch piano, flush type single pole one way 5 Amps 230 volt complete all as specified and as directed. |
| 12 | S & F switch socket combination outlet 3 pin, 2-in-1, 5 Amp flush type complete all as specified and as directed. |
| 13 | S & F switch socket combination, multipurpose, 2 in 1, 3 pin, 15 & 16 Amp flush type complete all as specified and as directed. |
| 14 | S & F ceiling rose surface bakelite, 65x50mm three terminal complete all as specified and as directed. |
| 15 | S & F LED tube fittings1x20W, 220V, with necessary fittings and fixtures including LED tube light and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose, complete all as directed. |
| 16 | S&F LED luminaire of size 600mmx600mm, 35/36 watt, 220V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders and LED lamp suitable for roo ceiling including connecting up with driver three core flexible copper conductor of suitable size, complete all as specified and as directed. |
| 17 | S & F exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300m complete all as specified and as directed. |
| 18 | S & F in repairs single pole & neutral DBs 8 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 200 Amp rating copper bus bar complete all as specified and as directed. |
| 19 | S & F in repairs single pole & neutral DBs 4 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 200 Amp rating copper bus bar complete all as specified and as directed. |
| 20 | S&F MCBs, SPN/DP 40 to 63 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed. |
| 21 | S&F MCBs, SP 6 to 32 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed. |
| 22 | M&L for Sub main wiring with 2 runs of 6.0 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dia non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 6.0 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and type of conduit complete all as specified and directed. |
| 23 | M&L for plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate at a depth not less than 1.5 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth lead wire 4 mm dia or 8 SWG bolted (with GI nuts, bolts & check nuts) and earth plate electrode at one end and connected to main switch board/ DBs etc. at the other, earth strip encased(protected) in and including 15 mm bore GI pipe medium grade with all fittings from top of electrode to main switch board/ DBs etc fixed with and including 25 x 6mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-2 using 12 mm graded crushed stone aggregate, RCC cover, funnel, wire mesh including necessary excavation and earth work complete all as specified and shown in electrical plate No 3 of SSR Pt-I including taking down of old one, complete all as specified and directed. Please Enable Macros to View BoQ information |