| 1 | S/E of Section Double pole structure on ST pole 410 SP-62 with 1/6 over length of poles grounted with cement concrete in 1:3:6 (one cement:3 coarse sand :6 Stone balleast) including plingthing of pole 30 cm above grade level, plastering of plinth including excavation & back filling etc. The double pole structure consist of 100X50X6mm 2.50 mtr. & 75X40X6mm 2.50 mtr. M.S. channel with M.S. clamp packing piece Nuts Bolts etc. The rates includes all materials labour T&P etc. required for proper completion of work as per direction of E/I. YEIDA SOR-51. |
| 2 | S/F of 33 KV pin insulator with pin on poles or any where specified including bolts to fasten on pole cap/cross arm with the poles. (Jaishree, BHEL,RR, Hindustan make) Analysis of rate |
| 3 | S/F of cross arm made of 100X50 mm M.S. channel 2.5 mtr. long on poles with packing, piece, M.S. clamp, Nut bolts etc. complete in all respect. Analysis of rate YEIDA SOR-30 |
| 4 | Painting of the electric pole with two coat of Al-paint over red oxide primer complete in all respect. (PS-634) |
| 5 | Supply & fixing of MS rod for earthing with 2.5 m long, solid, 20 mm dia hot dipped galvanised MS rod buried till the top reaches 1.7 mts. Below the GL complete with bolts & nuts & GI earth wire 7/14. Analysis of rate YEIDA SOR-52 |
| 6 | S/F of G.I Pipe 150MM dia \\"B\\"class Zindal/tata make including reqired material T&P etc.complete in all respects. Analysis of rate YEIDA SOR-65 |
| 7 | S/L of 200mm dia. H.D.P.E. pipe for drawing of power cable across the road by drilling of 220mm dia. at 1mtr. below the road level thereby doing the work of providing HDPE pipe.PE-63/PN-8 Trenchless Method (For above 400 Sqmm. 33KV XLPE cable). Analysis of rate YEIDA SOR-54 |
| 8 | Supply, delivery, laying testing & commissioning of 33KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semin conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 33 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job (CCI (Bombay/Nashik), Fort Gloster (Calcutta / Baripara), Asian (Thane / Silvasha), Universal (Satna), Nicco (Calcutta), ICL (Rajpura), Diamond, Havells make (a)3CX400 Sq.mm. Analysis of rate YEIDA SOR-03 |
| 9 | Supply, Delivery, Installation, Testing & Commissioning of 33KV, Out door type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) Analysis of rate a) b) 3CX240/300/400 Sq.mm Outdoor type YEIDA SOR- 09 |
| 10 | Supply, Delivery, Installation, Testing & Commissioning of Straight through cable jointing kit for 33KV XLPE armoured cable jointing. Complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) Analysis of rate3CX400 Sq.mm. YEIDA SOR-08 |
| 11 | Supply, delivery, laying testing & commissioning of 11KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 11 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI (Bombay/Nashik), Fort Gloster (Calcutta / Baripara), Asian (Thane / Silvasha), Universal (Satna), Nicco (Calcutta), ICL (Rajpura), Diamond, Havells make &KEI. Analysis of rates OF yeida sor -2, (a) 3CX300 Sqmm. |
| 12 | Supply, Delivery, Installation, Testing & Commissioning of 11 KV Out door type cable termination kit of 3 core cable for cable termination at the panel & transformer complete in all respects as required for proper completion of work. (650mm length). Analysis of rates (make Raychem/C.C.I./Frontec) (a).3CX240/300 Sq.mm. YEIDA SOR-5 |
| 13 | Supply, Delivery, Installation, Testing & Commissioning of 11 KV indoor type cable termination kit of 3 core cable for cable termination at the panel & transformer complete in all respects as required for proper completion of work. (650mm length). Analysis of rates (make Raychem/C.C.I./Frontec) (a).3CX240/300 Sq.mm. YEIDA SOR-5 |
| 14 | S/E of ‘D’ clamps 50X6mm. flat iron on steel tubular pole / steel rail pole with bolts, nuts etc complete in all respect including with aluminium paint. (PS-623) PWD -2018 |
| 15 | Supply, Sagging, tensioning, jointing and bending of suitable size ACSR conductor conferming to I.S. specification including cost of aluminium wire and jointing sleeve required. The rates includes cost of material, labour, T&P etc. required for proper completion of work as per direction of E/I. P.S.-627, a) dog conductor. Please Enable Macros to View BoQ information |